Raypak 0135B, 0030B, 0090B manual Venting Connections, Fig. #8198.0

Page 5

2)When the boiler is installed in a confined space such as a utility room or closet (Models 0030,0042 and 0066 only), where all air is supplied from inside the building, the boiler room must be provided with two openings, each one having a minimum net free area, in square inches as follows:

 

Model

 

Sq. In. of Free Area

0030, 0042 & 0066

100

One opening shall be within 12" of the top, and the other opening within 12" of the floor. If additional gas appliances are installed in the same space, the total input of all gas appliances installed in the same space, must be considered in the calculation. Refer to Sec. 5.3.5 of the latest edition of the National Fuel Gas Code for additional requirements.

Location of the openings is the same as in the previous case - that is, within 12" of the top, and within 12" of the bottom of the enclosure. If horizontal ducts are used, the area must be doubled and the duct area shall not be less than the area of the openings they connect, and in no case shall the smallest dimension be less than 3".

VENTING CONNECTIONS

These boilers have built-in drafthoods. Vent piping the same size or larger than the drafthood outlet is recommended; however, when the total vent height (drafthood outlet to vent terminal) is at least ten (10) feet, the vent pipe size may be reduced by one size only as specified in Chapter 10 of the latest edition of the National Fuel Gas Code, ANSI Z 223.1. As much as possible, avoid long horizontal runs of vent pipe and too many elbows. If installation requires horizontal runs, the vent pipe must have a minimum of 1/4 inch per foot rise and should be supported at not less than five foot intervals. Maximum vent connector horizontal length shall be 1-1/2 feet (18 inches) for each inch of connector diameter as follows.

Model

Vent Connector

Max Horizontal

 

Diameter

Length - FT

30 & 42

4"

6'

66 & 90

5"

7.5'

135

6"

9'

180

7"

10.5'

Fig. #8198.0

NOTE: If louvers, grills or screens are used on the openings, obtain the net free area requirements from their supplier or manufacturer. If the design free area of a louver is not known nor available, it shall be assumed that wood louvers will have 20-25percent free area and metal louvers will have 60-75percent free area as shown in Sec. 5.3.5 National Fuel Gas Code.

3)If the boiler room is located against an outside wall and air openings can communicate directly with the outdoors, the two openings on the outside wall must each have a net free area as follows:

 

Model

 

(Sq. In.) Net Free Area

 

 

 

 

 

0030 & 0042

12

 

0066

 

18

 

0090

 

24

 

0135

 

35

 

0180

 

45

 

Gas vents supported only by the flashing and extend- ing above the roof more than five feet should be securely guyed or braced to withstand snow and wind loads. We recommend use of insulated vent pipe spacer through the roofs and walls.

For protection against rain or blockage by snow, the vent pipe must terminate with a listed vent cap which complies with the local codes or, in the absence of such codes, to the latest edition of the National Fuel Gas Code, ANSI Z 223.1.

The discharge opening must be a minimum of two feet vertically from the roof surface and at least two (2) feet higher than any part of the building within ten (10) feet. Vent stack shall be at least five (5) feet in vertical height above the drafthood outlet. The vent cap location shall have a minimum clearance of four (4) feet horizon- tally from, and in no case above or below, unless a 4-foot horizontal distance is maintained, from electric meters, gas meters regulators and relief equipment.

5

Image 5
Contents For Your Safety Installation Operating InstructionsContents Receiving Equipment General SpecificationsSpecifications and Dimensions Code Requirements Installation ProceduresMounting Base ClearancerequirementsFig. #8198.0 Venting ConnectionsFig.# Common VentsLocation Vent Damper InstallationMounting Installing the Vent Damper in Horizontal & Vertical VentD80D General Wiring Diagram System Schematic Ladder Diagram Vent Damper Position IndicatorVent Damper Operation Flair DamperConnection Diagram Water Connections & System Piping GAS Supply ConnectionsGaspressure SINGLE-ZONEPIPING Piping DiagramsZone Heating with Indirect Domestic HOT Water Supply Multiple Zones with Zone Valves Fig.# Electrical WiringWiring Diagram KEY Page Page Wiring Diagram Single-Zone Taco Valve Wiring Diagram System with 3 Zone Pumps Fig. #2223.2e Wiring Diagram Standing Pilot With Low Water Cut-off Device General Location of Controls Servicing ProceduresControl BOX Component Locations Models 135 Sequence of Operation Intermittent Ignition Device IIDWhat to do if YOU Smell GAS START-UPPROCEDURESFor Automatic Ignition Models Honeywell Pilot Robertshaw PilotTo Turn OFF GAS to Boiler SHUT-DOWNPROCEDUREFor Automatic Ignition Systems Inspectionprocedures Inspection Procedures BurnersSafe SHUT-DOWN Tests Limit Action Flame FailureRepairprocedures Raypak Tube Cleaning KITCombustion Chamber Removal Heat Exchanger RE-ASSEMBLYImportant Notice Troubleshooting GuidePiping ADJUSTMENT/REPLACEMENTOF Components RAYPAK, INC Replacement Parts ListPage Page Page Limited Parts Warranty