2)When the boiler is installed in a confined space such as a utility room or closet (Models 0030,0042 and 0066 only), where all air is supplied from inside the building, the boiler room must be provided with two openings, each one having a minimum net free area, in square inches as follows:
| Model |
| Sq. In. of Free Area |
0030, 0042 & 0066 | 100 |
One opening shall be within 12" of the top, and the other opening within 12" of the floor. If additional gas appliances are installed in the same space, the total input of all gas appliances installed in the same space, must be considered in the calculation. Refer to Sec. 5.3.5 of the latest edition of the National Fuel Gas Code for additional requirements.
Location of the openings is the same as in the previous case - that is, within 12" of the top, and within 12" of the bottom of the enclosure. If horizontal ducts are used, the area must be doubled and the duct area shall not be less than the area of the openings they connect, and in no case shall the smallest dimension be less than 3".
VENTING CONNECTIONS
These boilers have
Model | Vent Connector | Max Horizontal |
| Diameter | Length - FT |
30 & 42 | 4" | 6' |
66 & 90 | 5" | 7.5' |
135 | 6" | 9' |
180 | 7" | 10.5' |
Fig. #8198.0
NOTE: If louvers, grills or screens are used on the openings, obtain the net free area requirements from their supplier or manufacturer. If the design free area of a louver is not known nor available, it shall be assumed that wood louvers will have
3)If the boiler room is located against an outside wall and air openings can communicate directly with the outdoors, the two openings on the outside wall must each have a net free area as follows:
| Model |
| (Sq. In.) Net Free Area | |
|
|
|
|
|
0030 & 0042 | 12 |
| ||
0066 |
| 18 |
| |
0090 |
| 24 |
| |
0135 |
| 35 |
| |
0180 |
| 45 |
|
Gas vents supported only by the flashing and extend- ing above the roof more than five feet should be securely guyed or braced to withstand snow and wind loads. We recommend use of insulated vent pipe spacer through the roofs and walls.
For protection against rain or blockage by snow, the vent pipe must terminate with a listed vent cap which complies with the local codes or, in the absence of such codes, to the latest edition of the National Fuel Gas Code, ANSI Z 223.1.
The discharge opening must be a minimum of two feet vertically from the roof surface and at least two (2) feet higher than any part of the building within ten (10) feet. Vent stack shall be at least five (5) feet in vertical height above the drafthood outlet. The vent cap location shall have a minimum clearance of four (4) feet horizon- tally from, and in no case above or below, unless a
5