Raypak 0030B, 0090B, 0135B manual For Automatic Ignition Systems, Fig.#

Page 27

CAUTION: Should overheating occur or the gas supply fails to shut-off, DO NOT turn off or disconnect the electrical supply to the pump. Instead, shut-off the gas supply at a location external to the boiler. Failure to observe this precaution may aggravate the overheated condition resulting in possible damage to the boiler and injury to the user.

SECTION 4. Testing the Ignition Safety Shut-off. The ignition system safety shut-off must be tested by conducting the following tests:

For Standing Pilot Systems

a.With the main burners on, remove the pilot adjustment cover screw.

* NOTE: There is no pilot adjustment cover on Robertshaw 7200 gas valve.

b.Insert a small slot screw driver and turn the

adjustment screw clockwise until pilot flame goes out. Note and count number of turns made.

c.Gas valve will shut-off main burners after about three (3) minutes. If the gas valve will not shut-off, follow the instructions "To Turn Off Gas To Boiler" and call service technician or your gas supplier.

d.Return pilot adjustment screw counter-clock-

wise , using the same number of turns as in step (b).

FOR AUTOMATIC IGNITION SYSTEMS

Intermittent Ignition (IID)

1.Turn on power to the ignition systems and turn gas supply off at the gas valve.

2.Check ignition module as follows:

a.Set the thermostat or controller above room temperature to call for heat.

b.Watch for continuous spark at the pilot burner.

c.Time the spark operation. Time must be within the lockout timing period (15 or 90 seconds).

d.Turn thermostat down to end call for heat and wait 60 seconds on lockout models before beginning step 3.

3.Turn on gas supply.

4.Set thermostat or controller above room tempera- ture to call for heat.

5.Systems should start as follows:

a.Spark will turn on and pilot gas valve will open at once. Pilot burner should ignite after gas reaches the pilot burner.

b.Spark ignition should cut-off when pilot flame is established.

c.Main gas valve should open and main burner should ignite after gas reaches the burner port.

3

2

1

 

 

PILOT ADJ

O F F

S E T P I L O T O N

Pilot Adjustment

Fig.# 8935.0

ROBERTSHAW 7200 GAS VALVE

(Models 90, 135 & 180)

e.Replace pilot adjustment cover screw, then follow the lighting instructions to get boiler ready for operation.

27

Image 27
Contents For Your Safety Installation Operating InstructionsContents General Specifications Specifications and DimensionsReceiving Equipment Clearancerequirements Installation ProceduresCode Requirements Mounting BaseFig. #8198.0 Venting ConnectionsFig.# Common VentsLocation Vent Damper InstallationInstalling the Vent Damper in Horizontal & Vertical Vent D80D General Wiring DiagramMounting Flair Damper Vent Damper Position IndicatorSystem Schematic Ladder Diagram Vent Damper OperationConnection Diagram GAS Supply Connections GaspressureWater Connections & System Piping SINGLE-ZONEPIPING Piping DiagramsZone Heating with Indirect Domestic HOT Water Supply Multiple Zones with Zone Valves Fig.# Electrical WiringWiring Diagram KEY Page Page Wiring Diagram Single-Zone Taco Valve Wiring Diagram System with 3 Zone Pumps Fig. #2223.2e Wiring Diagram Standing Pilot With Low Water Cut-off Device Sequence of Operation Intermittent Ignition Device IID Servicing ProceduresGeneral Location of Controls Control BOX Component Locations Models 135What to do if YOU Smell GAS START-UPPROCEDURESFor Automatic Ignition Models Honeywell Pilot Robertshaw PilotTo Turn OFF GAS to Boiler SHUT-DOWNPROCEDUREFor Automatic Ignition Systems Flame Failure Inspection Procedures BurnersInspectionprocedures Safe SHUT-DOWN Tests Limit ActionRepairprocedures Raypak Tube Cleaning KITCombustion Chamber Removal Heat Exchanger RE-ASSEMBLYImportant Notice Troubleshooting GuidePiping ADJUSTMENT/REPLACEMENTOF Components RAYPAK, INC Replacement Parts ListPage Page Page Limited Parts Warranty