Raypak 0030B, 0090B, 0135B manual ADJUSTMENT/REPLACEMENTOF Components, Fig.#

Page 33

ADJUSTMENT/REPLACEMENTOF

COMPONENTS

DANGER - SHOCK HAZARD

Make sure electrical power to the boiler is disconnect- ed to avoid potential serious injury or damage to com- ponents.

1.Gas Valve Replacement

a)Shut-off electrical power and gas supply to the

boiler.

b)Remove gas piping to gas valve inlet.

c)Disconnect wiring connections, pilot tubing (when present).

d)Remove screws (2) holding the burner tray.

e)Slide burner tray out.

f)Remove gas valve bracket screws and bracket.

g)Unscrew gas valve from gas pipe.

h)Reverse above procedure to re-install.

2.Pilot Burner Cleaning or Replacement (Standing Pilot)

a)Shut-off electrical power and gas supply to the boiler.

b)Disconnect gas piping to gas valve.

c)Disconnect wiring connections to gas valve.

d)Remove screws (2) holding the burner tray.

e)Slide burner tray out.

f)Remove screw holding pilot lighter tube.

g)Remove screws (2) holding pilot bracket on the burner tray.

h)Disconnect thermocouple and pilot tubing from the gas valve.

i)Remove pilot burner from pilot bracket.

j)Remove pilot orifice and blow away lint or dirt. Clean with wire or small brush.

NOTE: Make sure pilot orifice is clear, but do not enlarge the hole.

k) Reverse above procedure to re-install.

HONEYWELL PILOT

ROBERTSHAW PILOT

PILOT

PILOT

AIR

OPENING

ORIFICE

ORIFICE

Fig.# 8045.2

Fig.# 8102.1

3.Flame Roll-out Switch Replacement

a)Shut-off electrical power to the boiler.

b)Remove wiring connections to switch.

c)Remove screws (2) holding the switch.

d)Reverse above procedure to re-install.

4.Vent Thermal Switch Replacement

a)Shut-off electrical power to the boiler.

b)Remove wiring connections to switch.

c)Remove the screws (2).

d)Reverse above procedure to re-install.

5.Ignition Module Replacement

a)Shut-off electrical power to the boiler.

b)Remove control cover screws and open control compartment.

c)Disconnect wiring connections to module.

d)Remove screws (2) holding module.

e)Reverse above procedure to re-install.

6.Transformer Replacement

a)Shut-off electrical power to the boiler.

b)Remove control cover screws and open control compartment.

c)Disconnect wiring connections from trans- former leads.

d)Remove screws (2) holding transformer.

e)Reverse above procedure to re-install.

7.Pump Relay Replacement

a)Shut-off electrical power to the boiler.

b)Remove control cover screws and open control compartment.

c)Disconnect wiring to the relay.

d)Remove screws (2) holding relay.

e)Reverse above procedure to re-install.

8.High Limit Control

a)Shut-off electrical power to the boiler.

b)Remove control cover screws and open control compartment.

c)The control is factory set at 180°F. To adjust to setting, use a small screw driver and turn dial

clockwise to lower the temperature or

counter-clockwise

to raise the setting.

d)To replace the limit control, disconnect the wir- ing connections.

e)Remove screws (2) holding the limit control.

f)Remove upper access panel.

g)Remove the wedge or retaining clip holding the sensing bulb in the control well in the in/out header.

h)Pull out the sensing bulb carefully from the control well.

i)Remove the limit control with capillary from unit.

j)Reverse above procedure to re-install.

33

Image 33
Contents For Your Safety Installation Operating InstructionsContents General Specifications Specifications and DimensionsReceiving Equipment Code Requirements Installation ProceduresMounting Base ClearancerequirementsFig. #8198.0 Venting ConnectionsFig.# Common VentsLocation Vent Damper InstallationInstalling the Vent Damper in Horizontal & Vertical Vent D80D General Wiring DiagramMounting System Schematic Ladder Diagram Vent Damper Position IndicatorVent Damper Operation Flair DamperConnection Diagram GAS Supply Connections GaspressureWater Connections & System Piping SINGLE-ZONEPIPING Piping DiagramsZone Heating with Indirect Domestic HOT Water Supply Multiple Zones with Zone Valves Fig.# Electrical WiringWiring Diagram KEY Page Page Wiring Diagram Single-Zone Taco Valve Wiring Diagram System with 3 Zone Pumps Fig. #2223.2e Wiring Diagram Standing Pilot With Low Water Cut-off Device General Location of Controls Servicing ProceduresControl BOX Component Locations Models 135 Sequence of Operation Intermittent Ignition Device IIDWhat to do if YOU Smell GAS START-UPPROCEDURESFor Automatic Ignition Models Honeywell Pilot Robertshaw PilotTo Turn OFF GAS to Boiler SHUT-DOWNPROCEDUREFor Automatic Ignition Systems Inspectionprocedures Inspection Procedures BurnersSafe SHUT-DOWN Tests Limit Action Flame FailureRepairprocedures Raypak Tube Cleaning KITCombustion Chamber Removal Heat Exchanger RE-ASSEMBLYImportant Notice Troubleshooting GuidePiping ADJUSTMENT/REPLACEMENTOF Components RAYPAK, INC Replacement Parts ListPage Page Page Limited Parts Warranty