Service Procedures
Continued
14.Dry fan thoroughly.
15.Replace fan on motor shaft. Place set- screw on fat of shaft. See chart in Figure
10 for distance of fan hub from end of motor shaft. Tighten setscrew firmly (40-
50 inch-pounds).
16.Remove screws securing motor mount to shell.
17.Pull motor and fan from shell. Turn motor and fan around. Carefully place back in shell. Note: Fan will go into shell first.
18.Line up mounting holes in shell with holes on motor mount. Replace 4 screws through shell and motor mount.
19.Route motor wires through hole in top of shell (see Figure 7, page 8).
20.Reconnect motor wires to the same posts on terminal block as removed in step 3, page 8 (see Figure 7, page 8).
21.Replace top cover.
22.Replace fan guard.
Setscrew
Fan
Motor
Shaft
Figure 9 - Fan, Motor Shaft and Setscrew
Identification
Model | Distance A |
|
55 | 0.19" (4.8 mm) |
|
85 0.5" (12.7 mm)* or | Fan | |
| 0.9" (22.9 mm)* |
|
125 0.5" (12.7 mm)* or |
| |
| 0.9" (22.9 mm)* | A |
170 | 0.25" (6.4 mm) | Motor |
* Depending |
| |
on Motor Shaft Motor | Hub | |
| Shaft |
Setscrew
Specifications
All Models
•Propane/LP Gas
•Gas Supply Pressure to Regulator: Max - Bottle Pressure, Min - 25 psig (172.4 kPa)
•Gas Supply Pressure Regulator Out: 20 psig (137.9 kPa)
•Electrical Input: 120V, 60 Hz, 1Ø, 3a
•Direct Spark Ignition
•Minimum Ambient Temp. Rating: 0° F
55,000 Btu/Hr Models
•30 - 55,000 Btu/Hr (8.8 - 16.1 kW)
•Fuel Consumption:
1.4 - 2.6 pounds/hr (0.70 - 1.28 kg/hr)
•Primary Flame Control: Thermocouple operated gas valve
•Heated Air Output: 300 CFM (8.49 m3/min)
85,000 Btu/Hr Models
•50 - 85,000 Btu/Hr (14.6 - 25.0 kW)
•Fuel Consumption:
2.3- 3.9 pounds/hr (1.04 - 1.77 kg/hr)
•Primary Flame Control: Thermocouple operated gas valve
•Heated Air Output: 350 CFM (9.91 m3/min)
125,000 Btu/Hr Models
•75 - 125,000 Btu/Hr (21.9 - 36.6 kW)
•Fuel Consumption:
3.5- 5.8 pounds/hr (1.59 - 2.63 kg/hr)
•Primary Flame Control: Thermocouple operated gas valve
•Heated Air Output: 350 CFM (9.91 m3/min)
170,000 Btu/Hr Models
•125 - 170,000 Btu/Hr (36.6 - 49.8 kW)
•Fuel Consumption:
5.8- 7.9 pounds/hr (2.63 - 3.6 kg/hr)
•Primary Flame Control:
DSI Flame Rectification
•Heated Air Output: 450 CFM (12.74 m3/min)