Monessen Hearth HBDV400N/PV7, HBDV300N/PV7 manual Twist Lock Pipes, How to Use the Vent Graph

Page 14

 

 

 

HBDV7 Series Direct Vent Gas Fireplace

Venting INFORMATION

 

 

 

Twist Lock Pipes

When using twist lock pipe it is not necessary to use sealant on the joints. The only areas of the venting system that need to be sealed with high temperature silicone sealant are the sliding joints of any telescopic vent section used in the system.

To join twist lock pipes together, simply align the beads of the male end with the grooves of the fe- male end, twisting the pipe until the flange on the female end contacts external flange on the male end. It is recommended that you secure the joints with three (3) sheet metal screws, however, this is not mandatory with twist lock pipe. Figure 14

To make it easier to assembly the joints, we suggest putting a lubricant (Vaseline or similar) on the male end of the twist lock pipe prior to assembly.

Male End

 

Female End

 

 

 

 

 

 

TWL100

Screw Holes

Figure 14 -

Twist-lock Pipe Joints

How to Use the Vent Graph

The Vent Graph should be read in conjunction with the following vent installation instructions to determine the re- lationship between the vertical and horizontal dimensions of the vent system.

1.Determine the height of the center of the horizontal vent pipe exiting through the outer wall. Using this di- mension on the Sidewall Vent Graph, Figure 15, locate the point intersecting with the slanted graph line.

2.From the point of this intersection, draw a vertical line to the bottom of the graph.

3.Select the indicated dimension, and position the fire- place in accordance with same.

EXAMPLE A:

If the vertical dimension from the floor of the unit is 11’ (3.4

m)the horizontal run to the face of the outer wall must not exceed 14’ (4.3 m).

EXAMPLE B:

If the vertical dimension from the floor of the unit is 7’ (2.1 m), the horizontal run to the face of the outer wall must not exceed 6’ (1.8 m).

Refer to Page 21 for requirements for snorkels.

 

 

 

40

 

 

 

 

 

 

38

 

 

 

of

 

 

36

 

 

 

Center

 

 

34

 

 

 

 

 

32

 

 

 

the

 

 

30

 

 

 

to

 

 

28

 

 

 

Unit

Pipe

 

 

 

 

 

26

 

 

 

Dimension from the Floor of

the Horizontal Vent

 

24

 

 

 

 

22

 

 

 

 

20

 

 

 

 

18

 

 

 

 

16

 

 

 

 

14

 

 

eg: A

 

12

 

 

 

 

 

 

 

10

 

 

 

Vertical

 

 

 

 

 

 

X

8

 

 

 

 

6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

 

 

 

 

 

 

2

 

 

 

 

 

 

2

4

6

8 10 1214 16 1820

Horizontal Dimension From the Outside of Termination to

the Back of the Fireplace

X = 29B\,” (753 mm) for 300 Models

X = 33Z\,” (841 mm) for 400 Models

Figure 15 -

Side Wall Venting Graph

14

54D8000

Image 14
Contents HBDV7 Series Direct Vent Gas Fireplace Massachusetts Residents Only Pre-Installation InformationCheck Gas Pressure Signature Command System Owner Important Safety InformationInstaller Known as wellhead gas Please Read the Following CarefullyNever connect unit to private non Code ApprovalProduct Specifications High ElevationsFraming Dimensions HBDV300 HBDV400Fireplace Location PRE-INSTALLATION InformationFirebox framing Cold Climate InsulationNever obstruct or modify the air inlet or Clearances to combustiblesMantel Clearances Outlet grilles louvers. This may create aSecure Fireplace to Floor or Framing Finishing MaterialOptional top vent application Optional TOP Vent ApplicationGeneral Venting Venting Installation InformationInstallation precautions Canadian Installations1 US Installations2 General Venting Information Termination LocationTermination Clearances USA InstallationsCanadian Installations Refer to Page 21 for requirements for snorkels How to Use the Vent GraphTwist Lock Pipes Vent Installation 1219 mmStep Rear Wall Vent Installation Twist Lock PipeRear Wall Vent Application Top vent Sidewall Application Rear Wall Vent Installations Flex Vent PipeVent configurations apply and must be strictly adhered to + B = 17 Max Always install horizontal venting on a level plane Venting InstallationVertical Sidewall Installation Twist Lock Pipe Vertical Sidewall installation flex vent pipe Install the 4 flex then 7 flex to the terminationDo not back fill around snorkel Below Grade InstallationsVertical THROUGH-THE-ROOF APPLICA- Tion Vertical THROUGH-THE-ROOF Installation Roof Flashing Install gas piping to fireplace / burner system location Check gas typePropane/LP Fireplace InstallationNatural Gas Do not use open flame to check for gas Millivolt Check GAS Pressure and Electrical installationElectrical Wiring LeaksRemote Wall Switch Electrical InstallationRemote Wall mounted Switch Optional DC Remote SystemsNever use an open flame to check for gas leak What to do if YOU Smell GASInitial lighting Never check for gas leak with open Approved leak testing methodOperating Instructions Millivolt FlamePilot position Main burner switchLighting the burner Connecting to main electrical power supply Optional Accessory RequirementsElectrician. Main power must be off when Or performing service. All wiring shall beWall Switch Installation Junction BOX WiringCommand Center Wall Installation Nected together if a wall switch is not Being used Blotsc Signature Command Blower FK-12 Manual Blower Optional FAN Blower SystemsBlot Automatic Thermostat Blower On next Operating Instructions Signature Command Command CenterCommand Center FeaturesBattery Installation Key Combinations for System Settings Function Operation Default SettingFUNCTIONS/OPERATION Command Center OperationsSelf Diagnostics Chart Function OperationGlass Frame Removal Brick installationGlass Removal Potential sooting, glass breakage and a fire Placement of Lava ROCK, Rock Wool and LogsDo not sprinkle the lava rock or ember HazardFinal Installation Left Front Log #6 Installing Universal Andirons Burner, Pilot and Control Compart- ment Logs Vent SysteMGlass Door Rock woolSymptom Possible Cause Action Standing Pilot IgnitionTroubleshooting Signature Command System Replacement Parts Firebox ComponentsFirebox components Description QtyStanding Pilot Millivolt Control LP to Natural Gas AccessoriesFuel Conversion Kits Natural Gas to LP Signature Command System HBDV300NSC7 HBDV300PSC7 HBDV400NSC7 HBDV400PSC7 Description Qty Replacement PartsLogs Vertical Venting Description Model NumberHorizontal Venting 7TBLSCTKHBDV7 Series Direct Vent Gas Fireplace HBDV7 Series Direct Vent Gas Fireplace Carbon Monoxide Detector Requirements Basic Warranty Lifetime WarrantyFive Year Warranty If Warranty Service is NeededMhsc Model EnerGuide Ratings Fireplace Efficiency %