Monessen Hearth HBDV400N/PSC7 Termination Clearances, USA Installations, Canadian Installations

Page 13
Figure 12 - Termination Clearances

Venting INFORMATION

HBDV7 Series Direct Vent Gas Fireplace

 

 

 

Termination Clearances

Termination clearances for buildings with combustible and noncombustible exteriors.

Inside Corner

 

 

 

 

 

G =

G

 

 

 

Combustible

 

 

 

 

 

6" (152 mm)

 

 

 

 

 

 

V Noncombustible 2" (51 mm)

Outside Corner

 

F =

 

 

Combustible

 

6"

(152 mm)

V

Noncombustible

2"

(51 mm)

 

 

F

 

Alcove Applications*

D

C C

V

E

O

Balcony -

with no side wall

M

V

M =

Combustible &

Noncombustible

12" (305 mm)

Balcony -

with perpendicular side wall

M

V

P

Combustible &

Noncombustible

M = 24" (610 mm)

P = 20” (508 mm)

E = Min. 6” (152 mm) for non-vinyl sidewalls Min. 12” (305 mm) for vinyl sidewalls

O = 8’ (2.4 m) Min.

No.

 

 

 

of Caps

DMin.

CMax.

 

 

1

3’ (914 mm)

2 x DActual

 

 

2

6’ (1.8 m)

1 x DActual

 

 

3

9’ (2.7 m)

2/3 x DActual

 

 

4

12’ (3.7 m)

1/2 x DActual

 

DMin.

= # of Termination caps x 3

 

CMax.

= (2 / # termination caps) x DActual

584-15

*NOTE: Termination in an alcove space (spaces open only on one side and with an overhang) is permitted with the dimensions specified for vinyl or non-vinyl siding and soffits. 1. There must be a 3’ (914 mm) minimum between termination caps. 2. All mechanical air intakes within 10’ (1 m) of a termination cap must be a minimum of 3’ (914 mm) below the termination cap. 3. All gravity air intakes within 3’ (914 mm) of a termination cap must be a minimum of 1’ (305 mm) below the termination cap.

General Information Assembling Vent Pipes

USA Installations

The venting system must conform to local codes and/or the current National Fuel Code ANSI Z223.1/NFPA 54.

Only venting components manufactured by MHSC may be used in Direct Vent systems and UL 1777 Listed Type

*Be sure the vent is actually crushed before proceeding. Apply a tug to be sure the vent will not slip off the collars. Repeat process with 7” flex vent pipe. The same proce- dure must be performed on the vent side.

Flex Venting.

Canadian Installations

The venting system must be installed in accordance with the current CSA-B149.1 installation code.

Flex Vent Pipes

Before joining the flex vent pipe to the unit, apply a bead of high temperature sealant* (provided) to the 4” pipe exiting the fireplace. Secure flex vent pipe in place with a hose clamp (provided).

*Be sure the flex pipe overlaps at least 1” (25 mm) onto the collars of the fireplace and termination. If the termi-

FP2585

Apply High Temperature Sealant

Hose Clamp

nation has an internal bead, be sure to overlap and se- cure 1” (25 mm) past the bead.

Figure 13 -

Apply high temperature sealant to 4” and 7” pipes.

54D8000

13

Image 13
Contents HBDV7 Series Direct Vent Gas Fireplace Check Gas Pressure Signature Command System Pre-Installation InformationMassachusetts Residents Only Installer Important Safety InformationOwner Never connect unit to private non Please Read the Following CarefullyKnown as wellhead gas Code ApprovalHigh Elevations Product SpecificationsHBDV300 HBDV400 Framing DimensionsFirebox framing PRE-INSTALLATION InformationFireplace Location Cold Climate InsulationMantel Clearances Clearances to combustiblesNever obstruct or modify the air inlet or Outlet grilles louvers. This may create aFinishing Material Secure Fireplace to Floor or FramingOptional TOP Vent Application Optional top vent applicationInstallation precautions Venting Installation InformationGeneral Venting General Venting Information Termination Location Canadian Installations1 US Installations2Canadian Installations USA InstallationsTermination Clearances Twist Lock Pipes How to Use the Vent GraphRefer to Page 21 for requirements for snorkels 1219 mm Vent InstallationRear Wall Vent Application Rear Wall Vent Installation Twist Lock PipeStep Vent configurations apply and must be strictly adhered to Rear Wall Vent Installations Flex Vent PipeTop vent Sidewall Application + B = 17 Max Vertical Sidewall Installation Twist Lock Pipe Venting InstallationAlways install horizontal venting on a level plane Install the 4 flex then 7 flex to the termination Vertical Sidewall installation flex vent pipeVertical THROUGH-THE-ROOF APPLICA- Tion Below Grade InstallationsDo not back fill around snorkel Vertical THROUGH-THE-ROOF Installation Roof Flashing Check gas type Install gas piping to fireplace / burner system locationNatural Gas Fireplace InstallationPropane/LP Electrical Wiring Millivolt Check GAS Pressure and Electrical installationDo not use open flame to check for gas LeaksRemote Wall mounted Switch Electrical InstallationRemote Wall Switch Optional DC Remote SystemsInitial lighting What to do if YOU Smell GASNever use an open flame to check for gas leak Operating Instructions Millivolt Approved leak testing methodNever check for gas leak with open FlameLighting the burner Main burner switchPilot position Electrician. Main power must be off when Optional Accessory RequirementsConnecting to main electrical power supply Or performing service. All wiring shall beCommand Center Wall Installation Junction BOX WiringWall Switch Installation Nected together if a wall switch is not Being used Blotsc Signature Command Blower Blot Automatic Thermostat Blower Optional FAN Blower SystemsFK-12 Manual Blower On next Command Center Operating Instructions Signature CommandBattery Installation FeaturesCommand Center Function Operation Default Setting Key Combinations for System SettingsSelf Diagnostics Chart Command Center OperationsFUNCTIONS/OPERATION Function OperationGlass Removal Brick installationGlass Frame Removal Do not sprinkle the lava rock or ember Placement of Lava ROCK, Rock Wool and LogsPotential sooting, glass breakage and a fire HazardFinal Installation Left Front Log #6 Installing Universal Andirons Burner, Pilot and Control Compart- ment Glass Door Vent SysteMLogs Rock woolStanding Pilot Ignition Symptom Possible Cause ActionTroubleshooting Signature Command System Firebox Components Replacement PartsDescription Qty Firebox componentsStanding Pilot Millivolt Control Fuel Conversion Kits Natural Gas to LP AccessoriesLP to Natural Gas Signature Command System HBDV300NSC7 HBDV300PSC7 HBDV400NSC7 HBDV400PSC7 Logs Replacement PartsDescription Qty Description Model Number Vertical Venting7TBLSCTK Horizontal VentingHBDV7 Series Direct Vent Gas Fireplace HBDV7 Series Direct Vent Gas Fireplace Carbon Monoxide Detector Requirements Five Year Warranty Lifetime WarrantyBasic Warranty If Warranty Service is NeededModel EnerGuide Ratings Fireplace Efficiency % Mhsc