Monessen Hearth HBDV300N/PV7 manual Clearances to combustibles, Mantel Clearances, Fire hazard

Page 8

HBDV7 Series Direct Vent Gas Fireplace

CLEARANCES

Clearances to combustibles

WARNING

Follow these instructions carefully to ensure safe installation. Failure to follow instructions exactly can create a fire hazard.

The appliance cannot be installed on a carpet, tile or other combustible material other than wood flooring. If installed on carpet or vinyl flooring, the appliance shall be installed on a metal, wood or noncombustible material panel extending full width and depth of the appliance.

Ceiling

 

Combustible

Mantel

 

 

71”

 

 

Minimum

12”

 

 

Minimum

 

NOTE: All mantel shelves, regard-

less of depth, should be a mini- mum of 12” from top of fireplace. Wall

Mantel shelf shall not exceed 12” maximum depth at 12” minimum

height from opening.

12”

12”

12”

Max.

Top of Exhaust

Louvers

Side View

Stud

Insulation

Board

Standoff

FP2581

Min. 4”

From Either

Side Wall

Figure 4 -

Clearances

FP2580

MANTEL CLEARANCES

NOTE: The combustible area above the facing must not protrude more than 3/4" from the facing. If it does, it is considered a mantel and must meet the mantel requirements listed in this manual.

WARNING

Never obstruct or modify the air inlet or

 

 

outlet grilles (louvers). This may create a

 

fire hazard.

 

 

 

 

Combustible

 

 

 

Material Area

 

 

 

Wall

 

FP2582

1" 156O

 

 

 

 

256O

256O

 

 

 

45°

 

3"

 

Side of Fire-

 

 

place Opening

 

4"

 

 

Top View

 

Figure 5 -

Mantel Clearances

54D8000

Image 8
Contents HBDV7 Series Direct Vent Gas Fireplace Massachusetts Residents Only Pre-Installation InformationCheck Gas Pressure Signature Command System Owner Important Safety InformationInstaller Please Read the Following Carefully Never connect unit to private nonKnown as wellhead gas Code ApprovalProduct Specifications High ElevationsFraming Dimensions HBDV300 HBDV400PRE-INSTALLATION Information Firebox framingFireplace Location Cold Climate InsulationClearances to combustibles Mantel ClearancesNever obstruct or modify the air inlet or Outlet grilles louvers. This may create aSecure Fireplace to Floor or Framing Finishing MaterialOptional top vent application Optional TOP Vent ApplicationGeneral Venting Venting Installation InformationInstallation precautions Canadian Installations1 US Installations2 General Venting Information Termination LocationTermination Clearances USA InstallationsCanadian Installations Refer to Page 21 for requirements for snorkels How to Use the Vent GraphTwist Lock Pipes Vent Installation 1219 mmStep Rear Wall Vent Installation Twist Lock PipeRear Wall Vent Application Top vent Sidewall Application Rear Wall Vent Installations Flex Vent PipeVent configurations apply and must be strictly adhered to + B = 17 Max Always install horizontal venting on a level plane Venting InstallationVertical Sidewall Installation Twist Lock Pipe Vertical Sidewall installation flex vent pipe Install the 4 flex then 7 flex to the terminationDo not back fill around snorkel Below Grade InstallationsVertical THROUGH-THE-ROOF APPLICA- Tion Vertical THROUGH-THE-ROOF Installation Roof Flashing Install gas piping to fireplace / burner system location Check gas typePropane/LP Fireplace InstallationNatural Gas Millivolt Check GAS Pressure and Electrical installation Electrical WiringDo not use open flame to check for gas LeaksElectrical Installation Remote Wall mounted SwitchRemote Wall Switch Optional DC Remote SystemsNever use an open flame to check for gas leak What to do if YOU Smell GASInitial lighting Approved leak testing method Operating Instructions MillivoltNever check for gas leak with open FlamePilot position Main burner switchLighting the burner Optional Accessory Requirements Electrician. Main power must be off whenConnecting to main electrical power supply Or performing service. All wiring shall beWall Switch Installation Junction BOX WiringCommand Center Wall Installation Nected together if a wall switch is not Being used Blotsc Signature Command Blower FK-12 Manual Blower Optional FAN Blower SystemsBlot Automatic Thermostat Blower On next Operating Instructions Signature Command Command CenterCommand Center FeaturesBattery Installation Key Combinations for System Settings Function Operation Default SettingCommand Center Operations Self Diagnostics ChartFUNCTIONS/OPERATION Function OperationGlass Frame Removal Brick installationGlass Removal Placement of Lava ROCK, Rock Wool and Logs Do not sprinkle the lava rock or emberPotential sooting, glass breakage and a fire HazardFinal Installation Left Front Log #6 Installing Universal Andirons Burner, Pilot and Control Compart- ment Vent SysteM Glass DoorLogs Rock woolSymptom Possible Cause Action Standing Pilot IgnitionTroubleshooting Signature Command System Replacement Parts Firebox ComponentsFirebox components Description QtyStanding Pilot Millivolt Control LP to Natural Gas AccessoriesFuel Conversion Kits Natural Gas to LP Signature Command System HBDV300NSC7 HBDV300PSC7 HBDV400NSC7 HBDV400PSC7 Description Qty Replacement PartsLogs Vertical Venting Description Model NumberHorizontal Venting 7TBLSCTKHBDV7 Series Direct Vent Gas Fireplace HBDV7 Series Direct Vent Gas Fireplace Carbon Monoxide Detector Requirements Lifetime Warranty Five Year WarrantyBasic Warranty If Warranty Service is NeededMhsc Model EnerGuide Ratings Fireplace Efficiency %