Monessen Hearth HBDV300N/PSC7 manual General, Optional Accessory Requirements, Code, CSA C22.1

Page 31

SIGNATURE COMMAND - CHECK GAS PRESSURE and ELECTRICALHBDV7 SeriesINSTALLATIONDirect Vent Gas Fireplace

1.Check gas type. The gas supply must be the same as stated on the appliance’s rating decal. If the gas supply is different from the fireplace, STOP! Do not install the appliance. Contact your dealer immediately.

2.To ease installation, a 24" (610 mm) flex line with manual shut-off valve has been provided with this ap- pliance. Install and attach 1/2" gas line onto shut-off valve.

3.After completing gas line connection, purge air from gas line and test all gas joints from the gas meter to the fireplace for leaks. Use a solution of 50/50 water and soap solution or a gas sniffer.

4.To check gas pressures at valve, turn captured screw counter clockwise 2 or 3 turns and then place tubing to pressure gauge over test point. Turn unit to high. Figure 52. After taking pressure reading, be sure and turn captured screw clockwise firmly to reseal. Do not over torque. Check test points for gas leaks.

Electrical Wiring

General

1.This fireplace is equipped with the Signature Control valve which operates on 6 volts. The 6 volt DC adapter plugs into the fireplace junction box A/C power supply. Four (4) “AA” batteries are used for back up during power outages.

2.The Signature Command System can also be operated without A/C power. The system can run on four (4) “AA” batteries for approximately six (6) months under normal use.

3.A/C power must be used to power the A/C module, blowers, lights and AUX accessories if used with this fireplace.

Optional Accessory Requirements

1.This fireplace may be used with a wall switch, wall mounted thermostat and/or Signature Command wire- less controls.

2.The command center control may be mounted on the wall with the use of the SCSWEK 15ft. wall mount exten- sion kit.

Pressure Inlet

Pressure Outlet

Pilot Adjust-

ment Screw

 

Figure 52 -

 

Signature Command Valve

 

 

WARNING

Do not use open flame to check for gas

 

 

 

 

leaks.

 

 

 

 

 

Electrical connections should only

 

 

be performed by a qualified, licensed

 

 

electrician. Main power must be off when

 

WARNING

connecting to main electrical power supply

 

or performing service. All wiring shall be

 

 

 

 

in compliance with all local, city and state

 

 

codes. The appliance, when installed, must

 

 

be electrically grounded in accordance with

 

 

local codes or in the absence of local codes,

 

 

with the National Electrical Code ANSI/NFPA

 

 

70 (latest edition) and Canadian Electrical

 

 

Code, CSA C22.1.

 

 

 

 

 

 

 

CAUTION

Label all wires before disconnecting when

 

 

 

 

servicing controls. Wiring errors can cause

 

 

improper and dangerous operation.

 

 

 

54D8000

31

Image 31
Contents HBDV7 Series Direct Vent Gas Fireplace Check Gas Pressure Signature Command System Pre-Installation InformationMassachusetts Residents Only Installer Important Safety InformationOwner Code Approval Please Read the Following CarefullyNever connect unit to private non Known as wellhead gasHigh Elevations Product SpecificationsHBDV300 HBDV400 Framing DimensionsCold Climate Insulation PRE-INSTALLATION InformationFirebox framing Fireplace LocationOutlet grilles louvers. This may create a Clearances to combustiblesMantel Clearances Never obstruct or modify the air inlet orFinishing Material Secure Fireplace to Floor or FramingOptional TOP Vent Application Optional top vent applicationInstallation precautions Venting Installation InformationGeneral Venting General Venting Information Termination Location Canadian Installations1 US Installations2Canadian Installations USA InstallationsTermination Clearances Twist Lock Pipes How to Use the Vent GraphRefer to Page 21 for requirements for snorkels 1219 mm Vent InstallationRear Wall Vent Application Rear Wall Vent Installation Twist Lock PipeStep Vent configurations apply and must be strictly adhered to Rear Wall Vent Installations Flex Vent PipeTop vent Sidewall Application + B = 17 Max Vertical Sidewall Installation Twist Lock Pipe Venting InstallationAlways install horizontal venting on a level plane Install the 4 flex then 7 flex to the termination Vertical Sidewall installation flex vent pipeVertical THROUGH-THE-ROOF APPLICA- Tion Below Grade InstallationsDo not back fill around snorkel Vertical THROUGH-THE-ROOF Installation Roof Flashing Check gas type Install gas piping to fireplace / burner system locationNatural Gas Fireplace InstallationPropane/LP Leaks Millivolt Check GAS Pressure and Electrical installationElectrical Wiring Do not use open flame to check for gasOptional DC Remote Systems Electrical InstallationRemote Wall mounted Switch Remote Wall SwitchInitial lighting What to do if YOU Smell GASNever use an open flame to check for gas leak Flame Approved leak testing methodOperating Instructions Millivolt Never check for gas leak with openLighting the burner Main burner switchPilot position Or performing service. All wiring shall be Optional Accessory RequirementsElectrician. Main power must be off when Connecting to main electrical power supplyCommand Center Wall Installation Junction BOX WiringWall Switch Installation Nected together if a wall switch is not Being used Blotsc Signature Command Blower Blot Automatic Thermostat Blower Optional FAN Blower SystemsFK-12 Manual Blower On next Command Center Operating Instructions Signature CommandBattery Installation FeaturesCommand Center Function Operation Default Setting Key Combinations for System SettingsFunction Operation Command Center OperationsSelf Diagnostics Chart FUNCTIONS/OPERATIONGlass Removal Brick installationGlass Frame Removal Hazard Placement of Lava ROCK, Rock Wool and LogsDo not sprinkle the lava rock or ember Potential sooting, glass breakage and a fireFinal Installation Left Front Log #6 Installing Universal Andirons Burner, Pilot and Control Compart- ment Rock wool Vent SysteMGlass Door LogsStanding Pilot Ignition Symptom Possible Cause ActionTroubleshooting Signature Command System Firebox Components Replacement PartsDescription Qty Firebox componentsStanding Pilot Millivolt Control Fuel Conversion Kits Natural Gas to LP AccessoriesLP to Natural Gas Signature Command System HBDV300NSC7 HBDV300PSC7 HBDV400NSC7 HBDV400PSC7 Logs Replacement PartsDescription Qty Description Model Number Vertical Venting7TBLSCTK Horizontal VentingHBDV7 Series Direct Vent Gas Fireplace HBDV7 Series Direct Vent Gas Fireplace Carbon Monoxide Detector Requirements If Warranty Service is Needed Lifetime WarrantyFive Year Warranty Basic WarrantyModel EnerGuide Ratings Fireplace Efficiency % Mhsc