Monessen Hearth HBDV400N/PV7, HBDV300N/PV7, HBDV400N/PSC7 Carbon Monoxide Detector Requirements

Page 62

MassachusettsHBDV7 Series DirectResidentsV nt Gas FireplaceOnly — Please read and follow these special requirements

NOTE REGARDING VENTED PRODUCTS

This product must be installed by a licensed plumber or gas fitter when installed within the Commonwealth of Massachusetts.

Any residence with a direct vent product must have a CO detector installed in the residence.

Installation of the fireplace or vented gas log in the State of Massachusetts requires the damper to be permanently removed or welded in the fully open position.

In addition, a naturally vented gas log may not be installed in a bedroom or bathroom in the State of Massachusetts.

Flex line installation must not exceed 36 inches and must have a T shutoff valve.

NOTE REGARDING VENT FREE PRODUCTS

This product must be installed by a licensed plumber or gas fitter when installed within the Commonwealth of Massachusetts.

In addition, vent free products may not be installed in a bedroom or bathroom regardless of size or type in the State of Massachusetts.

Flex line installation must not exceed 36 inches and must have a T shutoff valve.

CARBON MONOXIDE DETECTOR REQUIREMENTS

(2)Revise 10.8.3 by adding the following additional requirements:

(a)For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied:

1.Installation of carbon monoxide detectors. At the time of installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gas fitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gas fitter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors

a.In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.

b.In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.

2.Approved Carbon Monoxide Detectors. Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.

3.Signage. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, “GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS.”

4.Inspection. The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a)1 through 4.

(b)Exemptions: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:

1.The equipment listed in Chapter 10 entitled "Equipment Not Required To Be Vented" in the most current edition of NFPA 54 as adopted by the Board; and

2.Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or structure used in whole or in part for residential purposes.

(c)Manufacturer requirements — Gas Equipment Venting System Provided. When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:

1.Detailed instructions for the installation of the venting system design or the venting system components; and

2.A complete parts list for the venting system design or venting system.

(d)Manufacturer requirements — Gas Equipment Venting System Not Provided. When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies “special venting systems,” the following requirements shall be satisfied by the manufacturer:

1.The referenced "special venting system" instructions shall be included with the appliance or equipment installation instructions; and

2.The “special venting systems” shall be Product Approved by the Board, and the instructions for that system shall include a parts list and detailed installation instructions.

(e)A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions, all parts lists for venting instructions, and/or all venting design

62

54D8000

Image 62
Contents HBDV7 Series Direct Vent Gas Fireplace Massachusetts Residents Only Pre-Installation InformationCheck Gas Pressure Signature Command System Owner Important Safety InformationInstaller Known as wellhead gas Please Read the Following CarefullyNever connect unit to private non Code ApprovalProduct Specifications High ElevationsFraming Dimensions HBDV300 HBDV400Fireplace Location PRE-INSTALLATION InformationFirebox framing Cold Climate InsulationNever obstruct or modify the air inlet or Clearances to combustiblesMantel Clearances Outlet grilles louvers. This may create aSecure Fireplace to Floor or Framing Finishing MaterialOptional top vent application Optional TOP Vent ApplicationGeneral Venting Venting Installation InformationInstallation precautions Canadian Installations1 US Installations2 General Venting Information Termination LocationTermination Clearances USA InstallationsCanadian Installations Refer to Page 21 for requirements for snorkels How to Use the Vent GraphTwist Lock Pipes Vent Installation 1219 mmStep Rear Wall Vent Installation Twist Lock PipeRear Wall Vent Application Top vent Sidewall Application Rear Wall Vent Installations Flex Vent PipeVent configurations apply and must be strictly adhered to + B = 17 Max Always install horizontal venting on a level plane Venting InstallationVertical Sidewall Installation Twist Lock Pipe Vertical Sidewall installation flex vent pipe Install the 4 flex then 7 flex to the terminationDo not back fill around snorkel Below Grade InstallationsVertical THROUGH-THE-ROOF APPLICA- Tion Vertical THROUGH-THE-ROOF Installation Roof Flashing Install gas piping to fireplace / burner system location Check gas typePropane/LP Fireplace InstallationNatural Gas Do not use open flame to check for gas Millivolt Check GAS Pressure and Electrical installationElectrical Wiring LeaksRemote Wall Switch Electrical InstallationRemote Wall mounted Switch Optional DC Remote SystemsNever use an open flame to check for gas leak What to do if YOU Smell GASInitial lighting Never check for gas leak with open Approved leak testing methodOperating Instructions Millivolt FlamePilot position Main burner switchLighting the burner Connecting to main electrical power supply Optional Accessory RequirementsElectrician. Main power must be off when Or performing service. All wiring shall beWall Switch Installation Junction BOX WiringCommand Center Wall Installation Nected together if a wall switch is not Being used Blotsc Signature Command Blower FK-12 Manual Blower Optional FAN Blower SystemsBlot Automatic Thermostat Blower On next Operating Instructions Signature Command Command CenterCommand Center FeaturesBattery Installation Key Combinations for System Settings Function Operation Default SettingFUNCTIONS/OPERATION Command Center OperationsSelf Diagnostics Chart Function OperationGlass Frame Removal Brick installationGlass Removal Potential sooting, glass breakage and a fire Placement of Lava ROCK, Rock Wool and LogsDo not sprinkle the lava rock or ember HazardFinal Installation Left Front Log #6 Installing Universal Andirons Burner, Pilot and Control Compart- ment Logs Vent SysteMGlass Door Rock woolSymptom Possible Cause Action Standing Pilot IgnitionTroubleshooting Signature Command System Replacement Parts Firebox ComponentsFirebox components Description QtyStanding Pilot Millivolt Control LP to Natural Gas AccessoriesFuel Conversion Kits Natural Gas to LP Signature Command System HBDV300NSC7 HBDV300PSC7 HBDV400NSC7 HBDV400PSC7 Description Qty Replacement PartsLogs Vertical Venting Description Model NumberHorizontal Venting 7TBLSCTKHBDV7 Series Direct Vent Gas Fireplace HBDV7 Series Direct Vent Gas Fireplace Carbon Monoxide Detector Requirements Basic Warranty Lifetime WarrantyFive Year Warranty If Warranty Service is NeededMhsc Model EnerGuide Ratings Fireplace Efficiency %