Liebert 50 & 60Hz, 8 Tons Outdoor Air-Cooled Condensing Unit Installation, Electrical Connections

Page 31

Site Preparation and Installation

2.6Outdoor Air-Cooled Condensing Unit Installation

2.6.1Location Considerations

To insure a satisfactory air supply, locate air-cooled propeller fan condensing units in an environment providing clean air, away from loose dirt and foreign matter that may clog the coil. Condensing units must not be located in the vicinity of steam, hot air, or fume exhausts, or closer than 18 inches from a wall, obstruction, or adjacent unit. Avoid areas where heavy snow will accumulate at air inlet and dis- charge locations.

The condensing unit should be located for maximum security and maintenance accessibility. Avoid ground-level sites with public access.

Install a solid base, capable of supporting the weight of the condensing unit. The base should be at least 2 inches higher than the surrounding grade and 2 inches larger than the dimensions of the con- densing unit base. For snowy areas, a base of sufficient height to clear snow accumulation must be installed.

2.6.2Piping Connections

Details for refrigerant (R-22) loop piping are in Figure 12 - Piping connections - indoor air- cooled centrifugal fan condensing unit.

2.6.3Electrical Connections

Refer to 2.4.4 - Electrical Connections, Evaporator or Chilled-Water Unit for general wiring requirements and cautions. Refer to electrical schematic when making connections.

Power Connections

The outdoor condensing unit requires its own power source and earth ground, with a disconnect switch (field supplied) to isolate the unit for maintenance.

Control Connections

Field-supplied control wires must be connected between the evaporator and the condensing unit. (See Figure 6 and the electrical schematic on the units for more details.) Seven (7) wires are required between the evaporator and condensing unit. Eighth and ninth wires are required on systems with hot gas bypass.

23

Image 31
Contents Liebert Mini-Mate2 Page Table of Contents System Performance Microprocessor Controls Microprocessor ControlSystem OPERATION, TESTING, and Maintenance AlarmsFigures Table iv Heat rejection matchup 50 Hz Table iii Heat rejection matchup 60 HzPage Standard Product Features Optional Equipment Ancillary Ship Loose Accessories Application limits, evaporator and chilled-water units Installation ConsiderationsInput Voltage Entering Fluid Temperature Min Room PreparationLocation Considerations Drycooler Evaporator Unit weights System WeightsEquipment Inspection upon receipt Nylock Installing the Evaporator or Chilled-Water UnitsLocking nut Hex nut Nut Clamps are for shipping purposes only Close Coupled InstallationsHp Motor std Hp Motor opt Turns External Open Evaporator Air Distribution Filter BoxConnections for Ducted Systems Evaporator external static pressure 60 at 3750 CFM 6371 CMHPiping Connections and Coolant Requirements Drain Line Drain installationHumidifier Water Supply Line Condensate PumpChilled-Water Piping-Chilled-water Systems Only General arrangement diagram chilled-water systemsRecommended refrigerant line sizes Refrigerant R-22 PipingEquivalent Suction Feet Circuit Liquid Line Line charges field piping Total refrigerant = Units and LinesQuick Connect Fittings Ton unit refrigerant chargeOptional Filter BOX Electrical Connections, Evaporator or Chilled-Water Unit Power ConnectionsFront of Unit Evaporator unit electrical connectionsGeneral Considerations DuctingConsiderations for Specific Applications Electrical Connections Condensing Unit Piping ConnectionsControl Connections DPN000248Rev1 Heat rejection connection. Field Electrical Connections Outdoor Air-Cooled Condensing Unit InstallationEarth ground connection Electric service connectionHigh voltage Low voltageFootprint Dimensions 152 11-1/2292 Condensing Unit Fluid Requirements Water/Glycol Piping ConsiderationsRegulating Valve Indoor water/glycol condensing unit dimensional data Site Preparation and Installation Two circuits provided. Single circuit shown Optional free cooling coil 3-way valve on water/glycol units Optional Equipment PipingOptional free cooling coil 3-way valve on air-cooled units Checklist for Completed Installation Wall box Feature OverviewMain Menu Menu Setpoints Active AlarmsAlarm History Default setpoints and allowable rangesDate Setup OperationRestart Time Delay TimeLead Compressor Show DIP Switch10.2 C/F Degrees Humidity Control MethodCalibrate Sensors Change PasswordsAlarm Enable Setup functions, default values and allowable rangesAlarm default time delays Alarm Time DelayCommon Alarm Enable Custom AlarmsNonvolatile Memory Equipment Options SwitchesCustom Text LCD Display ContrastTest Outputs Run DiagnosticsTest Inputs Test Micro TB3-2 Connection to Terminal #2 Wallbox TB3-1 TB3-2 TB3-3 TB4-4 Wall Box DIP SwitchesTB3-4 Connection to Terminal #4 Wallbox TB3-3 Connection to Terminal #3 WallboxCooling Control Type Response Proportional ControlReheat Humidification Operation System Activation Load Control FeaturesDehumidification / Humidification Percent Required CommunicationsAir-Cooled Systems Alarms Definitions and TroubleshootingCustom Alarms High Head PressureLoss of Power TemperatureHumidifier Problem Alarm High-Water AlarmChange Filter Optional/Custom AlarmsSystem Testing Maintenance and Component Operation Thermostatic Expansion Valve Refrigeration SystemSuction Pressure Discharge PressureRegulating Valves Water/Glycol Condensing Units Glycol Solution MaintenanceHot Gas Bypass Optional Replacement Procedures Steam Generating Humidifier Operation Procedures Amps Circuit Board AdjustmentsHumidifier control board DIP switch settings Replacing the Humidifier CanisterMaintenance Inspection Checklist Troubleshooting Control pads Symptom Possible Cause Check or Remedy Cooling cycle tooShort Display freezesTroubleshooting Troubleshooting Troubleshooting Page That NetIti Tin