3.0MICROPROCESSOR CONTROL

The Microprocessor Control for the Liebert Mini-Mate2 unit features an easy to use menu-driven LCD display. The menus, control features, and circuit board details are described in this section. Detailed information concerning controls (4.0 - System Performance Microprocessor Controls) and alarms (5.0 - Alarms) are provided.

3.1Feature Overview

To turn the unit ON, press the ON/OFF (I/O) key after power is applied. To turn the unit OFF, press the ON/OFF (I/O) key before power is disconnected.

The following control keys may be used to move through the menus, as prompted on the LCD display:

ON/OFF (I/O) – turns unit on or off (top far left).

Menu – Enables user to access the program menu to change control parameters, alarms, setback schedule, etc. (top near left).

Increase (UP) – Raises the value of displayed parameter while in a set mode (setpoints, time, etc.) (Arrow-top near right) and navigates the program menu.

Escape (ESC) – Allows user to move back to a previous menu (top far right).

Alarm Silence/Help – If an alarm is present, pressing this keypad will silence he alarm. If this key is pressed when no alarms are present, help text will appear (bottom near left).

Decrease (DOWN) Arrow – Lowers the value of displayed parameter while in a set mode (bottom near right) and navigates the program menu.

Enter – After setting a control point, press ENTER to store the information in the microprocessor (bottom far right) Also, press ENTER to select a menu item.

Figure 23 Wall box

Active alarms are displayed on the LCD screen and sound an audible beeper. To silence an alarm, press the Alarm Silence/Help key as prompted on the display.

Setpoints, DIP switch settings, and other selections were made during factory testing of your unit and are based upon typical operating experience. (Other default selections were made according to options included with your unit). MAKE ADJUSTMENTS TO THE FACTORY DEFAULT SELECTIONS ONLY IF THEY DO NOT MEET YOUR SPECIFICATIONS.

Allowable ranges are displayed by pressing the help key. A password will be required (if enabled) to change setpoints, time delays, etc.

The display normally shown includes the present room temperature, humidity, active status func- tions (cooling, heating, dehumidifying, humidifying), and active alarms. More detailed status and alarm information is available from the menu.

34

Image 42
Contents Liebert Mini-Mate2 Page Table of Contents Microprocessor Control System Performance Microprocessor ControlsAlarms System OPERATION, TESTING, and MaintenanceFigures Table iii Heat rejection matchup 60 Hz Table iv Heat rejection matchup 50 HzPage Standard Product Features Optional Equipment Ancillary Ship Loose Accessories Room Preparation Installation ConsiderationsInput Voltage Entering Fluid Temperature Min Application limits, evaporator and chilled-water unitsLocation Considerations Drycooler Evaporator System Weights Unit weightsEquipment Inspection upon receipt Installing the Evaporator or Chilled-Water Units NylockLocking nut Hex nut Close Coupled Installations Nut Clamps are for shipping purposes onlyEvaporator external static pressure 60 at 3750 CFM 6371 CMH Evaporator Air Distribution Filter BoxConnections for Ducted Systems Hp Motor std Hp Motor opt Turns External OpenDrain installation Piping Connections and Coolant Requirements Drain LineCondensate Pump Humidifier Water Supply LineGeneral arrangement diagram chilled-water systems Chilled-Water Piping-Chilled-water Systems OnlyRefrigerant R-22 Piping Recommended refrigerant line sizesEquivalent Suction Feet Circuit Liquid Line Ton unit refrigerant charge Total refrigerant = Units and LinesQuick Connect Fittings Line charges field pipingOptional Filter BOX Power Connections Electrical Connections, Evaporator or Chilled-Water UnitEvaporator unit electrical connections Front of UnitDucting General ConsiderationsConsiderations for Specific Applications Piping Connections Electrical Connections Condensing UnitControl Connections DPN000248Rev1 Heat rejection connection. Field Outdoor Air-Cooled Condensing Unit Installation Electrical ConnectionsLow voltage Electric service connectionHigh voltage Earth ground connectionFootprint Dimensions 11-1/2 152292 Water/Glycol Piping Considerations Condensing Unit Fluid RequirementsRegulating Valve Indoor water/glycol condensing unit dimensional data Site Preparation and Installation Two circuits provided. Single circuit shown Optional Equipment Piping Optional free cooling coil 3-way valve on water/glycol unitsOptional free cooling coil 3-way valve on air-cooled units Checklist for Completed Installation Feature Overview Wall boxMain Menu Menu Default setpoints and allowable ranges Active AlarmsAlarm History SetpointsTime Setup OperationRestart Time Delay DateHumidity Control Method Show DIP Switch10.2 C/F Degrees Lead CompressorSetup functions, default values and allowable ranges Change PasswordsAlarm Enable Calibrate SensorsCustom Alarms Alarm Time DelayCommon Alarm Enable Alarm default time delaysLCD Display Contrast Equipment Options SwitchesCustom Text Nonvolatile MemoryRun Diagnostics Test OutputsTest Inputs Test Micro TB3-3 Connection to Terminal #3 Wallbox TB3-1 TB3-2 TB3-3 TB4-4 Wall Box DIP SwitchesTB3-4 Connection to Terminal #4 Wallbox TB3-2 Connection to Terminal #2 WallboxControl Type Response Proportional Control CoolingReheat Communications Load Control FeaturesDehumidification / Humidification Percent Required Humidification Operation System ActivationHigh Head Pressure Alarms Definitions and TroubleshootingCustom Alarms Air-Cooled SystemsHigh-Water Alarm TemperatureHumidifier Problem Alarm Loss of PowerOptional/Custom Alarms Change FilterSystem Testing Maintenance and Component Operation Discharge Pressure Refrigeration SystemSuction Pressure Thermostatic Expansion ValveGlycol Solution Maintenance Regulating Valves Water/Glycol Condensing UnitsHot Gas Bypass Optional Replacement Procedures Steam Generating Humidifier Operation Procedures Replacing the Humidifier Canister Circuit Board AdjustmentsHumidifier control board DIP switch settings AmpsMaintenance Inspection Checklist Troubleshooting Display freezes Symptom Possible Cause Check or Remedy Cooling cycle tooShort Control padsTroubleshooting Troubleshooting Troubleshooting Page Tin NetIti That