System Performance Microprocessor Controls
4.4Dehumidification / Humidification Percent Required
The humidity control for the MM2 is based on a calculated percent requirement for dehumidification or humidification. The percent requirement is calculated from the difference between the sensor read- ing and the humidity setpoint, divided by the sensitivity. The control method is selectable between relative and absolute. Relative humidity control is the default.
4.4.1Staged Dehumidification, Compressorized Direct Expansion (DX) Systems
For the
4.4.2Humidification Operation System Activation
The humidifier is activated when the humidity control calculates a requirement for 100% humidifica- tion, and is deactivated when the requirement falls below 50%.
4.4.3Dehumidification Lockout
Dehumidification is locked out if overcooling occurs. Dehumidification on the
4.5Load Control Features
The control system monitors the compressor and prevents it from turning on within a
4.6Communications
The control system uses a
The communications channel provides both monitoring and control options, including:
•TEMPERATURE/HUMIDITY: Current temperature and humidity readings.
•STATUS (%), Cooling/heating and humidify/dehumidify operating status.
•PRESENT ALARMS: Alarms currently activated.
•SETPOINTS:
•Temperature Setpoint
•Temperature Sensitivity
•Humidity Setpoint
•Humidity Sensitivity
•High Temperature Alarm
•Low Temperature Alarm
•High Humidity Alarm
•Low Humidity Alarm
•ON/OFF STATUS and CONTROL
•SILENCE ALARM
46