Liebert 8 Tons Dehumidification / Humidification Percent Required, Load Control Features

Page 54

System Performance Microprocessor Controls

4.4Dehumidification / Humidification Percent Required

The humidity control for the MM2 is based on a calculated percent requirement for dehumidification or humidification. The percent requirement is calculated from the difference between the sensor read- ing and the humidity setpoint, divided by the sensitivity. The control method is selectable between relative and absolute. Relative humidity control is the default.

4.4.1Staged Dehumidification, Compressorized Direct Expansion (DX) Systems

For the 8-ton unit operation, 1 or 2 stage dehumidification is selected through DIP switch #7. For 2 stages, the 5-ton compressor is the lead compressor when dehumidifying. Dehumidification will be staged on at 50 and 100% call. The electric reheats are turned on at 25% cooling (reheat 1) and 25% heating (reheat 2) for improved temperature control. The reheats are deactivated at 0% and 50% cool- ing requirement, respectively. If overcooling occurs, the first stage of dehumidification is disabled at 125% call for heating. If 1 stage or 2 stage is selected, dehumidification is disabled at 200% call for heating. Dehumidification is re-enabled at 66% call for 2 stage and 33% call for 1 stage. For optional hot water heating, the valve is energized at its normal point, 100% heating requirement.

4.4.2Humidification Operation System Activation

The humidifier is activated when the humidity control calculates a requirement for 100% humidifica- tion, and is deactivated when the requirement falls below 50%.

4.4.3Dehumidification Lockout

Dehumidification is locked out if overcooling occurs. Dehumidification on the 8-ton unit is disabled at 125% (first stage) and 200% (all stages) heating requirement. Dehumidification is re-enabled at 66% and 33% heating requirement.

4.5Load Control Features

The control system monitors the compressor and prevents it from turning on within a 3-minute period of being off. If this on-off cycle occurs to often (e.g. 10 times within a one hour period) a Short Cycle Alarm will occur.

4.6Communications

The control system uses a two-wire, RS-422 channel to communicate with Liebert Site Products via a proprietary protocol. A converter board (ECA2) is available to allow communications with a “dumb” terminal or a computer using RS-232 channel. More details are provided in the Site Products and ECA2 User Manual.

The communications channel provides both monitoring and control options, including:

TEMPERATURE/HUMIDITY: Current temperature and humidity readings.

STATUS (%), Cooling/heating and humidify/dehumidify operating status.

PRESENT ALARMS: Alarms currently activated.

SETPOINTS:

Temperature Setpoint

Temperature Sensitivity

Humidity Setpoint

Humidity Sensitivity

High Temperature Alarm

Low Temperature Alarm

High Humidity Alarm

Low Humidity Alarm

ON/OFF STATUS and CONTROL

SILENCE ALARM

46

Image 54
Contents Liebert Mini-Mate2 Page Table of Contents Microprocessor Control System Performance Microprocessor ControlsAlarms System OPERATION, TESTING, and MaintenanceFigures Table iii Heat rejection matchup 60 Hz Table iv Heat rejection matchup 50 HzPage Standard Product Features Optional Equipment Ancillary Ship Loose Accessories Room Preparation Installation ConsiderationsInput Voltage Entering Fluid Temperature Min Application limits, evaporator and chilled-water unitsLocation Considerations Drycooler Evaporator System Weights Unit weightsEquipment Inspection upon receipt Installing the Evaporator or Chilled-Water Units NylockLocking nut Hex nut Close Coupled Installations Nut Clamps are for shipping purposes onlyEvaporator external static pressure 60 at 3750 CFM 6371 CMH Evaporator Air Distribution Filter BoxConnections for Ducted Systems Hp Motor std Hp Motor opt Turns External OpenDrain installation Piping Connections and Coolant Requirements Drain LineCondensate Pump Humidifier Water Supply LineGeneral arrangement diagram chilled-water systems Chilled-Water Piping-Chilled-water Systems OnlyRefrigerant R-22 Piping Recommended refrigerant line sizesEquivalent Suction Feet Circuit Liquid Line Ton unit refrigerant charge Total refrigerant = Units and LinesQuick Connect Fittings Line charges field pipingOptional Filter BOX Power Connections Electrical Connections, Evaporator or Chilled-Water UnitEvaporator unit electrical connections Front of UnitDucting General ConsiderationsConsiderations for Specific Applications Piping Connections Electrical Connections Condensing UnitControl Connections DPN000248Rev1 Heat rejection connection. Field Outdoor Air-Cooled Condensing Unit Installation Electrical ConnectionsLow voltage Electric service connectionHigh voltage Earth ground connectionFootprint Dimensions 11-1/2 152292 Water/Glycol Piping Considerations Condensing Unit Fluid RequirementsRegulating Valve Indoor water/glycol condensing unit dimensional data Site Preparation and Installation Two circuits provided. Single circuit shown Optional Equipment Piping Optional free cooling coil 3-way valve on water/glycol unitsOptional free cooling coil 3-way valve on air-cooled units Checklist for Completed Installation Feature Overview Wall boxMain Menu Menu Default setpoints and allowable ranges Active AlarmsAlarm History SetpointsTime Setup OperationRestart Time Delay DateHumidity Control Method Show DIP Switch10.2 C/F Degrees Lead CompressorSetup functions, default values and allowable ranges Change PasswordsAlarm Enable Calibrate SensorsCustom Alarms Alarm Time DelayCommon Alarm Enable Alarm default time delaysLCD Display Contrast Equipment Options SwitchesCustom Text Nonvolatile MemoryRun Diagnostics Test OutputsTest Inputs Test Micro TB3-3 Connection to Terminal #3 Wallbox TB3-1 TB3-2 TB3-3 TB4-4 Wall Box DIP SwitchesTB3-4 Connection to Terminal #4 Wallbox TB3-2 Connection to Terminal #2 WallboxControl Type Response Proportional Control CoolingReheat Communications Load Control FeaturesDehumidification / Humidification Percent Required Humidification Operation System ActivationHigh Head Pressure Alarms Definitions and TroubleshootingCustom Alarms Air-Cooled SystemsHigh-Water Alarm TemperatureHumidifier Problem Alarm Loss of PowerOptional/Custom Alarms Change FilterSystem Testing Maintenance and Component Operation Discharge Pressure Refrigeration SystemSuction Pressure Thermostatic Expansion ValveGlycol Solution Maintenance Regulating Valves Water/Glycol Condensing UnitsHot Gas Bypass Optional Replacement Procedures Steam Generating Humidifier Operation Procedures Replacing the Humidifier Canister Circuit Board AdjustmentsHumidifier control board DIP switch settings AmpsMaintenance Inspection Checklist Troubleshooting Display freezes Symptom Possible Cause Check or Remedy Cooling cycle tooShort Control padsTroubleshooting Troubleshooting Troubleshooting Page Tin NetIti That