Liebert 50 & 60Hz, 8 Tons user manual Maintenance and Component Operation

Page 59

System Operation, Testing, and Maintenance

6.2Maintenance and Component Operation

6.2.1Electric Panel

The electric panel should be inspected on a semi-annual basis for any loose electrical connections.

6.2.2Filters

Filters are usually the most neglected item in an environmental control system. In order to maintain efficient operation, they should be checked monthly and changed as required. ALWAYS TURN POWER OFF BEFORE REPLACING FILTERS.

Filters are replaced by opening the hinged door on the return air filter box.

6.2.3Blower System

Monthly inspection of the blower package includes: motor mounts, belts, fan bearings, and impellers.

Fan impellers should be thoroughly inspected and any debris removed. Check to see if they are tightly mounted on the fan shaft and do not rub against the fan housing during rotation. Motor and fan bear- ings are permanently sealed and self-lubricating and do NOT need lubricated.

The drive belt should be checked monthly for signs of wear and proper tension. Pressing on belts mid- way between the sheave and pulley should produce from 1/2" to 1" (12 to 25 mm) of deflection. Belts that are too tight can cause excessive bearing wear.

Belt tension can be adjusted by raising or lowering the fan motor base. Loosen nut above motor mounting plate to remove belt. Turn nut below motor mounting plate to adjust belt tension. If belt appears cracked or worn, it should be replaced with a matched belt (identically sized). With proper care, a belt should last several years.

NOTE

After adjusting or changing the belt, always be certain that motor base nuts are tightened. The bottom adjustment nut should be finger tight. The top locking nut should be tightened with a wrench.

Air Distribution

Since all unit models are designed for constant volume air delivery, any unusual restrictions within the air circuit must be avoided. High efficiency filters can reduce air performance and evaporator capacity.

Blower Removal (Evaporator)

If the blower or bearings must be removed or serviced, use the following procedure.

1.Prepare the main center section of the three (3) piece electric panel by first marking and disconnecting all power and control wiring entering the panel.

2.Remove the electric panel by removing screws from top and bottom sections

3.Remove the bottom electric panel mounting flange from unit base.

4.Remove the belt, motor, motor mounting plate, and tensioning bolt.

5.Remove the four (4) screws holding the blower mounting rails to the sled.

! CAUTION

Protect refrigerant and water piping from damage.

6.Remove the (4) screws holding the blower mounting rails to the sled.

7.Slide the blower/rail assembly forward and rotate approximately 45 degrees and remove from unit.

8.Replace failed parts.

51

Image 59
Contents Liebert Mini-Mate2 Page Table of Contents System Performance Microprocessor Controls Microprocessor ControlSystem OPERATION, TESTING, and Maintenance AlarmsFigures Table iv Heat rejection matchup 50 Hz Table iii Heat rejection matchup 60 HzPage Standard Product Features Optional Equipment Ancillary Ship Loose Accessories Application limits, evaporator and chilled-water units Installation ConsiderationsInput Voltage Entering Fluid Temperature Min Room PreparationLocation Considerations Drycooler Evaporator Equipment Inspection upon receipt System WeightsUnit weights Locking nut Hex nut Installing the Evaporator or Chilled-Water UnitsNylock Nut Clamps are for shipping purposes only Close Coupled InstallationsHp Motor std Hp Motor opt Turns External Open Evaporator Air Distribution Filter BoxConnections for Ducted Systems Evaporator external static pressure 60 at 3750 CFM 6371 CMHPiping Connections and Coolant Requirements Drain Line Drain installationHumidifier Water Supply Line Condensate PumpChilled-Water Piping-Chilled-water Systems Only General arrangement diagram chilled-water systemsEquivalent Suction Feet Circuit Liquid Line Refrigerant R-22 PipingRecommended refrigerant line sizes Line charges field piping Total refrigerant = Units and LinesQuick Connect Fittings Ton unit refrigerant chargeOptional Filter BOX Electrical Connections, Evaporator or Chilled-Water Unit Power ConnectionsFront of Unit Evaporator unit electrical connectionsConsiderations for Specific Applications DuctingGeneral Considerations Control Connections Piping ConnectionsElectrical Connections Condensing Unit DPN000248Rev1 Heat rejection connection. Field Electrical Connections Outdoor Air-Cooled Condensing Unit InstallationEarth ground connection Electric service connectionHigh voltage Low voltageFootprint Dimensions 292 11-1/2152 Regulating Valve Water/Glycol Piping ConsiderationsCondensing Unit Fluid Requirements Indoor water/glycol condensing unit dimensional data Site Preparation and Installation Two circuits provided. Single circuit shown Optional free cooling coil 3-way valve on water/glycol units Optional Equipment PipingOptional free cooling coil 3-way valve on air-cooled units Checklist for Completed Installation Wall box Feature OverviewMain Menu Menu Setpoints Active AlarmsAlarm History Default setpoints and allowable rangesDate Setup OperationRestart Time Delay TimeLead Compressor Show DIP Switch10.2 C/F Degrees Humidity Control MethodCalibrate Sensors Change PasswordsAlarm Enable Setup functions, default values and allowable rangesAlarm default time delays Alarm Time DelayCommon Alarm Enable Custom AlarmsNonvolatile Memory Equipment Options SwitchesCustom Text LCD Display ContrastTest Inputs Run DiagnosticsTest Outputs Test Micro TB3-2 Connection to Terminal #2 Wallbox TB3-1 TB3-2 TB3-3 TB4-4 Wall Box DIP SwitchesTB3-4 Connection to Terminal #4 Wallbox TB3-3 Connection to Terminal #3 WallboxReheat Control Type Response Proportional ControlCooling Humidification Operation System Activation Load Control FeaturesDehumidification / Humidification Percent Required CommunicationsAir-Cooled Systems Alarms Definitions and TroubleshootingCustom Alarms High Head PressureLoss of Power TemperatureHumidifier Problem Alarm High-Water AlarmChange Filter Optional/Custom AlarmsSystem Testing Maintenance and Component Operation Thermostatic Expansion Valve Refrigeration SystemSuction Pressure Discharge PressureHot Gas Bypass Optional Glycol Solution MaintenanceRegulating Valves Water/Glycol Condensing Units Replacement Procedures Steam Generating Humidifier Operation Procedures Amps Circuit Board AdjustmentsHumidifier control board DIP switch settings Replacing the Humidifier CanisterMaintenance Inspection Checklist Troubleshooting Control pads Symptom Possible Cause Check or Remedy Cooling cycle tooShort Display freezesTroubleshooting Troubleshooting Troubleshooting Page That NetIti Tin