Liebert 8 Tons, 50 & 60Hz user manual Refrigeration System, Suction Pressure, Discharge Pressure

Page 60

System Operation, Testing, and Maintenance

6.2.4Electric Reheat

Reheat element sheets and fins are manufactured with stainless steel. Regular inspections are neces- sary to assure proper cleanliness of the reheating element. Should inspection reveal corrosion parti- cles on the reheating element or adjoining surfaces (including ducts and plenums), appropriate cleaning should be performed. Periodic replacement of the reheating element may be necessary to meet specific application requirements.

6.2.5Refrigeration System

Each month the components of the refrigeration system should be inspected for proper function and signs of wear. Since in most cases evidence of malfunction is present prior to component failure, peri- odic inspections can be a major factor in the prevention of most system failures. Refrigerant lines must be properly supported and not allowed to vibrate against ceilings, floors, or the unit frame. Inspect all refrigerant lines every six months for signs of wear and proper support. Inspect the capil- lary and equalizer lines from the expansion valve.

Suction Pressure

Suction pressure will vary with load conditions. Suction pressure normally ranges from 58 psi to 75 psi (405 kPa to 517 kPa). When the 3-ton circuit is operating alone, the upper range of suction pres- sure may approach 100 psig. This is a function of the unit design and is acceptable for scroll compres- sors.

Discharge Pressure

The discharge pressure will vary greatly with load and ambient conditions (Table 16). The high-pres- sure switch will shut the compressor down at its cut-out setting.

Table 16 Typical discharge pressures

System Design

psig

(kPa)

 

 

 

Air-Cooled

180-275

(1242-1895)

 

 

 

Water-Cooled

 

 

65ºF to 85ºF water

200-225

(1380-1550)

(18 to 29.4ºC)

 

 

Glycol-Cooled

210-275

(1445-1895)

 

 

 

Maximum

330

(2275)

 

 

 

High Pressure Cut-Out

360

(2480)

 

 

 

Thermostatic Expansion Valve

The thermostatic expansion valve keeps the evaporator supplied with enough refrigerant to satisfy load conditions. Proper valve operation can be determined by measuring superheat level. If too little refrigerant is being fed to the evaporator, then the superheat will be high. Conversely, if too much refrigerant is being supplied, then the superheat will be low. The correct superheat setting is between 10 and 15°F (5.6 and 8.3°C). Only the 5-ton valve is adjustable.

Air-Cooled Condensing Units

Restricted airflow through the condenser coil will reduce the operating efficiency of the unit. Addi- tionally, it can result in high compressor head pressure and loss of cooling. Using compressed air or commercial coil cleaner, clean the condenser coil of all debris that will inhibit airflow. In winter, do not permit snow to accumulate around the side or underneath the condenser. At the same time check for bent or damaged coil fins and repair as necessary. Check all refrigerant lines and capillaries for vibration and support as necessary. Carefully inspect all refrigerant lines for signs of oil leaks.

Coaxial Condensers (Water/Glycol-Cooled Condensing Units)

Each water or glycol-cooled condensing unit has a coaxial condenser consisting of an exterior steel tube and an interior copper tube. If the water supply is clean, coaxial condensers do not normally require maintenance or replacement. Should your system begin to operate at high head pressure with reduced capacity, and all other causes have been eliminated, the condenser may be obstructed or fouled and should be replaced.

52

Image 60
Contents Liebert Mini-Mate2 Page Table of Contents Microprocessor Control System Performance Microprocessor ControlsAlarms System OPERATION, TESTING, and MaintenanceFigures Table iii Heat rejection matchup 60 Hz Table iv Heat rejection matchup 50 HzPage Standard Product Features Optional Equipment Ancillary Ship Loose Accessories Installation Considerations Input Voltage Entering Fluid Temperature MinRoom Preparation Application limits, evaporator and chilled-water unitsLocation Considerations Drycooler Evaporator System Weights Unit weightsEquipment Inspection upon receipt Installing the Evaporator or Chilled-Water Units NylockLocking nut Hex nut Close Coupled Installations Nut Clamps are for shipping purposes onlyEvaporator Air Distribution Filter Box Connections for Ducted SystemsEvaporator external static pressure 60 at 3750 CFM 6371 CMH Hp Motor std Hp Motor opt Turns External OpenDrain installation Piping Connections and Coolant Requirements Drain LineCondensate Pump Humidifier Water Supply LineGeneral arrangement diagram chilled-water systems Chilled-Water Piping-Chilled-water Systems OnlyRefrigerant R-22 Piping Recommended refrigerant line sizesEquivalent Suction Feet Circuit Liquid Line Total refrigerant = Units and Lines Quick Connect FittingsTon unit refrigerant charge Line charges field pipingOptional Filter BOX Power Connections Electrical Connections, Evaporator or Chilled-Water UnitEvaporator unit electrical connections Front of UnitDucting General ConsiderationsConsiderations for Specific Applications Piping Connections Electrical Connections Condensing UnitControl Connections DPN000248Rev1 Heat rejection connection. Field Outdoor Air-Cooled Condensing Unit Installation Electrical ConnectionsElectric service connection High voltageLow voltage Earth ground connectionFootprint Dimensions 11-1/2 152292 Water/Glycol Piping Considerations Condensing Unit Fluid RequirementsRegulating Valve Indoor water/glycol condensing unit dimensional data Site Preparation and Installation Two circuits provided. Single circuit shown Optional Equipment Piping Optional free cooling coil 3-way valve on water/glycol unitsOptional free cooling coil 3-way valve on air-cooled units Checklist for Completed Installation Feature Overview Wall boxMain Menu Menu Active Alarms Alarm HistoryDefault setpoints and allowable ranges SetpointsSetup Operation Restart Time DelayTime DateShow DIP Switch 10.2 C/F DegreesHumidity Control Method Lead CompressorChange Passwords Alarm EnableSetup functions, default values and allowable ranges Calibrate SensorsAlarm Time Delay Common Alarm EnableCustom Alarms Alarm default time delaysEquipment Options Switches Custom TextLCD Display Contrast Nonvolatile MemoryRun Diagnostics Test OutputsTest Inputs Test Micro TB3-1 TB3-2 TB3-3 TB4-4 Wall Box DIP Switches TB3-4 Connection to Terminal #4 WallboxTB3-3 Connection to Terminal #3 Wallbox TB3-2 Connection to Terminal #2 WallboxControl Type Response Proportional Control CoolingReheat Load Control Features Dehumidification / Humidification Percent RequiredCommunications Humidification Operation System ActivationAlarms Definitions and Troubleshooting Custom AlarmsHigh Head Pressure Air-Cooled SystemsTemperature Humidifier Problem AlarmHigh-Water Alarm Loss of PowerOptional/Custom Alarms Change FilterSystem Testing Maintenance and Component Operation Refrigeration System Suction PressureDischarge Pressure Thermostatic Expansion ValveGlycol Solution Maintenance Regulating Valves Water/Glycol Condensing UnitsHot Gas Bypass Optional Replacement Procedures Steam Generating Humidifier Operation Procedures Circuit Board Adjustments Humidifier control board DIP switch settingsReplacing the Humidifier Canister AmpsMaintenance Inspection Checklist Troubleshooting Symptom Possible Cause Check or Remedy Cooling cycle too ShortDisplay freezes Control padsTroubleshooting Troubleshooting Troubleshooting Page Net ItiTin That