Liebert 50 & 60Hz Symptom Possible Cause Check or Remedy Cooling cycle too, Short, Control pads

Page 67

Troubleshooting

Table 18 Troubleshooting (continued)

Symptom

Possible Cause

Check or Remedy

 

 

 

Cooling cycle too

Sensor response delay too

Increase sensor response delay. See 3.12 - Calibrate Sensors.

short

short

 

Display freezes

 

During period of low humidity, static electricity can cause the control

 

program to freeze or display incorrect information. Although this is

and control pads

Static discharge

unlikely, the control can be reset by cycling power from the disconnect

do not respond

 

 

switch.

 

 

 

 

 

Condensate

Open or short circuit in

Find open or short circuit and repair power to pump.

pump does not

wiring

operate

 

 

 

 

 

 

 

 

Temperature display will indicate dashes. Check wiring from

Continuous

Failed temperature sensor

temperature/humidity board (remote sensors) to the control board or

Cooling

from control board to wallbox. Replace temperature/humidity circuit

 

 

 

board (remote sensors) or wallbox.

 

 

 

Continuous

 

 

Heating

Shorted wiring or failed

Check wiring and/or replace control board.

Dehumidification

control board

 

Humidification

 

 

 

 

 

59

Image 67
Contents Liebert Mini-Mate2 Page Table of Contents System Performance Microprocessor Controls Microprocessor ControlSystem OPERATION, TESTING, and Maintenance AlarmsFigures Table iv Heat rejection matchup 50 Hz Table iii Heat rejection matchup 60 HzPage Standard Product Features Optional Equipment Ancillary Ship Loose Accessories Application limits, evaporator and chilled-water units Installation ConsiderationsInput Voltage Entering Fluid Temperature Min Room PreparationLocation Considerations Drycooler Evaporator Unit weights System WeightsEquipment Inspection upon receipt Nylock Installing the Evaporator or Chilled-Water UnitsLocking nut Hex nut Nut Clamps are for shipping purposes only Close Coupled InstallationsHp Motor std Hp Motor opt Turns External Open Evaporator Air Distribution Filter BoxConnections for Ducted Systems Evaporator external static pressure 60 at 3750 CFM 6371 CMHPiping Connections and Coolant Requirements Drain Line Drain installationHumidifier Water Supply Line Condensate PumpChilled-Water Piping-Chilled-water Systems Only General arrangement diagram chilled-water systemsRecommended refrigerant line sizes Refrigerant R-22 PipingEquivalent Suction Feet Circuit Liquid Line Line charges field piping Total refrigerant = Units and LinesQuick Connect Fittings Ton unit refrigerant chargeOptional Filter BOX Electrical Connections, Evaporator or Chilled-Water Unit Power ConnectionsFront of Unit Evaporator unit electrical connectionsGeneral Considerations DuctingConsiderations for Specific Applications Electrical Connections Condensing Unit Piping ConnectionsControl Connections DPN000248Rev1 Heat rejection connection. Field Electrical Connections Outdoor Air-Cooled Condensing Unit InstallationEarth ground connection Electric service connectionHigh voltage Low voltageFootprint Dimensions 152 11-1/2292 Condensing Unit Fluid Requirements Water/Glycol Piping ConsiderationsRegulating Valve Indoor water/glycol condensing unit dimensional data Site Preparation and Installation Two circuits provided. Single circuit shown Optional free cooling coil 3-way valve on water/glycol units Optional Equipment PipingOptional free cooling coil 3-way valve on air-cooled units Checklist for Completed Installation Wall box Feature OverviewMain Menu Menu Setpoints Active AlarmsAlarm History Default setpoints and allowable rangesDate Setup OperationRestart Time Delay TimeLead Compressor Show DIP Switch10.2 C/F Degrees Humidity Control MethodCalibrate Sensors Change PasswordsAlarm Enable Setup functions, default values and allowable rangesAlarm default time delays Alarm Time DelayCommon Alarm Enable Custom AlarmsNonvolatile Memory Equipment Options SwitchesCustom Text LCD Display ContrastTest Outputs Run DiagnosticsTest Inputs Test Micro TB3-2 Connection to Terminal #2 Wallbox TB3-1 TB3-2 TB3-3 TB4-4 Wall Box DIP SwitchesTB3-4 Connection to Terminal #4 Wallbox TB3-3 Connection to Terminal #3 WallboxCooling Control Type Response Proportional ControlReheat Humidification Operation System Activation Load Control FeaturesDehumidification / Humidification Percent Required CommunicationsAir-Cooled Systems Alarms Definitions and TroubleshootingCustom Alarms High Head PressureLoss of Power TemperatureHumidifier Problem Alarm High-Water AlarmChange Filter Optional/Custom AlarmsSystem Testing Maintenance and Component Operation Thermostatic Expansion Valve Refrigeration SystemSuction Pressure Discharge PressureRegulating Valves Water/Glycol Condensing Units Glycol Solution MaintenanceHot Gas Bypass Optional Replacement Procedures Steam Generating Humidifier Operation Procedures Amps Circuit Board AdjustmentsHumidifier control board DIP switch settings Replacing the Humidifier CanisterMaintenance Inspection Checklist Troubleshooting Control pads Symptom Possible Cause Check or Remedy Cooling cycle tooShort Display freezesTroubleshooting Troubleshooting Troubleshooting Page That NetIti Tin