Liebert 8 Tons Evaporator Air Distribution Filter Box, Connections for Ducted Systems, Static

Page 18

Site Preparation and Installation

2.4.2Evaporator Air Distribution Filter Box

The optional filter box mounts directly to the return air opening of the evaporator. The filter box is supplied with two (2) 20% (Liebert part no. A-0320) or 30% (Liebert part no. A-0400) 25" x 20" x 4" fil- ters.

NOTE

Do not operate the unit without filters installed in return air system.

Connections for Ducted Systems

Use flexible duct work or non-flammable cloth collars to attach duct work to the unit and to help con- trol the transmission of vibrations to building structures. Insulation of duct work is vital to prevent condensation during the cooling cycle. The use of a vapor barrier is required to prevent absorption of moisture from the surrounding air into the insulation.

If the return air duct is short, or if noise is likely to be a problem, sound-absorbing insulation should be used on the duct. Duct work should be fabricated and installed in accordance with local and national codes.

Table 5 Evaporator external static pressure (60) at 3750 CFM (6371 CMH)

 

2 hp Motor (std)

3 hp Motor (opt)

Turns

 

 

 

 

 

External

 

External

Open

RPM

Static, in.

RPM

Static, in.

0

n/a

n/a

1146

1.9

 

 

 

 

 

0.5

n/a

n/a

1125

1.8

 

 

 

 

 

1

n/a

n/a

1104

1.7

 

 

 

 

 

1.5

946

0.9

1083

1.6

 

 

 

 

 

2

922

0.8

1063

1.5

 

 

 

 

 

2.5

972

0.7

1042

1.4

 

 

 

 

 

3

899

0.6

1021

1.3

 

 

 

 

 

3.5

851

0.5

1000

1.2

 

 

 

 

 

4

828

0.4

979

1.1

 

 

 

 

 

4.5

804

0.3

958

1.0

 

 

 

 

 

5

780

0.2

938

0.9

 

 

 

 

 

5.5

757

0.1

917

0.8

 

 

 

 

 

6

733

0

896

0.7

 

 

 

 

 

If free-cooling or hot water coil is ordered, reduce available external static pressure by 0.3" (8 mm). Contact Liebert Representative for other Air Volumes.

Factory setting is 0.5" (13 mm) with 2 hp motor. Field adjust to suit application.

NOTE

Maximum return air static pressure should not exceed 0.3" (8 mm) to provide proper drainage of the unit.

10

Image 18
Contents Liebert Mini-Mate2 Page Table of Contents Microprocessor Control System Performance Microprocessor ControlsAlarms System OPERATION, TESTING, and MaintenanceFigures Table iii Heat rejection matchup 60 Hz Table iv Heat rejection matchup 50 HzPage Standard Product Features Optional Equipment Ancillary Ship Loose Accessories Room Preparation Installation ConsiderationsInput Voltage Entering Fluid Temperature Min Application limits, evaporator and chilled-water unitsLocation Considerations Drycooler Evaporator System Weights Unit weightsEquipment Inspection upon receipt Installing the Evaporator or Chilled-Water Units NylockLocking nut Hex nut Close Coupled Installations Nut Clamps are for shipping purposes onlyEvaporator external static pressure 60 at 3750 CFM 6371 CMH Evaporator Air Distribution Filter BoxConnections for Ducted Systems Hp Motor std Hp Motor opt Turns External OpenDrain installation Piping Connections and Coolant Requirements Drain LineCondensate Pump Humidifier Water Supply LineGeneral arrangement diagram chilled-water systems Chilled-Water Piping-Chilled-water Systems OnlyRefrigerant R-22 Piping Recommended refrigerant line sizesEquivalent Suction Feet Circuit Liquid Line Ton unit refrigerant charge Total refrigerant = Units and LinesQuick Connect Fittings Line charges field pipingOptional Filter BOX Power Connections Electrical Connections, Evaporator or Chilled-Water UnitEvaporator unit electrical connections Front of UnitDucting General ConsiderationsConsiderations for Specific Applications Piping Connections Electrical Connections Condensing UnitControl Connections DPN000248Rev1 Heat rejection connection. Field Outdoor Air-Cooled Condensing Unit Installation Electrical ConnectionsLow voltage Electric service connectionHigh voltage Earth ground connectionFootprint Dimensions 11-1/2 152292 Water/Glycol Piping Considerations Condensing Unit Fluid RequirementsRegulating Valve Indoor water/glycol condensing unit dimensional data Site Preparation and Installation Two circuits provided. Single circuit shown Optional Equipment Piping Optional free cooling coil 3-way valve on water/glycol unitsOptional free cooling coil 3-way valve on air-cooled units Checklist for Completed Installation Feature Overview Wall boxMain Menu Menu Default setpoints and allowable ranges Active AlarmsAlarm History SetpointsTime Setup OperationRestart Time Delay DateHumidity Control Method Show DIP Switch10.2 C/F Degrees Lead CompressorSetup functions, default values and allowable ranges Change PasswordsAlarm Enable Calibrate SensorsCustom Alarms Alarm Time DelayCommon Alarm Enable Alarm default time delaysLCD Display Contrast Equipment Options SwitchesCustom Text Nonvolatile MemoryRun Diagnostics Test OutputsTest Inputs Test Micro TB3-3 Connection to Terminal #3 Wallbox TB3-1 TB3-2 TB3-3 TB4-4 Wall Box DIP SwitchesTB3-4 Connection to Terminal #4 Wallbox TB3-2 Connection to Terminal #2 WallboxControl Type Response Proportional Control CoolingReheat Communications Load Control FeaturesDehumidification / Humidification Percent Required Humidification Operation System ActivationHigh Head Pressure Alarms Definitions and TroubleshootingCustom Alarms Air-Cooled SystemsHigh-Water Alarm TemperatureHumidifier Problem Alarm Loss of PowerOptional/Custom Alarms Change FilterSystem Testing Maintenance and Component Operation Discharge Pressure Refrigeration SystemSuction Pressure Thermostatic Expansion ValveGlycol Solution Maintenance Regulating Valves Water/Glycol Condensing UnitsHot Gas Bypass Optional Replacement Procedures Steam Generating Humidifier Operation Procedures Replacing the Humidifier Canister Circuit Board AdjustmentsHumidifier control board DIP switch settings AmpsMaintenance Inspection Checklist Troubleshooting Display freezes Symptom Possible Cause Check or Remedy Cooling cycle tooShort Control padsTroubleshooting Troubleshooting Troubleshooting Page Tin NetIti That