Liebert 8 Tons Alarm Time Delay, Common Alarm Enable, Custom Alarms, Alarm default time delays

Page 48

Microprocessor Control

3.14Alarm Time Delay

Each individual alarm can be programmed with a time delay (Table 13), causing the unit to delay a specified amount of time (0-255 seconds) before recognizing the alarm. The alarm condition must be present for the full amount of the time delay before the alarm will sound. If the alarm condition is diverted prematurely, the alarm will not be recognized and the time delay will automatically reset.

NOTE

For software alarms such as “loss of power” and “short cycle,” the time delay should be left at the factory default of 0.

Table 13 Alarm default time delays

 

Default Time Delay

Alarm

(seconds)

 

 

Hum Prob

2

 

 

Chng Fltr

2

 

 

Custom Alarm #1

0

 

 

Custom Alarm #2

0

 

 

Custom Alarm #3

0

 

 

High Temperature

30

 

 

Low Temperature

30

 

 

High Humidity

30

 

 

Low Humidity

30

 

 

Short Cycle 1 & 2

0

 

 

Loss of Power

0

 

 

3.15Common Alarm Enable

Each individual alarm can be selected to activate/deactivate the common alarm relay. If the energize common alarm function is set to YES, the relay is energized immediately as the alarm is enunciated, and de-energized when the alarm condition has cleared. If the alarm is completely DISABLED, the alarm has no effect on the common alarm relay. Use the UP/DOWN arrows to scroll to a particular alarm, press the ENTER button to select it, then press the ENTER key again to select Yes or No.

3.16Custom Alarms

The custom alarm messages can be selected from a list of standard alarm messages, or the operator can write his/her own message. A MAXIMUM OF THREE (3) ALARM MESSAGES CAN BE CUS-

TOMIZED.

The text for custom alarms can be changed at any time by selecting “CUSTOM ALARMS”. To change the text for a custom alarm, select the alarm you would like to change, 1, 2 or 3. Using the UP/DOWN arrows, step through the list of seven standard alarm messages (listed below) and two custom alarms. Select the alarm message desired and store it by pressing ENTER.

SMOKE DETECTED

CUSTOM 2

CUSTOM 3

STANDBY GC PUMP

WATER FLOW LOSS

STANDBY UNIT ON

CUSTOM 1

40

Image 48
Contents Liebert Mini-Mate2 Page Table of Contents Microprocessor Control System Performance Microprocessor ControlsAlarms System OPERATION, TESTING, and MaintenanceFigures Table iii Heat rejection matchup 60 Hz Table iv Heat rejection matchup 50 HzPage Standard Product Features Optional Equipment Ancillary Ship Loose Accessories Installation Considerations Input Voltage Entering Fluid Temperature MinRoom Preparation Application limits, evaporator and chilled-water unitsLocation Considerations Drycooler Evaporator System Weights Unit weightsEquipment Inspection upon receipt Installing the Evaporator or Chilled-Water Units NylockLocking nut Hex nut Close Coupled Installations Nut Clamps are for shipping purposes onlyEvaporator Air Distribution Filter Box Connections for Ducted SystemsEvaporator external static pressure 60 at 3750 CFM 6371 CMH Hp Motor std Hp Motor opt Turns External OpenDrain installation Piping Connections and Coolant Requirements Drain LineCondensate Pump Humidifier Water Supply LineGeneral arrangement diagram chilled-water systems Chilled-Water Piping-Chilled-water Systems OnlyRefrigerant R-22 Piping Recommended refrigerant line sizesEquivalent Suction Feet Circuit Liquid Line Total refrigerant = Units and Lines Quick Connect FittingsTon unit refrigerant charge Line charges field pipingOptional Filter BOX Power Connections Electrical Connections, Evaporator or Chilled-Water UnitEvaporator unit electrical connections Front of UnitDucting General ConsiderationsConsiderations for Specific Applications Piping Connections Electrical Connections Condensing UnitControl Connections DPN000248Rev1 Heat rejection connection. Field Outdoor Air-Cooled Condensing Unit Installation Electrical ConnectionsElectric service connection High voltageLow voltage Earth ground connectionFootprint Dimensions 11-1/2 152292 Water/Glycol Piping Considerations Condensing Unit Fluid RequirementsRegulating Valve Indoor water/glycol condensing unit dimensional data Site Preparation and Installation Two circuits provided. Single circuit shown Optional Equipment Piping Optional free cooling coil 3-way valve on water/glycol unitsOptional free cooling coil 3-way valve on air-cooled units Checklist for Completed Installation Feature Overview Wall boxMain Menu Menu Active Alarms Alarm HistoryDefault setpoints and allowable ranges SetpointsSetup Operation Restart Time DelayTime DateShow DIP Switch 10.2 C/F DegreesHumidity Control Method Lead CompressorChange Passwords Alarm EnableSetup functions, default values and allowable ranges Calibrate SensorsAlarm Time Delay Common Alarm EnableCustom Alarms Alarm default time delaysEquipment Options Switches Custom TextLCD Display Contrast Nonvolatile MemoryRun Diagnostics Test OutputsTest Inputs Test Micro TB3-1 TB3-2 TB3-3 TB4-4 Wall Box DIP Switches TB3-4 Connection to Terminal #4 WallboxTB3-3 Connection to Terminal #3 Wallbox TB3-2 Connection to Terminal #2 WallboxControl Type Response Proportional Control CoolingReheat Load Control Features Dehumidification / Humidification Percent RequiredCommunications Humidification Operation System ActivationAlarms Definitions and Troubleshooting Custom AlarmsHigh Head Pressure Air-Cooled SystemsTemperature Humidifier Problem AlarmHigh-Water Alarm Loss of PowerOptional/Custom Alarms Change FilterSystem Testing Maintenance and Component Operation Refrigeration System Suction PressureDischarge Pressure Thermostatic Expansion ValveGlycol Solution Maintenance Regulating Valves Water/Glycol Condensing UnitsHot Gas Bypass Optional Replacement Procedures Steam Generating Humidifier Operation Procedures Circuit Board Adjustments Humidifier control board DIP switch settingsReplacing the Humidifier Canister AmpsMaintenance Inspection Checklist Troubleshooting Symptom Possible Cause Check or Remedy Cooling cycle too ShortDisplay freezes Control padsTroubleshooting Troubleshooting Troubleshooting Page Net ItiTin That