Microprocessor Control
3.14Alarm Time Delay
Each individual alarm can be programmed with a time delay (Table 13), causing the unit to delay a specified amount of time
NOTE
For software alarms such as “loss of power” and “short cycle,” the time delay should be left at the factory default of 0.
Table 13 Alarm default time delays
| Default Time Delay |
Alarm | (seconds) |
|
|
Hum Prob | 2 |
|
|
Chng Fltr | 2 |
|
|
Custom Alarm #1 | 0 |
|
|
Custom Alarm #2 | 0 |
|
|
Custom Alarm #3 | 0 |
|
|
High Temperature | 30 |
|
|
Low Temperature | 30 |
|
|
High Humidity | 30 |
|
|
Low Humidity | 30 |
|
|
Short Cycle 1 & 2 | 0 |
|
|
Loss of Power | 0 |
|
|
3.15Common Alarm Enable
Each individual alarm can be selected to activate/deactivate the common alarm relay. If the energize common alarm function is set to YES, the relay is energized immediately as the alarm is enunciated, and
3.16Custom Alarms
The custom alarm messages can be selected from a list of standard alarm messages, or the operator can write his/her own message. A MAXIMUM OF THREE (3) ALARM MESSAGES CAN BE CUS-
TOMIZED.
The text for custom alarms can be changed at any time by selecting “CUSTOM ALARMS”. To change the text for a custom alarm, select the alarm you would like to change, 1, 2 or 3. Using the UP/DOWN arrows, step through the list of seven standard alarm messages (listed below) and two custom alarms. Select the alarm message desired and store it by pressing ENTER.
•SMOKE DETECTED
•CUSTOM 2
•CUSTOM 3
•STANDBY GC PUMP
•WATER FLOW LOSS
•STANDBY UNIT ON
•CUSTOM 1
40