Liebert 8 Tons 10.2 C/F Degrees, Humidity Control Method, Lead Compressor, Show DIP Switch

Page 46

Microprocessor Control

3.10.2C/F Degrees

The control may be selected to show readings and setpoints in either degrees Fahrenheit (°F) or in degrees Celsius (°C). To change the value use ENTER to select this function, then use the UP/DOWN arrow to change the value. Press ENTER to store the value.

3.10.3Humidity Control Method

The operator may select either relative (direct) or absolute (predictive) humidity control. If “relative” is selected, the RH control is taken directly from the RH sensor. If “absolute” is selected, the RH con- trol is automatically adjusted whenever return air temperature deviates from the desired tempera- ture setpoint (i.e., predictive humidity control). The LCD display will indicate percentage relative humidity for both methods of control. If the “absolute” feature is selected, the adjusted humidity read- ing will also be shown. When utilizing the predictive humidity control feature, the humidity level is automatically adjusted ~2% RH for each degree difference between the return air temperature and the temperature setpoint.

Unnecessary dehumidification can result when overcooling occurs during a dehumidification cycle. This is due to a higher than normal RH reading caused by overcooling the room (about 2% RH for each degree of overcooling). This drop in temperature extends the dehumidification cycle. Later, when the dehumidification ends and the temperature rises to the setpoint, the RH reading falls. The final RH reading will then be lower than actually desired. If the temperature drop was significant enough, the percentage RH could be low enough to activate the humidifier.

If the absolute humidity control is selected, over-dehumidification may be avoided. When overcooling occurs (i.e., causing an increase in the RH reading) the humidity control program estimates what the RH will be when the dehumidification cycle ends and temperature returns to the setpoint. This allows the dehumidification cycle to end at the proper time. Predictive humidity control can greatly reduce energy consumption by minimizing both compressor/reheat operation. Use the UP/DOWN ARROW key to select the desired humidity control method.

3.10.4Lead Compressor

This function allows the user to select which compressor is the lead: Compressor 1 (3 ton), Compres- sor 2 (5 ton), or Auto. The factory default is Auto. If Auto is selected, the control will determine which compressor is to be the lead compressor based on the average room load over the previous one hour of operation.

3.10.5Show DIP Switch

This function shows the position of the DIP switches which are located on the control board in the unit. 1 = Switch is “ON” and 0 = Switch is “OFF”. For more information on the DIP switches and their functions, see Table 17 Equipment Switch Settings.

3.10.6Valve Time (For Systems With a Modulating Chilled-Water Valve)

This function shows the full valve travel time of the modulating valve on a chilled-water system. This is the time it takes for the valve to travel from full closed to full open. It is programmable from 50 to 250 seconds; factory default time is 165 seconds and should not be changed unless actual valve travel time is not correct. The full valve travel time is used by the control to determine the appropriate valve position. For example, if the valve travel time is 165 seconds and 50% cooling is being called for, the valve will open for 83 seconds to achieve 50% open.

38

Image 46
Contents Liebert Mini-Mate2 Page Table of Contents Microprocessor Control System Performance Microprocessor ControlsAlarms System OPERATION, TESTING, and MaintenanceFigures Table iii Heat rejection matchup 60 Hz Table iv Heat rejection matchup 50 HzPage Standard Product Features Optional Equipment Ancillary Ship Loose Accessories Room Preparation Installation ConsiderationsInput Voltage Entering Fluid Temperature Min Application limits, evaporator and chilled-water unitsLocation Considerations Drycooler Evaporator Unit weights System WeightsEquipment Inspection upon receipt Nylock Installing the Evaporator or Chilled-Water UnitsLocking nut Hex nut Close Coupled Installations Nut Clamps are for shipping purposes onlyEvaporator external static pressure 60 at 3750 CFM 6371 CMH Evaporator Air Distribution Filter BoxConnections for Ducted Systems Hp Motor std Hp Motor opt Turns External OpenDrain installation Piping Connections and Coolant Requirements Drain LineCondensate Pump Humidifier Water Supply LineGeneral arrangement diagram chilled-water systems Chilled-Water Piping-Chilled-water Systems OnlyRecommended refrigerant line sizes Refrigerant R-22 PipingEquivalent Suction Feet Circuit Liquid Line Ton unit refrigerant charge Total refrigerant = Units and LinesQuick Connect Fittings Line charges field pipingOptional Filter BOX Power Connections Electrical Connections, Evaporator or Chilled-Water UnitEvaporator unit electrical connections Front of UnitGeneral Considerations DuctingConsiderations for Specific Applications Electrical Connections Condensing Unit Piping ConnectionsControl Connections DPN000248Rev1 Heat rejection connection. Field Outdoor Air-Cooled Condensing Unit Installation Electrical ConnectionsLow voltage Electric service connectionHigh voltage Earth ground connectionFootprint Dimensions 152 11-1/2292 Condensing Unit Fluid Requirements Water/Glycol Piping ConsiderationsRegulating Valve Indoor water/glycol condensing unit dimensional data Site Preparation and Installation Two circuits provided. Single circuit shown Optional Equipment Piping Optional free cooling coil 3-way valve on water/glycol unitsOptional free cooling coil 3-way valve on air-cooled units Checklist for Completed Installation Feature Overview Wall boxMain Menu Menu Default setpoints and allowable ranges Active AlarmsAlarm History SetpointsTime Setup OperationRestart Time Delay DateHumidity Control Method Show DIP Switch10.2 C/F Degrees Lead CompressorSetup functions, default values and allowable ranges Change PasswordsAlarm Enable Calibrate SensorsCustom Alarms Alarm Time DelayCommon Alarm Enable Alarm default time delaysLCD Display Contrast Equipment Options SwitchesCustom Text Nonvolatile MemoryTest Outputs Run DiagnosticsTest Inputs Test Micro TB3-3 Connection to Terminal #3 Wallbox TB3-1 TB3-2 TB3-3 TB4-4 Wall Box DIP SwitchesTB3-4 Connection to Terminal #4 Wallbox TB3-2 Connection to Terminal #2 WallboxCooling Control Type Response Proportional ControlReheat Communications Load Control FeaturesDehumidification / Humidification Percent Required Humidification Operation System ActivationHigh Head Pressure Alarms Definitions and TroubleshootingCustom Alarms Air-Cooled SystemsHigh-Water Alarm TemperatureHumidifier Problem Alarm Loss of PowerOptional/Custom Alarms Change FilterSystem Testing Maintenance and Component Operation Discharge Pressure Refrigeration SystemSuction Pressure Thermostatic Expansion ValveRegulating Valves Water/Glycol Condensing Units Glycol Solution MaintenanceHot Gas Bypass Optional Replacement Procedures Steam Generating Humidifier Operation Procedures Replacing the Humidifier Canister Circuit Board AdjustmentsHumidifier control board DIP switch settings AmpsMaintenance Inspection Checklist Troubleshooting Display freezes Symptom Possible Cause Check or Remedy Cooling cycle tooShort Control padsTroubleshooting Troubleshooting Troubleshooting Page Tin NetIti That