Liebert 8 Tons, 50 & 60Hz user manual Replacement Procedures

Page 62

System Operation, Testing, and Maintenance

Replacement Procedures

Compressor Replacement: Infrequently a fault in the motor insulation may result in a motor burn- out (if system is properly installed, motor burnout rarely occurs). Primarily this type of failure is due to mechanical or lubrication problems, where the burnout is a secondary consequence.

Early detection can prevent a large percentage of the problems that can cause compressor failures. Periodic maintenance inspections by alert service personnel (i.e., identification of abnormal opera- tion) can be a major factor in reducing maintenance costs. It is easier and more cost-effective to imple- ment the necessary preventative steps that ensure proper system operation; rather than ignore a problem until it results in compressor failure and costly replacement. When troubleshooting a com- pressor problem, check all electrical components for proper operation:

! CAUTION

Avoid touching or contacting the gas and oils with exposed skin. Severe burns will result. Use long rubber gloves in handling contaminated parts.

• Check all fuses and circuit breakers.

• Check pressure switch operation.

• If a compressor failure has occurred, determine whether its cause is an electrical or mechanical problem.

! CAUTION

System contains refrigerant. Recover refrigerant before maintenance

Mechanical Failure: If you have determined that a mechanical failure has occurred, the compressor must be replaced.

Electrical Failure: In the event of an electrical failure and subsequent burnout of the refrigeration com- pressor motor, proper procedures must be followed to thoroughly remove any acids that would cause a future failure. There are two kits that can be used with a complete compressor burnout: Sporlan System Cleaner and Alco Dri-Kleener. Follow the manufacturer's procedure. DAMAGE TO A REPLACEMENT COMPRES-

SOR DUE TO IMPROPER SYSTEM CLEANING CONSTITUTES ABUSE UNDER THE TERMS OF THE WARRANTY, THEREBY VOIDING THE WARRANTY.

Replacement compressors are available from your Liebert supplier and will be shipped to the job site in a reusable crate (as required by the service contractor). If the compressor is under warranty, it must be returned to Liebert in order to receive proper warranty credit. It should be returned in the same container the replacement was shipped in. The possible cause(s) or condition(s) of the damage should be legibly recorded on the provided return tag.

Proper procedures to remove and replace the failed compressor are:

1.Disconnect power

2.Attach suction and discharge gauges to access fittings.

3.Recover refrigerant using standard recovery procedures and equipment.

NOTE

Release of refrigerant to the atmosphere is harmful to the environment and unlawful. Refrigerant must be recycled or discarded in accordance with federal, state, and local regulations.

4.Remove failed compressor.

5.Install replacement compressor and make all connections. Pressurize and leak test the system at approximately 150 psig (1034kPa) pressure.

6.Follow manufacturer's instructions for clean out kits.

7.Evacuate the system twice to 1500 microns, and the third time to 500 microns. Break the vacuum each time with clean, dry refrigerant to 2 psig (13.8 kPa).

8.Charge the system with refrigerant (R-22) based on requirements of the evaporator, condensing unit, and lines. Refer to the installation manual or the unit nameplate.

9.Apply power and operate the system. Check for proper operation. Refer to Table 16 for discharge pressure.

54

Image 62
Contents Liebert Mini-Mate2 Page Table of Contents Microprocessor Control System Performance Microprocessor ControlsAlarms System OPERATION, TESTING, and MaintenanceFigures Table iii Heat rejection matchup 60 Hz Table iv Heat rejection matchup 50 HzPage Standard Product Features Optional Equipment Ancillary Ship Loose Accessories Room Preparation Installation ConsiderationsInput Voltage Entering Fluid Temperature Min Application limits, evaporator and chilled-water unitsLocation Considerations Drycooler Evaporator Equipment Inspection upon receipt System WeightsUnit weights Locking nut Hex nut Installing the Evaporator or Chilled-Water UnitsNylock Close Coupled Installations Nut Clamps are for shipping purposes onlyEvaporator external static pressure 60 at 3750 CFM 6371 CMH Evaporator Air Distribution Filter BoxConnections for Ducted Systems Hp Motor std Hp Motor opt Turns External OpenDrain installation Piping Connections and Coolant Requirements Drain LineCondensate Pump Humidifier Water Supply LineGeneral arrangement diagram chilled-water systems Chilled-Water Piping-Chilled-water Systems OnlyEquivalent Suction Feet Circuit Liquid Line Refrigerant R-22 PipingRecommended refrigerant line sizes Ton unit refrigerant charge Total refrigerant = Units and LinesQuick Connect Fittings Line charges field pipingOptional Filter BOX Power Connections Electrical Connections, Evaporator or Chilled-Water UnitEvaporator unit electrical connections Front of UnitConsiderations for Specific Applications DuctingGeneral Considerations Control Connections Piping ConnectionsElectrical Connections Condensing Unit DPN000248Rev1 Heat rejection connection. Field Outdoor Air-Cooled Condensing Unit Installation Electrical ConnectionsLow voltage Electric service connectionHigh voltage Earth ground connectionFootprint Dimensions 292 11-1/2152 Regulating Valve Water/Glycol Piping ConsiderationsCondensing Unit Fluid Requirements Indoor water/glycol condensing unit dimensional data Site Preparation and Installation Two circuits provided. Single circuit shown Optional Equipment Piping Optional free cooling coil 3-way valve on water/glycol unitsOptional free cooling coil 3-way valve on air-cooled units Checklist for Completed Installation Feature Overview Wall boxMain Menu Menu Default setpoints and allowable ranges Active AlarmsAlarm History SetpointsTime Setup OperationRestart Time Delay DateHumidity Control Method Show DIP Switch10.2 C/F Degrees Lead CompressorSetup functions, default values and allowable ranges Change PasswordsAlarm Enable Calibrate SensorsCustom Alarms Alarm Time DelayCommon Alarm Enable Alarm default time delaysLCD Display Contrast Equipment Options SwitchesCustom Text Nonvolatile MemoryTest Inputs Run DiagnosticsTest Outputs Test Micro TB3-3 Connection to Terminal #3 Wallbox TB3-1 TB3-2 TB3-3 TB4-4 Wall Box DIP SwitchesTB3-4 Connection to Terminal #4 Wallbox TB3-2 Connection to Terminal #2 WallboxReheat Control Type Response Proportional ControlCooling Communications Load Control FeaturesDehumidification / Humidification Percent Required Humidification Operation System ActivationHigh Head Pressure Alarms Definitions and TroubleshootingCustom Alarms Air-Cooled SystemsHigh-Water Alarm TemperatureHumidifier Problem Alarm Loss of PowerOptional/Custom Alarms Change FilterSystem Testing Maintenance and Component Operation Discharge Pressure Refrigeration SystemSuction Pressure Thermostatic Expansion ValveHot Gas Bypass Optional Glycol Solution MaintenanceRegulating Valves Water/Glycol Condensing Units Replacement Procedures Steam Generating Humidifier Operation Procedures Replacing the Humidifier Canister Circuit Board AdjustmentsHumidifier control board DIP switch settings AmpsMaintenance Inspection Checklist Troubleshooting Display freezes Symptom Possible Cause Check or Remedy Cooling cycle tooShort Control padsTroubleshooting Troubleshooting Troubleshooting Page Tin NetIti That