Liebert 50 & 60Hz Ducting, General Considerations, Considerations for Specific Applications

Page 27

Site Preparation and Installation

2.5Indoor Air-Cooled Centrifugal Fan Condensing Unit Installation

2.5.1Location Considerations

The centrifugal fan air-cooled condensing unit may be located above the dropped ceiling or any remote indoor area. If noise is of concern, the condensing unit should be located away from personnel. Normal operating sound may be objectionable if the condensing unit is placed near quiet work areas.

To mount the unit in the ceiling, refer to 2.4 - Installing the Evaporator or Chilled-Water Units for hanging guidelines and to Figure 13 for dimensional data.

2.5.2Ducting

Fan operation is designed for 5000 CFM (8495 CMH) at 0.5" external static pressure.

General Considerations

Use flexible duct work or nonflammable cloth collars to attach duct work to the unit and to control vibration transmission to the building. Attach the duct work to the unit using the flanges provided. Locate the unit and duct work so that the discharge air does not short circuit to the return air inlet.

Duct work that runs through a conditioned space or is exposed to areas where condensation may occur must be insulated. Duct work should be suspended using flexible hangers. Duct work should not be fastened directly to the building structure.

For multiple unit installations, space the units so that the hot condensing unit exhaust air is not directed toward the air inlet of an adjacent unit.

Considerations for Specific Applications

In applications where the ceiling plenum is used as the heat rejection domain, the discharge air must be directed away from the condensing unit air inlet and a screen must be added to the end of the discharge duct to protect service personnel. Locate the air discharge a minimum of 4 feet from an adjacent wall. Failure to do so may result in reduced air flow and poor system performance.

If the condensing unit draws air from the outside of the building, rain hoods must be installed. Hood intake dimensions should be the same as the condensing unit duct dimensions. In addition, install a triple layer bird screen over rain hood openings to eliminate the possibility of insects, birds, water, or debris entering the unit. Avoid directing the hot exhaust air toward adjacent doors or windows.

19

Image 27
Contents Liebert Mini-Mate2 Page Table of Contents System Performance Microprocessor Controls Microprocessor ControlSystem OPERATION, TESTING, and Maintenance AlarmsFigures Table iv Heat rejection matchup 50 Hz Table iii Heat rejection matchup 60 HzPage Standard Product Features Optional Equipment Ancillary Ship Loose Accessories Application limits, evaporator and chilled-water units Installation ConsiderationsInput Voltage Entering Fluid Temperature Min Room PreparationLocation Considerations Drycooler Evaporator System Weights Unit weightsEquipment Inspection upon receipt Installing the Evaporator or Chilled-Water Units NylockLocking nut Hex nut Nut Clamps are for shipping purposes only Close Coupled InstallationsHp Motor std Hp Motor opt Turns External Open Evaporator Air Distribution Filter BoxConnections for Ducted Systems Evaporator external static pressure 60 at 3750 CFM 6371 CMHPiping Connections and Coolant Requirements Drain Line Drain installationHumidifier Water Supply Line Condensate PumpChilled-Water Piping-Chilled-water Systems Only General arrangement diagram chilled-water systemsRefrigerant R-22 Piping Recommended refrigerant line sizesEquivalent Suction Feet Circuit Liquid Line Line charges field piping Total refrigerant = Units and LinesQuick Connect Fittings Ton unit refrigerant chargeOptional Filter BOX Electrical Connections, Evaporator or Chilled-Water Unit Power ConnectionsFront of Unit Evaporator unit electrical connectionsDucting General ConsiderationsConsiderations for Specific Applications Piping Connections Electrical Connections Condensing UnitControl Connections DPN000248Rev1 Heat rejection connection. Field Electrical Connections Outdoor Air-Cooled Condensing Unit InstallationEarth ground connection Electric service connectionHigh voltage Low voltageFootprint Dimensions 11-1/2 152292 Water/Glycol Piping Considerations Condensing Unit Fluid RequirementsRegulating Valve Indoor water/glycol condensing unit dimensional data Site Preparation and Installation Two circuits provided. Single circuit shown Optional free cooling coil 3-way valve on water/glycol units Optional Equipment PipingOptional free cooling coil 3-way valve on air-cooled units Checklist for Completed Installation Wall box Feature OverviewMain Menu Menu Setpoints Active AlarmsAlarm History Default setpoints and allowable rangesDate Setup OperationRestart Time Delay TimeLead Compressor Show DIP Switch10.2 C/F Degrees Humidity Control MethodCalibrate Sensors Change PasswordsAlarm Enable Setup functions, default values and allowable rangesAlarm default time delays Alarm Time DelayCommon Alarm Enable Custom AlarmsNonvolatile Memory Equipment Options SwitchesCustom Text LCD Display ContrastRun Diagnostics Test OutputsTest Inputs Test Micro TB3-2 Connection to Terminal #2 Wallbox TB3-1 TB3-2 TB3-3 TB4-4 Wall Box DIP SwitchesTB3-4 Connection to Terminal #4 Wallbox TB3-3 Connection to Terminal #3 WallboxControl Type Response Proportional Control CoolingReheat Humidification Operation System Activation Load Control FeaturesDehumidification / Humidification Percent Required CommunicationsAir-Cooled Systems Alarms Definitions and TroubleshootingCustom Alarms High Head PressureLoss of Power TemperatureHumidifier Problem Alarm High-Water AlarmChange Filter Optional/Custom AlarmsSystem Testing Maintenance and Component Operation Thermostatic Expansion Valve Refrigeration SystemSuction Pressure Discharge PressureGlycol Solution Maintenance Regulating Valves Water/Glycol Condensing UnitsHot Gas Bypass Optional Replacement Procedures Steam Generating Humidifier Operation Procedures Amps Circuit Board AdjustmentsHumidifier control board DIP switch settings Replacing the Humidifier CanisterMaintenance Inspection Checklist Troubleshooting Control pads Symptom Possible Cause Check or Remedy Cooling cycle tooShort Display freezesTroubleshooting Troubleshooting Troubleshooting Page That NetIti Tin