Carrier 58CTA/CTX instruction manual Furnace Vent, Diameter Vent Height Orientation INPUTBTUH/HR

Page 32

58CT

SEE NOTES: 1,2,4,5,7,8,9

A02068

Fig. 47 - Horizontal Right Application-Vent Elbow Left

NOTES: Venting Notes for Fig. 35---47

1.For common vent, vent connector sizing and vent material: United States--- ---use the NFGC Canada --- ---use the CAN/CSA---B149.1---05

2.Immediately increase to 5---in. or 6---in. (127 or 152 mm) vent connector outside furnace casing when 5---in. (127 mm) vent connector is required, refer to Note 1 above.

3.Side outlet vent for upflow and downflow installations must use Type B vent immediately after exiting the furnace, except when KGAVG0101DFG, Downflow Vent Guard Kit, is used in the downflow position.

4.Type---B vent where required, refer to Note 1 above.

5.Four ---in. (102 mm) single---wall (26 ga. min.) vent must be used inside furnace casing and when the KGAVG0101DFG Downflow Vent Guard Kit is used external to the furnace.

6.Accessory Downflow Vent Guard Kit, KGAVG0101DFG required in downflow installations with lower vent configuration.

7.Chimney Adapter Kit may be required for exterior masonry chimney applications. Refer to Chimney Adapter Kit, KGACA02014FC or KGACA02015FC, for sizing and complete application details.

8.Secure vent connector to furnace elbow with (2) corrosion ---resistant sheet metal screws, spaced approximately 180_ apart.

9.Secure all other single wall vent connector joints with (3) corrosion resistant screws spaced approximately 120_ apart. Secure Type---B vent connectors per vent connector manufacturer’s recommendations.

10.The total height of the vent and connector shall be at least seven feet (2 M) for the 154,000 Btuh gas input rate model when installed in a downflow applica- tion with furnace elbow turned to left side with the connector elbow outside furnace casing pointing upward. (See Fig. 40.)

Caution!! For the following applications, use the minimum vertical heights as specified below.

For all other applications, follow exclusively the National Fuel Gas Code

FURNACE

VENT

FURNACE

MINIMUM VENT

MINIMUM VERTICAL

DIAMETER

VENT HEIGHT

ORIENTATION

ORIENTATION

INPUT(BTUH/HR)

IN. (mm)*

FT. (M)**

 

 

 

 

 

 

 

 

 

Vent elbow left, then

154,000

 

 

Downflow

132,000

5 (127)

12 (3.6)

up Fig. 39

 

110,000(036/--- 12 only)

 

 

 

 

 

 

 

 

 

 

 

Horizontal Left

Vent elbow right,

154,000

5 (127)

7 (.65)

then up Fig. 42

132,000

 

 

 

 

 

 

 

 

Horizontal Left

Vent Elbow up Fig.

154,000

5 (127)

7 (.65)

43

132,000

 

 

 

 

 

 

 

 

Horizontal Left

Vent elbow right Fig.

154,000

5 (127)

7 (.65)

44

 

 

 

 

 

 

 

 

 

Downflow

Vent elbow up then

110,000 (036/--- 12 only)

5 (127)

10 (3.0)

left Fig. 37

 

 

 

 

 

 

 

 

 

Downflow

Vent elbow up, then

110,000 (036/--- 12 only)

5 (127)

10 (3.0)

right Fig. 40

 

 

 

 

*4 in. (102 mm) inside casing or vent guard **Including 4 in. (102 mm) vent section(s)

NOTE: All vent configurations must also meet National Fuel Gas Code venting requirements NFGC.

32

Image 32
Contents Ama CUT Hazard Safety ConsiderationsFurnace Reliability Hazard Dimensions IntroductionClearances to Combustibles Electrostatic Discharge ESD Precautions Procedure Codes and StandardsCarbon Monoxide Poisoning and Unit Damage Hazard LocationGeneral FIRE, Injury or Death Hazard Fire HazardProperty Damage Hazard Location Relative to Cooling EquipmentAIR for Combustion Ventilation Furnace Corrosion HazardCarbon Monoxide Poisoning Hazard Outdoor Combustion Air MethodAir for Combustion, Ventilation, and Dilution for Outdoors Installation Upflow InstallationDownflow Installation Horizontal InstallationFIRE, EXPLOSION, and Carbon Monoxide Poisoning Hazard Suspended Furnace SupportPlatform Furnace Support Roll-Out ProtectionOpening dimensions In. mm Duct FlangesHorizontal Unit Suspension Filter Arrangement Carbon Monoxide Poisoning Hazard AIR DuctsGeneral Requirements Ductwork Acoustical Treatment Supply Air ConnectionsSpeed External Static Pressure IN. WC Size Inlet Air Delivery CFM With FilterFurnace Air Delivery CFM With Filter* Downflow FurnacesReturn Air Connections GAS Piping Fire or Explosion HazardUpflow Return Air Configurations and Restrictions Maximum Capacity of Pipe Furnace Damage HazardWiring Electrical Connections Electrical Shock HazardElectrical Shock and Fire Hazard Furnace MAY not Operate HazardElectrical Connection to J-BOX Electrical DataBOX Relocation Power Cord Installation in Furnace J-BOX BX. Cable Installation in Furnace J-BOXElectrical Box on Furnace Casing Side. See Fig Fire or Electrical Shock HazardTwo-Stage Furnace with Two-Speed Air Conditioner See notes 2, 11, and 12 on the page following these figures Accessories VentingGeneral Venting Requirements Masonry Chimney RequirementsChimney Inspection Chart Vent Height Appliance Application RequirementsInternal Area of Chimney Upflow Application-Vent Elbow Up Downflow Application-Vent Elbow Up then Left Horizontal Left Application Vent Elbow Left Furnace Vent Diameter Vent Height Orientation INPUTBTUH/HRUsing Tin Snips to Cut Tie Points Burn Hazard START-UP, ADJUSTMENT, and Safety CheckGeneral Start-Up Procedures AdjustmentsStage Furnace Setup Switch Description Fire and Explosion HazardAltitude Derate Multiplier for U.S.A Redundant Automatic Gas Control ValveOrifice Hole Seconds Size of Test Dial For Revolution Gas Rate cu ft. /hrFurnace Overheating Hazard Speed Selection Color Speed AS ShippedCheck Safety Controls ChecklistStage Furnace Blower OFF delay Setup Switch Desired Heating Mode Setup Switch Blower OFF Delay SECA08485 Orifice Size and Manifold Pressures In wc for Gas Input Rate A08219 A08219A Service and Maintenance Procedures IntroductionCare and Maintenance Carbon Monoxide Poisoning and Fire HazardWiring Diagram Blower Motor and Wheel Cleaning AND/OR Replacing AIR FilterFilter Size Information IN. / MM Cleaning Heat Exchanger Unit Damage HazardSequence of Operation Igniter Position-Top View58CT Single-Speed Cooling Single-Stage Thermostat and Two-Speed Cooling Adaptive ModeThermidistat Mode Continuous Blower Mode Wiring DiagramsTroubleshooting Troubleshooting Guide 2-Speed KitAdapter Chimneyin Usedswitch Shutoffvent Blocked Catalog No58CT---10SI