Carrier 58CTA/CTX instruction manual START-UP, ADJUSTMENT, and Safety Check, General, Burn Hazard

Page 34

58CT

A04129

Fig. 50 - Knockout Pulled Loose

A04130

Fig. 51 - Hammer and Screwdriver Used for Knockout

A04131

Fig. 52 - Remove Knockout with Hammer

!CAUTION

BURN HAZARD

Failure to follow this caution may cause personal injury.

Hot vent pipe is within reach of small children when installed in downflow position.

See the following instruction.

An accessory Vent Guard Kit, KGAVG0101DFG is REQUIRED for downflow applications for use where the vent exits through the lower portion of the furnace casing door. Refer to the Vent Guard Kit Instructions for complete details.

The horizontal portion of the venting system shall slope upwards not less than 1/4-in. per linear ft. (6 mm/.3 M) from the furnace to the vent and shall be rigidly supported every 5 ft. (1.5 M) or less with metal hangers or straps to ensure there is no movement after installation.

SIDEWALL VENTING

This furnace is not approved for direct sidewall horizontal venting.

In the U.S.: Per section 10.3.4 of the NFPA 54 / ANSI Z223.1-2006, any listed mechanical venter may be used, when approved by the authority having jurisdiction.

In Canada: Per section 8.24.2 of the CAN/CSA-B149.1-05, any listed mechanical venter may be used, when approved by the authority having jurisdiction.

Select the listed mechanical venter to match the Btuh input of the furnace being vented. Follow all manufacturer’s installation requirements for venting and termination included with the listed mechanical venter.

START-UP, ADJUSTMENT, AND SAFETY

CHECK

Step 1 — General

!WARNING

FIRE HAZARD

Failure to follow this warning could result in personal injury, death and/or property damage.

This furnace is equipped with manual reset limit switches in the gas control area. The switches open and shut off power to the gas valve if a flame roll-out or overheating condition occurs in the gas control area. DO NOT bypass the switches. Correct problem before resetting the switches.

1.Maintain 115-v wiring and ground. Improper polarity will result in rapid flashing LED and no furnace operation.

2.Make thermostat wire connections at the 24-v terminal block on the furnace control. Failure to make proper con- nections will result in improper operation. (See Fig. 23.)

3.Gas supply pressure to the furnace must be greater than 4.5-in. wc (0.16 psig ) but not exceed 14-in. wc (0.5 psig).

!CAUTION

CUT HAZARD

Failure to follow this caution may result in personal injury.

Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing, safety glasses and gloves when handling parts and servicing furnaces.

4.Check all manual-reset switches for continuity.

5.Install blower compartment door. Door must be in place to operate furnace.

6.Setup switch descriptions The 2 stage furnace has DIP switches used to select thermostat staging and blower off delay timings. For switch locations on Furnace control board, See Fig. 33 and 57.

7.Setup switch descriptions - See Table 10.

34

Image 34
Contents Ama Furnace Reliability Hazard Safety ConsiderationsCUT Hazard Dimensions IntroductionClearances to Combustibles Electrostatic Discharge ESD Precautions Procedure Codes and StandardsGeneral LocationCarbon Monoxide Poisoning and Unit Damage Hazard Property Damage Hazard FIRE, Injury or Death HazardFire Hazard Location Relative to Cooling EquipmentCarbon Monoxide Poisoning Hazard AIR for Combustion VentilationFurnace Corrosion Hazard Outdoor Combustion Air MethodAir for Combustion, Ventilation, and Dilution for Outdoors Installation Upflow InstallationFIRE, EXPLOSION, and Carbon Monoxide Poisoning Hazard Downflow InstallationHorizontal Installation Suspended Furnace SupportPlatform Furnace Support Roll-Out ProtectionOpening dimensions In. mm Duct FlangesHorizontal Unit Suspension General Requirements Filter Arrangement Carbon Monoxide Poisoning HazardAIR Ducts Ductwork Acoustical Treatment Supply Air ConnectionsFurnace Air Delivery CFM With FilterSpeed External Static Pressure IN. WC Size Inlet Return Air Connections Air Delivery CFM With Filter*Downflow Furnaces GAS Piping Fire or Explosion HazardUpflow Return Air Configurations and Restrictions Maximum Capacity of Pipe Furnace Damage HazardElectrical Shock and Fire Hazard WiringElectrical Connections Electrical Shock Hazard Furnace MAY not Operate HazardBOX Relocation Electrical DataElectrical Connection to J-BOX Electrical Box on Furnace Casing Side. See Fig Power Cord Installation in Furnace J-BOXBX. Cable Installation in Furnace J-BOX Fire or Electrical Shock HazardTwo-Stage Furnace with Two-Speed Air Conditioner See notes 2, 11, and 12 on the page following these figures Accessories VentingGeneral Venting Requirements Masonry Chimney RequirementsChimney Inspection Chart Internal Area of Chimney Appliance Application RequirementsVent Height Upflow Application-Vent Elbow Up Downflow Application-Vent Elbow Up then Left Horizontal Left Application Vent Elbow Left Furnace Vent Diameter Vent Height Orientation INPUTBTUH/HRUsing Tin Snips to Cut Tie Points General START-UP, ADJUSTMENT, and Safety CheckBurn Hazard Stage Furnace Setup Switch Description Start-Up ProceduresAdjustments Fire and Explosion HazardAltitude Derate Multiplier for U.S.A Redundant Automatic Gas Control ValveOrifice Hole Furnace Overheating Hazard Gas Rate cu ft. /hrSeconds Size of Test Dial For Revolution Speed Selection Color Speed AS ShippedStage Furnace Blower OFF delay Setup Switch Check Safety ControlsChecklist Desired Heating Mode Setup Switch Blower OFF Delay SECA08485 Orifice Size and Manifold Pressures In wc for Gas Input Rate A08219 A08219A Service and Maintenance Procedures IntroductionCare and Maintenance Carbon Monoxide Poisoning and Fire HazardWiring Diagram Filter Size Information IN. / MM Cleaning AND/OR Replacing AIR FilterBlower Motor and Wheel Cleaning Heat Exchanger Unit Damage HazardSequence of Operation Igniter Position-Top View58CT Thermidistat Mode Single-Stage Thermostat and Two-Speed Cooling Adaptive ModeSingle-Speed Cooling Troubleshooting Wiring DiagramsContinuous Blower Mode Troubleshooting Guide 2-Speed KitAdapter Chimneyin Usedswitch Shutoffvent Blocked Catalog No58CT---10SI