Carrier 58CTA/CTX instruction manual Orifice Hole

Page 37

b.Run for 3 minutes in low-heat operation.

c.Measure time (in sec) for gas meter to complete 1 revolu- tion and note reading. The 2 or 5 cubic feet dial provides a more accurate measurement of gas flow.

BURNER

ORIFICE

A93059

Fig. 54 - Orifice Hole

d.Refer to Table 12 for cubic ft. of gas per hr.

e.Multiply gas rate cu ft. /hr by heating value (Btuh/cu ft. ) to obtain input. If clocked rate does not match required input from Step 1, increase manifold pressure to increase input or decrease manifold pressure to decrease input. Repeat steps b through e until correct low heat input is achieved. Re-install low-heat regulator seal cap on gas valve.

5.Set low-heat temperature rise. The furnace must operate within the temperature rise ranges specified on the furnace rating plate. Do not exceed temperature rise ranges spe- cified on unit rating plate for high-and low-heat. Determine the temperature rise as follows:

NOTE: Blower access door must be installed when taking temperature rise reading. Leaving blower access door off will result in incorrect temperature measurements.

!WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury or death.

Disconnect 115-v electrical power before changing speed tap.

a.Verify unit is running in low heat per Step 3. Place ther- mometers in return and supply ducts as close to furnace as possible. Be sure thermometers do not see radiant heat from heat exchangers. Radiant heat affects temperature rise readings. This practice is particularly important with straight-run ducts.

b.When thermometer readings stabilize, subtract return-air temperature from supply-air temperature to determine air temperature rise.

NOTE: If the temperature rise is outside this range, first check: (1.) Gas input for low heat operation.

(2.) Derate for altitude if applicable.

(3.) Return and supply ducts for excessive restrictions causing static pressures greater than 0.50-in. wc.

58CT

37

Image 37
Contents Ama Furnace Reliability Hazard Safety ConsiderationsCUT Hazard Introduction DimensionsClearances to Combustibles Codes and Standards Electrostatic Discharge ESD Precautions ProcedureGeneral LocationCarbon Monoxide Poisoning and Unit Damage Hazard Fire Hazard FIRE, Injury or Death HazardProperty Damage Hazard Location Relative to Cooling EquipmentFurnace Corrosion Hazard AIR for Combustion VentilationCarbon Monoxide Poisoning Hazard Outdoor Combustion Air MethodAir for Combustion, Ventilation, and Dilution for Outdoors Upflow Installation InstallationHorizontal Installation Downflow InstallationFIRE, EXPLOSION, and Carbon Monoxide Poisoning Hazard Suspended Furnace SupportRoll-Out Protection Platform Furnace SupportDuct Flanges Opening dimensions In. mmHorizontal Unit Suspension AIR Ducts Filter Arrangement Carbon Monoxide Poisoning HazardGeneral Requirements Ductwork Acoustical Treatment Supply Air ConnectionsFurnace Air Delivery CFM With FilterSpeed External Static Pressure IN. WC Size Inlet Downflow Furnaces Air Delivery CFM With Filter*Return Air Connections GAS Piping Fire or Explosion HazardUpflow Return Air Configurations and Restrictions Furnace Damage Hazard Maximum Capacity of PipeElectrical Connections Electrical Shock Hazard WiringElectrical Shock and Fire Hazard Furnace MAY not Operate HazardBOX Relocation Electrical DataElectrical Connection to J-BOX BX. Cable Installation in Furnace J-BOX Power Cord Installation in Furnace J-BOXElectrical Box on Furnace Casing Side. See Fig Fire or Electrical Shock HazardTwo-Stage Furnace with Two-Speed Air Conditioner See notes 2, 11, and 12 on the page following these figures Venting AccessoriesMasonry Chimney Requirements General Venting RequirementsChimney Inspection Chart Internal Area of Chimney Appliance Application RequirementsVent Height Upflow Application-Vent Elbow Up Downflow Application-Vent Elbow Up then Left Horizontal Left Application Vent Elbow Left Diameter Vent Height Orientation INPUTBTUH/HR Furnace VentUsing Tin Snips to Cut Tie Points General START-UP, ADJUSTMENT, and Safety CheckBurn Hazard Adjustments Start-Up ProceduresStage Furnace Setup Switch Description Fire and Explosion HazardRedundant Automatic Gas Control Valve Altitude Derate Multiplier for U.S.AOrifice Hole Furnace Overheating Hazard Gas Rate cu ft. /hrSeconds Size of Test Dial For Revolution Color Speed AS Shipped Speed SelectionChecklist Check Safety ControlsStage Furnace Blower OFF delay Setup Switch Desired Heating Mode Setup Switch Blower OFF Delay SECA08485 Orifice Size and Manifold Pressures In wc for Gas Input Rate A08219 A08219A Introduction Service and Maintenance ProceduresCarbon Monoxide Poisoning and Fire Hazard Care and MaintenanceWiring Diagram Filter Size Information IN. / MM Cleaning AND/OR Replacing AIR FilterBlower Motor and Wheel Unit Damage Hazard Cleaning Heat ExchangerIgniter Position-Top View Sequence of Operation58CT Thermidistat Mode Single-Stage Thermostat and Two-Speed Cooling Adaptive ModeSingle-Speed Cooling Troubleshooting Wiring DiagramsContinuous Blower Mode Troubleshooting Guide 2-Speed KitAdapter Chimneyin Usedswitch Shutoffvent Blocked Catalog No58CT---10SI