NOTE: Using the 2 cu. ft. or 5 cu. ft. gas meter dial provides greater accuracy in verifying gas input rate.
If clocked rate does not match required input from Step 1, increase manifold pressure to increase input or decrease manifold pressure to decrease input. Repeat steps b through e until correct high heat input is achieved.
8.Set high heat temperature rise.
Jumper R to W/W1 and W2 to check
Determine the air temperature rise as follows:
NOTE: Blower access door must be installed when taking temperature rise reading. Leaving blower access door off will result in incorrect temperature measurements.
a.Verify the furnace is operating in high heat per Step 6. Place thermometers in return and supply ducts as close to furnace as possible. Be sure thermometers do not see radiant heat from heat exchangers. Radiant heat affects temperature rise readings. This practice is particularly im- portant with
b.When thermometer readings stabilize, subtract
NOTE: If the temperature rise is outside this range, first check: (1.) Gas input for
(2.) Derate for altitude if applicable.
(3.) Return and supply ducts for excessive restrictions causing static pressures greater than
(4.) Dirty filter.
c.Adjust air temperature rise by adjusting blower speed. In- crease blower speed to reduce temperature rise. Decrease blower speed to increase temperature rise. For high heat, speed selection can be
!WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Disconnect
d.To change motor speed selection for high heat, remove blower motor lead from control
e.Repeat steps a thru e.
f.When correct high heat input rate and temperature rise is achieved, turn gas valve ON/OFF switch to OFF.
g.Release Blower Access Door switch.
h.Remove manometer or similar device from gas valve.
i.
!WARNING
FIRE HAZARD
Failure to reinstall manifold pressure tap plug in gas valve could result in personal injury, property damage or death.
Reinstall manifold pressure tap plug in gas valve to prevent gas leak.
j. Remove thermostat jumper wire from furnace control board.
k.Turn LHT switch OFF.
l.Turn gas valve ON/OFF switch to ON.
m.Proceed to Step 9, “Set Blower Off Delay” before in- stalling blower access door.
!CAUTION
FURNACE OVERHEATING HAZARD
Failure to follow this caution may result in reduced furnace life.
Recheck temperature rise. It must be within limits specified on the rating plate. Recommended operation is at the midpoint of rise range or slightly above.
9.Set Blower Off Delay
a.Remove Blower Access Door if installed.
b.Turn Dip switch 2 and 3 ON or OFF for desired blower off delay. (See Table 14 and Fig 34.)
10.Set thermostat heat anticipator.
a.Mechanical thermostat - Set thermostat heat anticipator to match the amp. draw of the electrical components in the
(2.) Remove thermostat from
(3.) Connect an amp. meter as shown in Fig. 55 across the R and W subbase terminals or R and W wires at wall.
(4.) Record amp. draw across terminals when furnace is in low heat and after blower starts.
(5.) Set heat anticipator on thermostat per thermostat in- structions and install on subbase or wall.
(6.) Turn LHT switch OFF.
(7.) Install blower access door.
b. Electronic thermostat: Set cycle rate for 3 cycles per hr.
11.Set airflow CFM for cooling
Select the desired blower motor speed lead for cooling air- flow. See Table
Table 13 – Speed Selection
COLOR | SPEED | AS SHIPPED |
White | Common | BLW |
Black | High | COOL |
Yellow | SPARE | |
Orange† | Med | SPARE |
Blue | ||
Red | Low* | LO HEAT |
*
58CT
39