13.Verify that blower wheel is centered in blower housing and set screw contacts the flat portion of the motor shaft. Loosen set screw on blower wheel and reposition if neces- sary.
14.Spin the blower wheel by hand to verify that the wheel does not rub on the housing.
15.Reinstall blower assembly in furnace.
16.Reinstall control box assembly in furnace.
!CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in shortened heat exchanger life.
Heating fan speed(s) MUST be adjusted to provide proper air temperature rise as specified on the rating plate. Recommended operation is at the midpoint of the rise range or slightly above. Refer to “SET TEMPERATURE RISE” under
NOTE: Refer to Table 13 for motor speed lead relocation if leads were not identified before disconnection.
17.Reconnect blower leads to furnace control. Refer to fur- nace wiring diagram, and connect thermostat leads if pre- viously disconnected.
18.To check blower for proper rotation:
a.Turn on electrical supply.
b.Manually close blower access door switch.
NOTE: If thermostat terminals are jumpered at the time blower access door switch is closed, blower will run for 90 sec before beginning a heating or cooling cycle.
c.Perform component
d.Verify blower is rotating in the correct direction.
19.If furnace is operating properly, RELEASE BLOWER ACCESS DOOR SWITCH. Remove any jumpers or re- connect any disconnected thermostat leads. Replace blower access door.
!WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury, or death.
Blower access door switch opens
20.Downflow or horizontal furnaces with vent pipe through furnace only:
a.Install and connect short piece of vent pipe inside furnace to existing vent.
b.Connect vent connector to vent elbow.
21.Turn on gas supply and cycle furnace through one com- plete heating and cooling cycle. Verify the furnace temper- ature rise as shown in Adjustments Section. Adjust tem- perature rise as shown in Adjustments Section. If outdoor temperature is below 70_F (21_C) turn off circuit breaker to outdoor unit before running furnace in the cooling
cycle. Turn outdoor circuit breaker on after completing cooling cycle.
CLEANING HEAT EXCHANGER
The following steps should be performed by a qualified service agency:
NOTE: If the heat exchangers get a heavy accumulation of soot and carbon, they should be replaced rather than trying to clean them thoroughly. A
If it becomes necessary to clean the heat exchangers because of dust or corrosion, proceed as follows:
1. | Turn OFF gas and electrical power to furnace. |
| |
| |||
2. | Remove outer access door. | 58CT | |
3. | Disconnect vent connector from furnace vent elbow. | ||
| |||
4. | For downflow or horizontal furnace having an internal |
| |
| vent pipe, remove internal vent pipe within the casing. |
| |
5. | Disconnect wires to the following components. Mark |
| |
| wires to aid in reconnection of (be careful when discon- |
| |
| necting wires from switches because damage may occur): |
| |
| a. Draft safeguard switch. |
| |
| b. Inducer motor. |
| |
| c. Pressure switches. |
| |
| d. Limit overtemperature switch. |
| |
| e. Gas valve. |
| |
| f. Hot surface igniter. |
| |
| g. |
| |
| h. Flame rollout switches. |
| |
6. | Remove screws that fasten the collector box assembly to |
| |
| the cell panel. Be careful not to damage the collector box. |
| |
| Inducer assembly and elbow need not be removed from |
| |
| collector box. |
| |
7. | Disconnect gas line from gas manifold. |
| |
8. | Remove the 5 screws that attach the burner assembly to |
| |
| the cell panel. The gas valve and individual burners need |
|
not be removed from support assembly. Remove NOx baffles if installed.
NOTE: Be very careful when removing burner assembly to avoid breaking igniter. See Fig. 58 and 59 for correct igniter location.
A05025
Fig. 58 - Igniter Position-Side View
49