58CT
Table 12 – Gas Rate (cu ft. /hr)
|
|
|
|
|
|
|
|
SECONDS | SIZE OF TEST DIAL | SECONDS | SIZE OF TEST DIAL | ||||
FOR 1 |
|
|
| FOR 1 |
|
|
|
REVOLUTION | 1 CU FT. | 2 CU FT. | 5 CU FT. | REVOLUTION | 1 CU FT. | 2 CU FT. | 5 CU FT. |
10 | 360 | 720 | 1800 | 50 | 72 | 144 | 360 |
11 | 327 | 655 | 1636 | 51 | 71 | 141 | 355 |
12 | 300 | 600 | 1500 | 52 | 69 | 138 | 346 |
13 | 277 | 555 | 1385 | 53 | 68 | 136 | 340 |
14 | 257 | 514 | 1286 | 54 | 67 | 133 | 333 |
15 | 240 | 480 | 1200 | 55 | 65 | 131 | 327 |
16 | 225 | 450 | 1125 | 56 | 64 | 129 | 321 |
17 | 212 | 424 | 1059 | 57 | 63 | 126 | 316 |
18 | 200 | 400 | 1000 | 58 | 62 | 124 | 310 |
19 | 189 | 379 | 947 | 59 | 61 | 122 | 305 |
20 | 180 | 360 | 900 | 60 | 60 | 120 | 300 |
21 | 171 | 343 | 857 | 62 | 58 | 116 | 290 |
22 | 164 | 327 | 818 | 64 | 56 | 112 | 281 |
23 | 157 | 313 | 783 | 66 | 54 | 109 | 273 |
24 | 150 | 300 | 750 | 68 | 53 | 106 | 265 |
25 | 144 | 288 | 720 | 70 | 51 | 103 | 257 |
26 | 138 | 277 | 692 | 72 | 50 | 100 | 250 |
27 | 133 | 267 | 667 | 74 | 48 | 97 | 243 |
28 | 129 | 257 | 643 | 76 | 47 | 95 | 237 |
29 | 124 | 248 | 621 | 78 | 46 | 92 | 231 |
30 | 120 | 240 | 600 | 80 | 45 | 90 | 225 |
31 | 116 | 232 | 581 | 82 | 44 | 88 | 220 |
32 | 113 | 225 | 563 | 84 | 43 | 86 | 214 |
33 | 109 | 218 | 545 | 86 | 42 | 84 | 209 |
34 | 106 | 212 | 529 | 88 | 41 | 82 | 205 |
35 | 103 | 206 | 514 | 90 | 40 | 80 | 200 |
36 | 100 | 200 | 500 | 92 | 39 | 78 | 196 |
37 | 97 | 195 | 486 | 94 | 38 | 76 | 192 |
38 | 95 | 189 | 474 | 96 | 38 | 75 | 188 |
39 | 92 | 185 | 462 | 98 | 37 | 74 | 184 |
40 | 90 | 180 | 450 | 100 | 36 | 72 | 180 |
41 | 88 | 176 | 439 | 102 | 35 | 71 | 178 |
42 | 86 | 172 | 429 | 104 | 35 | 69 | 173 |
43 | 84 | 167 | 419 | 106 | 34 | 68 | 170 |
44 | 82 | 164 | 409 | 108 | 33 | 67 | 167 |
45 | 80 | 160 | 400 | 110 | 33 | 65 | 164 |
46 | 78 | 157 | 391 | 112 | 32 | 64 | 161 |
47 | 76 | 153 | 383 | 116 | 31 | 62 | 155 |
48 | 75 | 150 | 375 | 120 | 30 | 60 | 150 |
49 | 73 | 147 | 367 |
|
|
|
|
c.Adjust air temperature rise by adjusting blower speed. In- crease blower speed to reduce temperature rise. Decrease blower speed to increase temperature rise. For low heat, speed selection can be low (factory setting),
d.Remove thermostat jumpers and release Blower Access Door Switch.
e.To change motor speed selection for low heat, remove blower motor lead from control
f.Repeat steps a through e.
!CAUTION
FURNACE OVERHEATING HAZARD
Failure to follow this caution may result in reduced furnace life.
Recheck temperature rise. It must be within limits specified on the rating plate. Recommended operation is at the midpoint of rise range or slightly above.
g.When correct low heat input rate and temperature rise is achieved, proceed to Step 6.
6.Adjust Manifold Pressure to Obtain High Heat Rate
a. Remove high fire regulator adjustment cap from gas valve pressure regulator.
b.Manually close blower access door switch.
c.Jumper R, W/W1 and W2 thermostat connections on control to run furnace in high heat. (See Fig. 33.)
d.d. Turn
e.
f.Leave manifold or similar device connected and proceed to Step 7.
NOTE: DO NOT set
7.Verify natural gas high heat input rate by clocking meter. NOTE: Gas valve regulator adjustment caps must be in place for proper input to be clocked.
a.Turn off all other gas appliances and pilots served by the meter.
b.Run for 3 minutes in
c.Measure time (in sec) for gas meter to complete 1 revolu- tion and note reading.
d.Refer to Table 12 for cubic ft. of gas per hr.
e.Multiply gas rate cu ft. /hr by heating value (Btuh/cu ft.) to obtain input.
38