Condensate Pump Flow Graph
| 4 | |
(metres) | 3 | |
2 | ||
Head | ||
1 | ||
| ||
| 0 |
1.5 | 2 | 2.5 | 3 | 3.5 | 4 |
Flow (l/min)
Min. radius 100mm |
|
|
|
|
|
| |
Point ‘A’ |
|
|
| Gravity Drain min. fall 3° | |||
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Note: The point of discharge from |
|
|
|
|
|
|
| the pumped length of condensate |
|
|
|
|
|
| pipe (point ‘A’) must not be below | |
|
|
| Max. Head | ||||
| Boiler |
|
| 3 metres |
|
| the level of the pump, whether |
|
|
|
|
|
| discharging direct into a drain or | |
|
|
|
|
|
|
| |
|
|
|
|
|
|
| into an additional gravity drain. |
|
|
|
|
|
|
|
|
Alternative Horizontal
Discharge
Fig. A
10mm PVC Pipe
7.0Site Requirements
7.6Condensate Drain - General
Failure to install the condensate discharge pipework correctly will affect the reliable operation of the boiler.
1.Ensure the discharge of condensate complies with any national or local regulations in force.
BS 6798 & Part H1 of the Building Regulations give further guidance.
2.If any further drain pipe is required (additional to that supplied with the boiler), it should be run in a proprietary material
e.g. PVC,
3.Metal pipework is NOT suitable for use in condensate discharge systems.
4.Any pipe fitted externally must be kept as short as possible to minimise the potential of freezing and must be insulated using waterproof material.
5.When discharging condensate into a soil stack or waste pipe the effects of existing plumbing must be considered.
7.7Condensate Disposal
1. | This boiler incorporates an automatic pumped condensate |
system. See the graph opposite for available pump flow rates. | |
2. | 3.5 metres of flexible 10mm PVC pipe are supplied with the |
boiler. 0.5 metres of this length remains coiled within the boiler | |
to allow removal of the pump assembly. This must not be | |
uncoiled to provide extra length. | |
3. | A fitting and securing clip (Fig. B) to accept the 10mm PVC |
pipe and connect to 21.5mm overflow pipe is also supplied. | |
4. | The 10mm pipe can be routed to a maximum of 3 metres |
vertically and then discharge via gravity or be routed horizontally | |
(Fig. A). A combination of vertical and horizontal runs is | |
permissible. | |
5. | The pipe must be supported, either using suitably spaced clips |
or run within larger diameter pipe. When using clips take care |
Condensate Pipe
Direct Connect
Fitting
(8.5mm I.D.)
Securing Clip
8.5mm Ø O.D.
21.5mm Ø O.D. to fit
Overflow Pipe
Fig. B
not to deform the pipe. |
6. When routing the pipe through a wall it must be suitably |
sleeved. Also the pipe must not be exposed to sources of heat, |
and should be protected in locations where it may be damaged. |
7. The pipe should be routed so that any sharp bends, dips and |
loops are avoided. A minimum radius of 100mm is |
recommended for any bends. No slope is necessary and air |
breaks are not required on the pumped part of the condensate |
run. |
8. If the boiler is fitted in an unheated location the entire length |
of condensate pipe should be treated as external, and run within |
insulated larger diameter pipe. |
© Baxi Heating UK Ltd 2011 | 17 |