Wall Thickness
10.0Installation
10.5Fitting the Standard Flue
At least
1.5°
Fig. 26
Waste
Edge of Boiler Case to Wall
Wall Thickness
(Z)= Side Exit
(X)= Rear Exit
IMPORTANT: The flue should always be installed with at least 1.5° fall from terminal to elbow, to allow condensate to run back to the boiler.
1.The standard flue is suitable for lengths 270mm minimum to 800mm maximum (measured from the edge of the flue elbow outlet).
Rear Flue: maximum wall thickness - 575mm
Side Flue: maximum wall thickness - 535mm
2.For rear exit - measure the wall thickness (Fig. 26) and to this dimension add 270mm. This dimension to be known as (X).
i.e. (X) = wall thickness + 270
3.Take the flue and mark off (X) from the terminal end as indicated in the diagram (Fig. 27).
4.For side exit - measure the distance from the edge of the boiler case to the inner face of the wall (Fig. 26) and to this dimension add the wall thickness + 280mm. This dimension to be known as (Z).
i.e. (Z) = case to wall + wall thickness + 280
5.Take the flue and mark off (Z) from the terminal end as indicated (Fig. 27).
Before cutting check your dimensions !
6.The flue tubes are fixed together. Cut through both tubes whilst resting the flue on the
NOTE: When cutting ensure the cut does not interfere with the inner flue support bracket (Fig. 27a).
Flue
Fig. 27
Inner Flue Support Bracket
Fig. 27a
30© Baxi Heating UK Ltd 2011