Mains On | Boiler On | Lockout |
LED Light | LED Light | LED Light |
(Green) (Green) (Red)
*denotes LED flashing
17.0Fault Finding
NOTE: The fan is supplied with 325 Vdc.
Fan Fault Finding should only be carried out after the boiler has been electrically isolated.
General Fault Finding should only be carried out by someone who is appropriately qualified.
Lights |
|
|
Off Off Off | YES | Go to Electrical Supply |
|
| section of the fault finding |
|
| instructions. |
Lights |
| Live & Neutral Reversed | |
* Off On | YES | ||
Incoming Live and Neutral | |||
|
| ||
|
| reversed. |
Lights |
| Go to | |
* * On | YES | ||
section of the fault finding | |||
| |||
|
| instructions. | |
|
|
|
Lights |
|
|
|
| |
On Off On | YES | Go to Ignition Lockout section |
| ||
|
| of the fault finding instructions. |
|
|
|
Lights |
|
| |||
| Go to Overheat Lockout | ||||
|
|
|
| ||
On Off | * |
| YES | ||
| section of the fault finding | ||||
|
| ||||
|
|
|
| instructions. | |
|
|
|
|
|
| Lights | * |
| Go to Fan Lockout | |
On | * | YES | |||
section of the fault finding | |||||
|
|
|
| instructions. |
Lights
On * On
Lights
* Off *
Lights
On On On
Lights
* On *
Lights
*On On
Lights
On On *
Lights
* * On
YES
YES
YES
YES
YES
YES
YES
Go to Thermistor section
of the fault finding
instructions.
Low Electrical Supply
Incoming Voltage less than
180V. Check System
Controls & System Wiring. Otherwise contact Electricity Provider.
LV Wiring Harness
Ensure the small 8 way
connector is securely plugged
into the PCB. If the fault
persists replace wiring harness.
PCB Fault
Replace PCB.
PCB Fault
Replace PCB.
PCB Fault
Replace PCB.
Go to Condensate Pump section of the fault finding instructions.