Baxi Potterton Gold FSB 30 HE manual Installation

Page 29

Edge of Boiler

Example

2m

 

 

 

Horizontal

Side Flue

Centre Line

Centre

125mm

Example

V = 55mm

EXAMPLE: If the boiler is 2 metres away from corner of wall the flue duct hole will be 55mm higher than the horizontal side flue centre line. This will maintain an approx. 1.5° backfall to the boiler. It is especially important to consider this when fitting the boiler under a work top !

10.0 Installation

Check Site Requirements before commencing.

10.1Initial Preparation & Installation

1.Remove the outer carton.

2.For the boiler to operate correctly it must be level in both planes. Place the fixing template in the proposed boiler position ensuring that it is level.

3.Mark the centre of the flue hole (rear exit).

For side exit: project the horizontal side flue centre

Hole

Template

Fig. 20

Wall Thickness

Flue Hole ø

 

 

up to 227mm

125mm core drill

up to 750mm

150mm core drill

up to 1200mm

175mm core drill

line into the corner of the room and along the wall to where the flue hole will be drilled. (Fig. 20).

The diagram (Fig. 21) shows the dimensions required to ensure any horizontal flue is installed with the correct fall to the boiler. Mark the offset (V) dimension and if required, mark the position of the gas, water and condensate pipes. Remove the template.

Backfall to the boiler, ie. 2m flue offset (V) position 55mm

4. Cut the hole for the flue (minimum diameter

125mm, see table (Fig. 20) for wall thicknesses and flue

Flue Duct Hole OffsetV (mm)

13.5

27.5

55

82.5

110 (mm)

hole diameters).

5. Complete any pipework and wiring that will be

V

0.5

1.0

2.0

3.0

4.0

(metres)

1.5°

inaccessible once the boiler is in position.

6. Undo the securing screws and remove the facia,

front door panel and top panel (see Figs. 1 & 2 on

page 6). Remove the securing screw and disengage the

pipe access panel.

 

 

 

 

 

 

10.2

Making the Water Connections

1. If desired the flow and return tails supplied with the

boiler can be fitted at this stage and secured with the

spring clips. The flow and return connections are

identified on the boiler rear panel. The flow pipe

incorporates a manual air vent.

Fig. 21

Flow Tail

Return

Tail

Transit Bracket

Gas

Connection

Hole for

Electrical

Cable

Hole for

Condensate

Drain Outlet

Fig. 22

2. Note that the seal is made by use of an ‘O’ ring,

therefore some pipe movement will be evident even

though a water tight seal has been achieved. Excessive

force could result in damage to the connection.

3. Make all soldered joints before connecting the tails

to the boiler to avoid damaging the ‘O’ rings.

4. Refit the pipe access panel.

10.3

Making the Gas Connection

1.The connection to the boiler is a 15mm tail on the gas service cock. The tail protrudes through the boiler rear panel and is protected by a transit bracket which may be removed to aid connection (see Fig. 22).

2.If solder joints are being used for the gas connection, remove the gas tap from the valve as excessive heat may damage the ‘O’ ring seal.

10.4Priming the Condensate Trap

1.Using a funnel and tube, carefully pour approximately 1 cupful (250ml) of tap water into the flue products exhaust at the terminal or flue elbow sampling point to ensure a seal is made in the trap.

© Baxi Heating UK Ltd 2011

 

29

 

Image 29
Contents FSB 30 HE Potterton Gold FSB 30 HE No 592 Natural GasScheme Members only Installer Notification GuidelinesGas Safety Installation & Use Regulations Important Installation, Commissioning, Service & RepairLegislation Codes of Practice, most recent version should be usedContents Important Information IntroductionDescription Position of Optional Integral Timer Wiring Flow Temperature Thermistor RedGeneral Layout Layout Figs , 4, 5All TRVs Shut Down ? Minute Anti-cycle Boiler OperationBoiler Operation Ipxx Technical DataCAT I 2H Dimensions and Fixings Treatment of Water Circulating Systems System DetailsWater Circulating Systems Air Vents Low Head InstallationPipework System Controls & Wiring Sealed Systems Fig Compartment Site RequirementsLocation Gas Supply Clearances Figs &16Electrical Supply 5mm Min 500mm Min For Servicing Purposes 390mmCondensate Disposal Condensate Drain GeneralSink Site Requirement± 10 from vertical Blockage or restriction of the pipe into the drainMIN FlueHorizontal Flue System Examples Flue OptionsHorizontal Flue Systems This bend is equivalent to 0.5 metreTwin & Vertical Flue Systems Vertical Flue System Examples Twin PipeTotal equivalent length 17.2 + 34.4 = 51.6 metresCDS Flue AccessoriesFlue Group B Flue Group PFor Twin Flues For Vertical Flues For Vertical Flue SystemsFor Twin Flue Systems For Roof Terminals Flue DimensionsTerminal Guard Fig Flue Deflector aPlume Displacement Kit P.D.K Plume DisplacementDetermining Permissible Lengths P.D.K This section of the flue Must be horizontal General Fitting Notes P.D.KMin metres Min .3 metres Fig. H Installation Flue Inner Flue Support Bracket Fitting the Standard FluePoints Inner Flue Support Bracket Flue Elbow Gasket Flue TrimConnection Making the Condensate DrainIntegral Programmer Making The Electrical ConnectionsCable Clamp Way Terminal Block Electrical Schematic Wiring DiagramGreen/Yellow Fuse 3.15 ATPCB Illustrated Wiring DiagramPriming the Condensate Pump Commissioning the BoilerCommissioning the Boiler Check the Operational Working Gas Inlet Pressure Completion 13.2 ‘Benchmark’ ChecklistFitting The Case Panels & Facia HandoverAnnual Servicing Servicing the BoilerAir Box Door Panel Spark Sleeve Annual Servicing InspectionEarth Combustion Box Door Panel InsulationCracks/damage. Clean with a soft brush Pipe may be removed to increase accessLock Nut Service Drain Plug Central Insulation Panel To it FigChanging Components & Preparation Flow Temperature Thermistor and Safety Thermostat FigChanging Components Clip Condensate Pump Complete aDrain the boiler see .1 paragraph 2 Check operation of the pump See SectionChanging Components Spark and Sensing Electrodes Fig Gas Valve Fig Injector Pipe FigCondensate Trap Fig Securing Nut Sensor Leads Condensate Trap Lock NutCombustion Box Door Panel Burner Support Bracket Heat Exchanger Manifold AssemblyHeat Exchanger Burner Securing Screws Key Description Short Parts ListShort Parts List Fault Finding 240V at B ? 240V at a ?240V at C ? 240V at D ?Viewed from Wire Entry end Replace Flow Switch Wires from inline Connector to PCB faultySystem full of water ? Pump running ?Rectify wiring Wiring from PCBReplace PCB Way Connector Lead from PCB to Gas Valve faulty Is there Gas at gas valve inlet ?Lights On Off Replace Stat Replace fan Lights Rectify wiring Viewed from Wire Entry end YES ‘C’ ‘D’ ‘B’‘A’ Condensing Boilers only Service Record Brooks House, Coventry Road, Warwick. CV34 4LL Comp No 6/11 Potterton

Gold FSB 30 HE specifications

The Baxi Potterton Gold FSB 30 HE is a high-efficiency system boiler designed to meet the demands of modern homes while providing exceptional performance and reliability. As part of the Baxi Potterton Gold range, this model combines advanced engineering with user-friendly features, making it a top choice for homeowners and installers alike.

One of the primary features of the Baxi Potterton Gold FSB 30 HE is its impressive efficiency rating. With an ErP rating of A for heat and a seasonal efficiency of up to 90%, this boiler not only reduces energy consumption but also helps in lowering utility bills. The high-efficiency design ensures that more of the fuel consumed is converted into usable heat, making it an environmentally friendly option.

The boiler utilizes a lightweight design, weighing in at just 30 kg, which makes it easy to transport and install. Its compact size allows for flexibility in siting, meaning it can fit comfortably in kitchen cupboards or utility rooms without taking up excessive space. The small footprint caters to property owners looking to save on installation areas while still having a powerful heating system.

In terms of technology, the Baxi Potterton Gold FSB 30 HE features an integral thermostat and a user-friendly LCD display for easy boiler operation and maintenance. This advanced control system provides homeowners with accurate temperature readings and the ability to adjust settings with ease. The built-in diagnostics feature simplifies fault-finding and allows for quick resolutions, minimizing downtime.

The boiler is also equipped with weather compensation technology, which adjusts the heating output based on the external temperature. This ensures optimal performance year-round, maintaining a comfortable environment inside the home and optimizing energy use.

Safety features are paramount in the design of the Baxi Potterton Gold FSB 30 HE. It includes a range of built-in safeguards, such as a frost protection mode and an overheat thermostat, giving users peace of mind. Moreover, it is compatible with various heating controls and can be linked to smart home systems, offering further convenience and energy-saving options.

Overall, the Baxi Potterton Gold FSB 30 HE stands out for its efficiency, compact design, and advanced technology, making it a reliable solution for domestic heating needs. With a solid reputation for quality and performance, the Gold FSB 30 HE continues to be a favored choice for those looking to invest in an effective system boiler.