Baxi Potterton Gold FSB 30 HE manual Commissioning the Boiler, Priming the Condensate Pump

Page 36
(Green Light)
© Baxi Heating UK Ltd 2011

Flue Sampling Point

Manual Air Vent

Gas Service

Cock

Fig. 35

Open

Fig. 34

DO NOT check gas pressure here

IN OUT

Fig. 36

Inlet Gas Pressure Test Point

12.0Commissioning the Boiler

12.1Commissioning the Boiler

WARNING: The PCB Control and Fan Assembly are 325 Vdc. Isolate at supply before access.

1.Reference should be made to BS:EN 12828 & 14336 when commissioning the boiler.

2.At the time of commissioning, complete all relevant sections of the Benchmark Checklist at the rear of this publications.

3.Flush the whole system using a suitable flushing agent (see Section 6.2) and vent the radiators. Check for water leaks.

4.Refill the system with inhibitor following the inhibitor manufacturer’s instructions and BS 7593 Code of Practice for Treatment of Water in Domestic Hot Water Central Heating Systems (see Section 6.2).

5.Complete the label supplied with the inhibitor and attach to the inside of the boiler case. Detail of system treatment should be added for future reference.

6.Turn the gas supply on and purge according to in GB BS 6891 and in IE I.S. 813 “Domestic Gas Installations”.

7.Turn the gas service cock anticlockwise to the ON position and check for gas tightness up to the gas valve (Fig. 34). Turn the power to the boiler ON.

IMPORTANT: The combustion for this appliance has been checked, adjusted and preset at the factory for operation on the gas type specified on the appliance data plate. No measurement of the combustion is necessary. Do not adjust the air/gas ratio valve.

8. Having checked:

•That the boiler has been installed in accordance with these instructions.

•The integrity of the flue system and the flue seals.

 

 

 

 

Central Heating

Low

 

 

 

Control Knob

High

 

 

 

(No OFF Position)

 

 

 

 

Reset Button

 

 

 

 

 

 

 

 

 

 

Reset

 

 

 

 

Mains On

 

 

 

 

 

 

 

 

(Green Light)

 

 

 

 

Burner On

 

 

 

 

(Green Light)

 

 

 

 

Flame Failure

 

 

 

 

(Red Light)

Turn the Central Heating Control Knob clockwise to increase or anticlockwise to decrease the boiler flow temperature.

The Reset Button should extinguish the Flame Failure Light and restore normal operation.

This indicates that there is electricity to the Boiler.

This indicates that the Burner has fired up and is heating your system.

If Flame Failure Light is ON. Press the Reset Button. If Flame Failure occurs persistently consult your Installer or Service Engineer.

•The integrity of the boiler combustion circuit and the relevant seals.

Proceed to put the boiler into operation as follows:

 

12.2

 

Priming the Condensate Pump

1. Using a funnel and tube, carefully pour approximately 1litre of

tap water into the flue products exhaust at the terminal or flue

elbow sampling point to fill the trap and allow the condensate

pump reservoir to fill.

2. Continue filling with water until the condensate pump

operates.

 

Condensate Pump This indicates that the Condensate Pump is running.

The pump ONLY runs when the condensate reservoir is full.

Fig. 36a

3.

Check that the condensate drain pipework is not leaking and

that it is discharging correctly to drain.

4.

See Fig. 36a for operation of LEDs on boiler facia.

 

 

36

Image 36
Contents FSB 30 HE Natural Gas Potterton Gold FSB 30 HE No 592Installer Notification Guidelines Scheme Members onlyImportant Installation, Commissioning, Service & Repair Gas Safety Installation & Use RegulationsLegislation Codes of Practice, most recent version should be usedContents Introduction DescriptionImportant Information Flow Temperature Thermistor Red Position of Optional Integral Timer WiringGeneral Layout Layout Figs , 4, 5Boiler Operation Boiler OperationAll TRVs Shut Down ? Minute Anti-cycle Technical Data CAT I 2HIpxx Dimensions and Fixings System Details Water Circulating SystemsTreatment of Water Circulating Systems Low Head Installation PipeworkAir Vents System Controls & Wiring Sealed Systems Fig Site Requirements LocationCompartment Clearances Figs &16 Gas SupplyElectrical Supply 5mm Min 500mm Min For Servicing Purposes 390mmCondensate Drain General Condensate DisposalSite Requirement Sink± 10 from vertical Blockage or restriction of the pipe into the drainFlue MINFlue Options Horizontal Flue System ExamplesHorizontal Flue Systems This bend is equivalent to 0.5 metreVertical Flue System Examples Twin Pipe Twin & Vertical Flue SystemsTotal equivalent length 17.2 + 34.4 = 51.6 metresFlue Accessories CDSFlue Group B Flue Group PFor Vertical Flues For Vertical Flue Systems For Twin Flue SystemsFor Twin Flues Flue Dimensions For Roof TerminalsTerminal Guard Fig Flue Deflector aPlume Displacement Plume Displacement Kit P.D.KDetermining Permissible Lengths P.D.K General Fitting Notes P.D.K Min metres Min .3 metresThis section of the flue Must be horizontal Fig. H Installation Fitting the Standard Flue Flue Inner Flue Support BracketInner Flue Support Bracket Flue Elbow Gasket Flue Trim PointsMaking the Condensate Drain ConnectionMaking The Electrical Connections Cable Clamp Way Terminal BlockIntegral Programmer Schematic Wiring Diagram ElectricalGreen/Yellow Fuse 3.15 ATIllustrated Wiring Diagram PCBCommissioning the Boiler Commissioning the BoilerPriming the Condensate Pump Check the Operational Working Gas Inlet Pressure 13.2 ‘Benchmark’ Checklist CompletionFitting The Case Panels & Facia HandoverServicing the Boiler Annual ServicingAnnual Servicing Inspection Air Box Door Panel Spark SleeveEarth Combustion Box Door Panel InsulationPipe may be removed to increase access Cracks/damage. Clean with a soft brushLock Nut Service Drain Plug Central Insulation Panel To it FigFlow Temperature Thermistor and Safety Thermostat Fig Changing ComponentsChanging Components & Preparation Condensate Pump Complete a ClipDrain the boiler see .1 paragraph 2 Check operation of the pump See SectionChanging Components Spark and Sensing Electrodes Fig Injector Pipe Fig Gas Valve FigCondensate Trap Fig Securing Nut Sensor Leads Condensate Trap Lock NutHeat Exchanger Manifold Assembly Heat ExchangerCombustion Box Door Panel Burner Support Bracket Burner Securing Screws Short Parts List Short Parts ListKey Description Fault Finding 240V at a ? 240V at B ?240V at C ? 240V at D ?Wires from inline Connector to PCB faulty Viewed from Wire Entry end Replace Flow SwitchSystem full of water ? Pump running ?Wiring from PCB Rectify wiringReplace PCB Way Connector Lead from PCB to Gas Valve faulty Is there Gas at gas valve inlet ?Lights On Off Replace Stat Replace fan Lights Rectify wiring Viewed from Wire Entry end ‘C’ ‘D’ ‘B’ ‘A’YES Condensing Boilers only Service Record Potterton Brooks House, Coventry Road, Warwick. CV34 4LL Comp No 6/11

Gold FSB 30 HE specifications

The Baxi Potterton Gold FSB 30 HE is a high-efficiency system boiler designed to meet the demands of modern homes while providing exceptional performance and reliability. As part of the Baxi Potterton Gold range, this model combines advanced engineering with user-friendly features, making it a top choice for homeowners and installers alike.

One of the primary features of the Baxi Potterton Gold FSB 30 HE is its impressive efficiency rating. With an ErP rating of A for heat and a seasonal efficiency of up to 90%, this boiler not only reduces energy consumption but also helps in lowering utility bills. The high-efficiency design ensures that more of the fuel consumed is converted into usable heat, making it an environmentally friendly option.

The boiler utilizes a lightweight design, weighing in at just 30 kg, which makes it easy to transport and install. Its compact size allows for flexibility in siting, meaning it can fit comfortably in kitchen cupboards or utility rooms without taking up excessive space. The small footprint caters to property owners looking to save on installation areas while still having a powerful heating system.

In terms of technology, the Baxi Potterton Gold FSB 30 HE features an integral thermostat and a user-friendly LCD display for easy boiler operation and maintenance. This advanced control system provides homeowners with accurate temperature readings and the ability to adjust settings with ease. The built-in diagnostics feature simplifies fault-finding and allows for quick resolutions, minimizing downtime.

The boiler is also equipped with weather compensation technology, which adjusts the heating output based on the external temperature. This ensures optimal performance year-round, maintaining a comfortable environment inside the home and optimizing energy use.

Safety features are paramount in the design of the Baxi Potterton Gold FSB 30 HE. It includes a range of built-in safeguards, such as a frost protection mode and an overheat thermostat, giving users peace of mind. Moreover, it is compatible with various heating controls and can be linked to smart home systems, offering further convenience and energy-saving options.

Overall, the Baxi Potterton Gold FSB 30 HE stands out for its efficiency, compact design, and advanced technology, making it a reliable solution for domestic heating needs. With a solid reputation for quality and performance, the Gold FSB 30 HE continues to be a favored choice for those looking to invest in an effective system boiler.