APC UCCS Temperature Control specifications Actuators and Positioners Pneumatic

Page 21

3.Refrigerant for the dryer shall be R-134A, or approved, non-CFC, alternate.

4.Dryers Shall be adjusted for 6,400 feet above sea level. C. Filter and PRV Station:

1.Provide a two-stage, aerosol, coalescing autodrain, submicron type air filter assembly with replaceable element, 99.99% efficient for solids and oil droplets 0.01 micron and larger at rated capacity. Sized for maximum of 1 psi drop at 80 psig inlet and rated system capacity, 10 SCFM minimum. Rated working pressure: 150 psig minimum. Furnish each stage with manual filter bypass and shutoff valves, differential pressure gauges with color-coded indications for clean/dirty filter conditions, and one spare filter element. Install with a Grade DX cartridge in the first stage and a Grade BX cartridge in the second stage. Mount the first stage upstream of the refrigerated air dryer and the second stage downstream of the dryer.

2.Provide relieving-type pressure-reducing valve suitable for temperature control service sized for rated system capacity (10 SCFM minimum). Furnish 0-30 psig control pressure gauge and a 0-50 psig pressure transmitter to be connected to Delta, on low pressure side of regulator.

3.Filter and/or PRV shall not be integral to, or mounted inside, the refrigerated air dryer.

D. Desiccant Compressed Air Dryer: Where control air lines run outside and are exposed to ambient temperatures, provide a desiccant air dryer on the lines to take the dewpoint temperature down to -20°F. Provide with a color-change dessicant and a clear bowl, or other means of determining when the dessicant is spent. Provide and install isolation valves on both sides of the dryer, a bypass loop with a shutoff valve, and a manual blowdown valve adjacent to or incorporated into the cylinder.

2.07ACTUATORS AND POSITIONERS – PNEUMATIC

A. Low-pressure pneumatic actuators shall be piston-rolling diaphragm type or diaphragm type.

1.Actuator housings may be molded or die-cast zinc or aluminum. Exception: Actuator housings for control dampers or control valves may be of high impact plastic construction with ambient temperature rating of 50 to 140F minimum.

2.Actuator size and spring ranges selected shall be suitable for intended application.

a. Damper actuators shall be selected per manufacturer's recommendations to provide sufficient closeoff force and to provide smooth modulating control under design flow and pressure conditions. Furnish a separate actuator for each damper section.

b. On sequencing applications, valve and damper actuators shall be sized for a maximum of a 2 p.s.i. shift in nominal spring range with ranges selected to prevent overlap.

B. Rack-and-pinion type butterfly-valve actuator shall be totally enclosed with no external

moving parts. The actuator shall be rack and pinion type, self-draining body with spring- return to provide fail-open or fail-closed action as required. Actuators shall be sized to

JANUARY 2008

UCCS STANDARDS

15950-21

Image 21
Contents Uccs Temperature Control Specifiers Guide Section Controls Part 1 General Special Conditions Work Included Drawings and Specifications DefinitionsSubmittal Data and Shop Drawings 15950-6 15950-7 Project Record Documents Demonstration and Training Warranty Ownership of Proprietary Material Quality AssurancePart 2 Products Manufacturers 15950-13 15950-14 Duct-mounted Uccs to add preferred manufacturer here 15950-16 Control Valves AIR Tubing and Control Wiring15950-18 Local Control Panels Compressed AIR Supply Pneumatic Actuators and Positioners Pneumatic 15950-22 15950-23 15950-24 Transmitters Solid State SOLID-STATE Sensing Devices15950-26 Auxiliary Devices Electric Actuators Electric Part 3 Execution CONTROL-AIR Piping Safety ControlsControl Piping Liquids Control Wiring SCX 920 LCX 810, TCX 850, LCX 800I ALL Infinity Controllers NET ControllersInstallation and Setup Requirements 15950-34 Control Device Locations Identification Control PanelsCleanup TestingProtection 15950-38 Control Execution General Workstation Programming 15950-41 END of Section DDC Software