APC UCCS Temperature Control specifications 15950-23

Page 23

a.Pneumatic signals: 0-20 psig.

b.Electric signals: 4 to 20 mA

2.Span (calibration) and start point shall be fully adjustable.

E.Indicating Gauges and Test Ports:

1.Control-signal indicating and test gauges shall be 1-1/2", back-connected, 0 to 30 psig.

2.Test ports on the air lines connected to a differential air pressure sensor shall consist of a tee in the line with a removable cap on the branch port. Test ports on water lines connected to a differential pressure sensor shall consist of a 1/4” size, quick-connect type, quick disconnect on a branch line with a shutoff valve.

3.Permanent indicating gauges shall be furnished for all pneumatic transducer, EP, controllers and relay outputs used to position actuators, valves or PE switches. Gauges shall be in local control panels when applicable. One main (supply) air pressure gauge shall be installed in each local control panel.

F.VAV Box Controls:

[Note to Consultant: Include this information in the VAV equipment specification. It is the intent that the VAV box supplier provide a complete controls package utilizing the controller listed below. In general, the Temperature Controls Contractor should not have to provide any additional hardware, but should be required to set them up and troubleshoot problems with them if necessary.]

1.Electric VAV box controls shall be configured to meet the specified sequence of operation. All hardware necessary to meet the sequence of operation shall be pro- vided. Coordinate with supplier of VAV box. (No pneumatic)

2.The Controls Contractor shall check, calibrate and setup all VAV box controllers, and be responsible for their operation. This applies whether the controls are provided by the Mechanical Contractor as part of the VAV box or the Temperature Controls Contractor.

3.Provide assistance to the Test and Balance Contractor in making adjustments to the controls.

4.See VAV box specifications for controller information.

2.09CONTROL DEVICES - ELECTRIC A. Room Thermostats:

1.All wall-mounted, room thermostats or sensors shall have locking covers with con- cealed set point adjustment. Omit thermometers when possible.

JANUARY 2008

UCCS STANDARDS

15950-23

Image 23
Contents Uccs Temperature Control Specifiers Guide Section Controls Part 1 General Special Conditions Work Included Submittal Data and Shop Drawings Drawings and SpecificationsDefinitions 15950-6 15950-7 Project Record Documents Demonstration and Training Warranty Ownership of Proprietary Material Quality AssurancePart 2 Products Manufacturers 15950-13 15950-14 Duct-mounted Uccs to add preferred manufacturer here 15950-16 Control Valves AIR Tubing and Control Wiring15950-18 Local Control Panels Compressed AIR Supply Pneumatic Actuators and Positioners Pneumatic 15950-22 15950-23 15950-24 Transmitters Solid State SOLID-STATE Sensing Devices15950-26 Auxiliary Devices Electric Actuators Electric Part 3 Execution CONTROL-AIR Piping Safety ControlsControl Piping Liquids Control Wiring SCX 920 LCX 810, TCX 850, LCX 800I ALL Infinity Controllers NET ControllersInstallation and Setup Requirements 15950-34 Control Device Locations Identification Control PanelsProtection CleanupTesting 15950-38 Control Execution General Workstation Programming 15950-41 END of Section DDC Software