provide smooth, reliable actuation at all times. Modulating valves shall be complete with positioners by the same manufacturer. Where indicated, position switches by the same manufacturer shall be provided.
2.08AUXILIARY DEVICES - PNEUMATIC A. Room Thermostats:
1.All room thermostats shall be
adjustable sensitivity (1 to 4 psi°F minimum), and an output test port. Provide indicating set point, locking covers
2.Provide single temperature thermostats for
3.Deadband thermostats are not acceptable. For heating/cooling applications, utilize
4.Provide recessed, aspirating thermostats or conventional thermostats with locking enclosures/gaurds for all thermostats located in public areas, such as lobbies, corridors, auditoriums, gyms, pools, theaters, stores, warehouses, garages, classrooms, etc.
B.
1.Provide one or
2.Shall be open type
3.Furnish permanent indicating gauge on each pneumatic signal line to PE switches.
C.
1.Shall be
2.Provide diecast or plastic body with stainless steel trim. Minimum safe pressure shall be 30 psig at 130F ambient and 130F control air temperatures.
3.Coil voltage as required up to 120VAC
4.Provide open type
D.
1.Shall accept industry standard inputs and provide standardized outputs.
JANUARY 2008 | UCCS STANDARDS |
|