APC UCCS Temperature Control specifications 15950-22

Page 22

provide smooth, reliable actuation at all times. Modulating valves shall be complete with positioners by the same manufacturer. Where indicated, position switches by the same manufacturer shall be provided.

2.08AUXILIARY DEVICES - PNEUMATIC A. Room Thermostats:

1.All room thermostats shall be high-capacity, relay type, with pneumatic feed-back,

adjustable sensitivity (1 to 4 psi°F minimum), and an output test port. Provide indicating set point, locking covers (Allen-head screws, or other means), as noted on drawings.

2.Provide single temperature thermostats for heating-only or cooling-only applications, direct-or reverse-acting with range as required.

3.Deadband thermostats are not acceptable. For heating/cooling applications, utilize non-overlapping spring ranges on the heating/cooling devices to achieve a deadband.

4.Provide recessed, aspirating thermostats or conventional thermostats with locking enclosures/gaurds for all thermostats located in public areas, such as lobbies, corridors, auditoriums, gyms, pools, theaters, stores, warehouses, garages, classrooms, etc.

B.Pressure-Electric (PE) Switches:

1.Provide one or two-stage switch action SPDT, DPST, or DPDT, as required by application. Electrically rated for pilot duty service (125 VA minimum), and/or for motor control.

2.Shall be open type (panel-mounted) or enclosed type for remote installation. Enclosed type shall be NEMA 1, unless otherwise specified.

3.Furnish permanent indicating gauge on each pneumatic signal line to PE switches.

C.Electro-Pneumatic (EP) Solenoid Air Valves:

1.Shall be snap-acting, three-way air valve with three ports (common, N.O. and N.C.), UL-listed.

2.Provide diecast or plastic body with stainless steel trim. Minimum safe pressure shall be 30 psig at 130F ambient and 130F control air temperatures.

3.Coil voltage as required up to 120VAC

4.Provide open type (panel-mounted) or enclosed type for remote installation. Enclosed in type NEMA 1 unless otherwise specified.

D.Current-Pneumatic (I/P) and Pneumatic-Current (P/I) Transducers:

1.Shall accept industry standard inputs and provide standardized outputs.

JANUARY 2008

UCCS STANDARDS

15950-22

Image 22
Contents Uccs Temperature Control Specifiers Guide Section Controls Part 1 General Special Conditions Work Included Definitions Drawings and SpecificationsSubmittal Data and Shop Drawings 15950-6 15950-7 Project Record Documents Demonstration and Training Warranty Quality Assurance Ownership of Proprietary MaterialPart 2 Products Manufacturers 15950-13 15950-14 Duct-mounted Uccs to add preferred manufacturer here 15950-16 AIR Tubing and Control Wiring Control Valves15950-18 Local Control Panels Compressed AIR Supply Pneumatic Actuators and Positioners Pneumatic 15950-22 15950-23 15950-24 SOLID-STATE Sensing Devices Transmitters Solid State15950-26 Auxiliary Devices Electric Actuators Electric Safety Controls Part 3 Execution CONTROL-AIR PipingControl Piping Liquids Control Wiring NET Controllers SCX 920 LCX 810, TCX 850, LCX 800I ALL Infinity ControllersInstallation and Setup Requirements 15950-34 Control Device Locations Control Panels IdentificationTesting CleanupProtection 15950-38 Control Execution General Workstation Programming 15950-41 DDC Software END of Section