APC UCCS Temperature Control specifications 15950-34

Page 34

1.Not allowed.

D.Standard Nomenclature for Valve and Damper Position Description:

1.Set up the conversion table for each valve or damper control output so that 100% OPEN = open and 0% OPEN = closed.

2.For mixed-air dampers, 100% OPEN = fully open outside air damper and closed return damper.

3.For face and bypass dampers, 100% OPEN = face damper fully open and bypass damper closed. This would apply to both a face and bypass damper for a heating coil, which is normally open to the coil; and to a face and bypass damper for a evaporative cooling pad, which is normally closed to the pad.

E.Setup of Setpoints

1.The Setpoint Box in the CX and Cyberstation software shall be checked for all numerical points to be used as setpoints or any type of constant value point.

F.Setup of Inputs

1.THRESHOLDS:. The threshold shall be filled-in with the following value. Where a particular application is not listed, enter a reasonable value based on the application.

Temperature (Space, OAT, MAT, DAT, RAT, etc.) .1F

Space Static Pressure 0.01”W.C.

Duct Static Pressure 0.2W.C.

Relative Humidity (Space, OAT, MAT, DAT, RAT, etc.) 1%

G.Provide thermal-conducting compound for all sensors in thermowells.

H. Protect all points where pneumatic tubing or sensing elements come in contact with metallic surfaces by enclosing the tubing or sensor with a section of poly-tubing. This applies at such locations as duct penetrations, points where tubing is attached to ductwork, points where sensing elements come into contact with or are attached to coil frames, etc.

I.Seal all penetrations into ductwork or air-handling units with duct sealant or other means to make the installation airtight.

J.Mount all control valves so that the stem is vertical. Prior approval is required from the UCCS HVAC Shop for all installations where this cannot be achieved.

KAveraging-type sensing elements shall be firmly supported in ductwork or air-handling units using 1/2" EMT or other auxiliary support.

JANUARY 2008

UCCS STANDARDS

15950-34

Image 34
Contents Uccs Temperature Control Specifiers Guide Section Controls Part 1 General Special Conditions Work Included Definitions Drawings and SpecificationsSubmittal Data and Shop Drawings 15950-6 15950-7 Project Record Documents Demonstration and Training Warranty Quality Assurance Ownership of Proprietary MaterialPart 2 Products Manufacturers 15950-13 15950-14 Duct-mounted Uccs to add preferred manufacturer here 15950-16 AIR Tubing and Control Wiring Control Valves15950-18 Local Control Panels Compressed AIR Supply Pneumatic Actuators and Positioners Pneumatic 15950-22 15950-23 15950-24 SOLID-STATE Sensing Devices Transmitters Solid State15950-26 Auxiliary Devices Electric Actuators Electric Safety Controls Part 3 Execution CONTROL-AIR PipingControl Piping Liquids Control Wiring NET Controllers SCX 920 LCX 810, TCX 850, LCX 800I ALL Infinity ControllersInstallation and Setup Requirements 15950-34 Control Device Locations Control Panels IdentificationTesting CleanupProtection 15950-38 Control Execution General Workstation Programming 15950-41 DDC Software END of Section