APC UCCS Temperature Control specifications Actuators Electric

Page 28

I. Refrigerant Vapor Sensor: Analyzer shall be microprocessor-based and employ infrared (lR) sensor technology, to provide sensing down to one (1) part per million (ppm) and shall be chemical-compound-specific and calibrated for either refrigerant R-11, R-12, R-22, R- 123, R-134a, or other refrigerant as required by the chiller system. Any installed unit can be switched to monitor, at a future date, another refrigerant type by replacing one component and recalibrating (i.e. R-11 to R-123, etc.). Initial alarm output setting shall comply with recommended Allowable Exposure Level (AEL). Adjustable, three (3)-level alarm for each point, shall be supplied with common alarm output contacts. Provide local digital indication of refrigerant concentration in ppm (microprocessor shall identify sample point and ppm of alarm by flashing display.) Unit shall have self-diagnostics, and supply contacts for a common malfunction output. Loss of sample flow at either sample or ZERO line shall indicate system malfunction.

Unit shall have a sensitivity of 1 ppm, resolution of 1 ppm, noise rating less than .5 ppm, and drift less than .5 ppm to the calibrated refrigerant.

The unit shall be enclosed in a NEMA-4, metal, wall-mount enclosure. Auto-zero calibra- tion shall be initiated at one hour intervals (factory set), or manually at the monitor, and shall be accomplished by drawing air from an uncontaminated air source. Include built-in sample pump and differential pressure flow switch for low-flow indication. Provide 4-20 mA dc analog output of refrigerant level for input into Direct Digital Control (DDC) or Building Management System (ABMS). Unit shall be insensitive to vibration, temperature variations, and shall have a provision for continuous sampling. Intermittent dump and purge, and batch-type sampling with long response times shall not be acceptable. Response time shall be twenty (20) seconds. Malfunction relay is energized due to flow loss or electrical malfunction.

The system shall be provided with a relay board, with dry contacts for each channel, to initiate output signals for three (3) concentration-level alarms at the local panel, the inter- face to the DDC or BMS, and the building ventilation system. Alarm levels will be pro- vided at the TLV-TWA levels of - 1st Level, 200 ppm; 2nd Level, 300 ppm; 3rd Level 500 ppm. The third level shall activate the warning horns and ventilation fans. Provide dry alarm contacts for each alarm level for interface to the DDC and Fire Alarm System.

Unit must be factory calibrated. No field calibration is acceptable at time of installation.

Maintenance & Calibration: No calibration shall be required for a period of one (1) year from date of shipment. Zero-filter and end-of-line filters should be replaced every three (3) to six (6) months or sooner, based on usage. Provide four (4) extra filters of each type.

2.13ACTUATORS - ELECTRIC

A.Electric actuators are acceptable. HVAC Shop will pre-approve.

B.Actuator size and rating shall be suitable for intended application.

1.Damper actuators shall be selected per manufacturer's recommendations to provide sufficient close-off force to effectively seal damper. Modulating actuators shall

JANUARY 2008

UCCS STANDARDS

15950-28

Image 28
Contents Uccs Temperature Control Specifiers Guide Section Controls Part 1 General Special Conditions Work Included Definitions Drawings and SpecificationsSubmittal Data and Shop Drawings 15950-6 15950-7 Project Record Documents Demonstration and Training Warranty Quality Assurance Ownership of Proprietary MaterialPart 2 Products Manufacturers 15950-13 15950-14 Duct-mounted Uccs to add preferred manufacturer here 15950-16 AIR Tubing and Control Wiring Control Valves15950-18 Local Control Panels Compressed AIR Supply Pneumatic Actuators and Positioners Pneumatic 15950-22 15950-23 15950-24 SOLID-STATE Sensing Devices Transmitters Solid State15950-26 Auxiliary Devices Electric Actuators Electric Safety Controls Part 3 Execution CONTROL-AIR PipingControl Piping Liquids Control Wiring NET Controllers SCX 920 LCX 810, TCX 850, LCX 800I ALL Infinity ControllersInstallation and Setup Requirements 15950-34 Control Device Locations Control Panels IdentificationTesting CleanupProtection 15950-38 Control Execution General Workstation Programming 15950-41 DDC Software END of Section