I. Low-voltage (24V or less) AC or DC wiring shall not be run in conduit containing 120 VAC wiring.

J.Infinet Communication Wiring:

1.Splicing is not acceptable.

2.Label all junction boxes. Labels provided by the UCCS HVAC Shop

K.Label all temperature control wiring and pneumatic tubing junction box covers with an adhesive backed water proof flexible mylar label with the letters T/C using an orange background with black letters to differentiate them from junction boxes installed by the electrical and fire alarm contractor. The labels shall be 3” by 3’’.

L.Use proper size wire nut type connectors on all sensor wiring. Crimp connectors are not allowed on sensor wiring.

3.04DELTA CONTROLLERS verify following specs with sole source provider: Setpoint.

A. NET CONTROLLERS

1.The Controls contractor shall follow the specifications shown in the Delta Hardware Installation Guide unless stated otherwise herein.

2.All Delta DDC controllers shall be connected to the existing university Delta

network.

3.Operating Delta controllers that are not connected to the university Delta network shall not be accepted.

4.Delta net controllers shall be installed in a KELE RET2826 OR, RET4230 OR cabinet.

5.Install Minimum 650VA UPS in Separate Panel to Feed net Controller.

Manufacturer: APC 650 VA****move to manf.list

B.SCX 920 LCX 810, TCX 850, LCX 800I (ALL INFINITY CONTROLLERS)

1.The Controls contractor shall follow the specifications shown in the Delta Hardware Installation Guide unless stated otherwise herein.

2.Controller Power shall have a separate disconnect (or fuse) for each controller.

3.All controllers will be connected for 24VAC, or 120V.

4.All digital outputs will have a relay to operate the device

5.Only Two pair of communication wires shall be connected to the communication

JANUARY 2008

UCCS STANDARDS

15950-32

Image 32
Contents Uccs Temperature Control Specifiers Guide Section Controls Part 1 General Special Conditions Work Included Submittal Data and Shop Drawings Drawings and SpecificationsDefinitions 15950-6 15950-7 Project Record Documents Demonstration and Training Warranty Quality Assurance Ownership of Proprietary MaterialPart 2 Products Manufacturers 15950-13 15950-14 Duct-mounted Uccs to add preferred manufacturer here 15950-16 AIR Tubing and Control Wiring Control Valves15950-18 Local Control Panels Compressed AIR Supply Pneumatic Actuators and Positioners Pneumatic 15950-22 15950-23 15950-24 SOLID-STATE Sensing Devices Transmitters Solid State15950-26 Auxiliary Devices Electric Actuators Electric Safety Controls Part 3 Execution CONTROL-AIR PipingControl Piping Liquids Control Wiring NET Controllers SCX 920 LCX 810, TCX 850, LCX 800I ALL Infinity ControllersInstallation and Setup Requirements 15950-34 Control Device Locations Control Panels IdentificationProtection CleanupTesting 15950-38 Control Execution General Workstation Programming 15950-41 DDC Software END of Section