APC UCCS Temperature Control specifications Control Wiring

Page 31

D.Provide ball valves or manifold if specified to isolate the instruments from the process.

E.Impulse Line piping for flow transmitters. The following information to be used for proper location & piping of differential pressure transmitters.

1.For liquid flow measurement taps should be made to the side of the line to avoid sediment deposits, with transmitter below the taps so gases or air will vent.

2.Make impulse lines short as possible. (Loops in impulse line piping not allowed.)

3.Slope piping at least 1 inch per foot or (per manufacture recommendations), up toward the process connection for liquid and steam.

4.Impulse lines shall run parallel so as to keep legs in balance.

5.Transmitters shall have 3-valve manifold for servicing.

6.Transmitter sensor body shall be mounted vertical so as to keep liquid leg heights equal.

G.Install the body of the transmitter or switch in such a way that the connecting points for the sensing lines are level, so that the liquid-leg heights are equal.

3.03CONTROL WIRING

A.All control and interlock wiring shall comply with the national and local electrical codes and Division 16 of these specifications. .

B.All Class 1 (line voltage) wiring shall be UL-listed in approved raceway per NEC and Division 16 requirements.

C.All low-voltage wiring shall also be in conduit. Conduit type, sizing, and installation requirements shall conform to NEC and Division 16.

D.All cable conductors shall be minimum 18 AWG TFFN stranded. Cables shall be shielded when so recommended by the manufacturer. Line-voltage power and interlock wiring conductors shall be Sized in accordance with NEC.

E.All wire insulation shall be color-coded and labeled for ease of identification.

F.All control wiring shall be installed in a neat and workmanlike manner parallel to building lines, with adequate support. Install without splices .

G.This Contractor shall terminate all control and/or interlock wiring and shall maintain updated (as-built) wiring diagrams with terminations identified at the job site.

H.Flexible metal conduits and liquid-tight, flexible metal conduits shall not exceed 3' in length

and shall be supported at each end. Flexible metal conduit less than 1/2" electrical trade size shall not be used. In areas exposed to moisture, , liquid-tight, flexible metal conduits shall be used.

JANUARY 2008

UCCS STANDARDS

15950-31

Image 31
Contents Uccs Temperature Control Specifiers Guide Section Controls Part 1 General Special Conditions Work Included Definitions Drawings and SpecificationsSubmittal Data and Shop Drawings 15950-6 15950-7 Project Record Documents Demonstration and Training Warranty Ownership of Proprietary Material Quality AssurancePart 2 Products Manufacturers 15950-13 15950-14 Duct-mounted Uccs to add preferred manufacturer here 15950-16 Control Valves AIR Tubing and Control Wiring15950-18 Local Control Panels Compressed AIR Supply Pneumatic Actuators and Positioners Pneumatic 15950-22 15950-23 15950-24 Transmitters Solid State SOLID-STATE Sensing Devices15950-26 Auxiliary Devices Electric Actuators Electric Part 3 Execution CONTROL-AIR Piping Safety ControlsControl Piping Liquids Control Wiring SCX 920 LCX 810, TCX 850, LCX 800I ALL Infinity Controllers NET ControllersInstallation and Setup Requirements 15950-34 Control Device Locations Identification Control PanelsTesting CleanupProtection 15950-38 Control Execution General Workstation Programming 15950-41 END of Section DDC Software