APC UCCS Temperature Control specifications Special Conditions

Page 3

flows, shall be by the Balancing Contractor. The Controls Contractor shall provide assis- tance to the Balancing Contractor with control adjustments as required to obtain design flows by:

1.Providing on-site instruction on the proper interfacing and operation of their equipment

2.Providing the necessary software for use with the balancer's personal computer for interfacing with their control equipment. Where proprietary equipment/gateways are

required, this equipment shall be provided for the Balancing Contractor's use.

F.Airflow stations are provided and installed by the Mechanical Contractor. The Controls Contractor shall make all necessary connections to the control system.

1.Flow meters and other control devices furnished by other contractors shall have all necessary connections to the control system made by the Controls Contractor.

1.02SPECIAL CONDITIONS

A. The University uses only Delta Controls for all DDC applications.

The University prefers to use Setpoint for all Delta products. Can we put a fixed price agree- ment with Setpoint for Delta products. Stating we have an agreed upon multiplier for pricing?

B.Currently, Setpoint is the only Delta provider in this area, providing a proximity benefit. Setpoint is also the current provider for Delta control systems providing a knowledge benefit. Other providers may bid on the Delta contol systems. Setpoint ??? Who else can install Delta? Rocky Mountain Power and Controls, with UCCS pre-approval

Westover Controls.

These companies competitively bid against each other for the entire controls portion of the project; including design, programming, component purchasing, installation, and startup.

The cost of any Delta equipment will be included in their price, along with the cost of all other items for which the Controls Contractor is responsible.

In order to perform programming, the company shall have staff who have been certified by Delta within the last 3 years.

1.03SCOPE

A. Type of System: The automatic temperature control system shall be Direct Digital Control (DDC/EMCS) with electric and pneumatic components as required.

B.All digital and analog control loops shall be microprocessor (DDC) controlled with electronic final control elements, unless otherwise shown on the Drawings.****

C.All damper and valve actuators, including those for smoke/fire or smoke dampers, shall be electric, unless specified otherwise. If field conditions appear to require another type of actuator, the University HVAC Shop shall be consulted, through the Engineer, for review

JANUARY 2008

UCCS STANDARDS

15950-3

Image 3
Contents Uccs Temperature Control Specifiers Guide Section Controls Part 1 General Special Conditions Work Included Drawings and Specifications DefinitionsSubmittal Data and Shop Drawings 15950-6 15950-7 Project Record Documents Demonstration and Training Warranty Ownership of Proprietary Material Quality AssurancePart 2 Products Manufacturers 15950-13 15950-14 Duct-mounted Uccs to add preferred manufacturer here 15950-16 Control Valves AIR Tubing and Control Wiring15950-18 Local Control Panels Compressed AIR Supply Pneumatic Actuators and Positioners Pneumatic 15950-22 15950-23 15950-24 Transmitters Solid State SOLID-STATE Sensing Devices15950-26 Auxiliary Devices Electric Actuators Electric Part 3 Execution CONTROL-AIR Piping Safety ControlsControl Piping Liquids Control Wiring SCX 920 LCX 810, TCX 850, LCX 800I ALL Infinity Controllers NET ControllersInstallation and Setup Requirements 15950-34 Control Device Locations Identification Control PanelsCleanup TestingProtection 15950-38 Control Execution General Workstation Programming 15950-41 END of Section DDC Software