APC UCCS Temperature Control specifications 15950-26

Page 26

response time. Zero and span shall be adjustable. KELE Model PTXIE, or equal. Install with isolation valve.

4.Water differential pressure transmitters for flow measurement shall have stainless steel diaphragm construction, proof-pressure of 150 psi minimum, and the accuracy shall be 0.25% of calibrated span. Overrange limit (P) and maximum static pressure shall be 3,000 psi. Transmitter shall be complete with 4-20 mA output, required mounting brackets, and five-valve manifold. Provide quick-connects on high- and low-pressure lines. Mount in a location accessible for service.

5.All differential pressure transmitters for water service shall have a differential pressure gauges mounted at the point of application. Provide tees with ½” size, quick-connect fittings (Hanson fittings) on the high- and low-pressure lines.

6.Air differential static pressure transmitters: [Note to Consultant: For critical applications where the differential pressure can drop below 0.2" W.C. - such as outside-air flowrate monitoring, or critical differential pressure control applications in laboratories - specify an Air-Monitor, Veltron II Model, differential-pressure transmitter only.]

7.All differential pressure transmitters for air shall have panel-mounted differential pressure gauges. Provide tees with removable caps on the high- and low-pressure lines.

C.Transmitter Span Selection:

1.The span of each transmitter must be carefully selected by the Contractor. Typical spans are shown above in Section 2.11 B. General selection procedures are given below.

2.The selection of the appropriate transmitter span is a crucial step in the design of a functional control system. In general, the span of the transmitter should match the normal ranges of the variable to be controlled. For example, the measurement of system pressure where the normal operating pressure is 20 psi and the peak system pressure is 35 psi, the correct span selection would be 0 to 50 psi. A 0 to 100 psi span, while workable, would be operating in the lower third of the span under normal conditions. This decreases the controller’s ability to detect small changes in pressure. Ideally, the control setpoint should be at approximately 75% of the transmitter’s span. However, expected maximum and minimum values encountered during normal operation of the system must be accounted for.

3.Particular attention to transmitter span must be taken with airflow monitoring sta- tions. The recommendations of the airflow-monitoring station supplier must be fol- lowed. Be sure to include an altitude correction factor.

4.Transmitters found operating in the lower 33% or upper 20% of their span, during normal conditions of system operation, shall be replaced, at the Contractor’s expense, with units having an acceptable span.

JANUARY 2008

UCCS STANDARDS

15950-26

Image 26
Contents Uccs Temperature Control Specifiers Guide Section Controls Part 1 General Special Conditions Work Included Submittal Data and Shop Drawings Drawings and SpecificationsDefinitions 15950-6 15950-7 Project Record Documents Demonstration and Training Warranty Quality Assurance Ownership of Proprietary MaterialPart 2 Products Manufacturers 15950-13 15950-14 Duct-mounted Uccs to add preferred manufacturer here 15950-16 AIR Tubing and Control Wiring Control Valves15950-18 Local Control Panels Compressed AIR Supply Pneumatic Actuators and Positioners Pneumatic 15950-22 15950-23 15950-24 SOLID-STATE Sensing Devices Transmitters Solid State15950-26 Auxiliary Devices Electric Actuators Electric Safety Controls Part 3 Execution CONTROL-AIR PipingControl Piping Liquids Control Wiring NET Controllers SCX 920 LCX 810, TCX 850, LCX 800I ALL Infinity ControllersInstallation and Setup Requirements 15950-34 Control Device Locations Control Panels IdentificationProtection CleanupTesting 15950-38 Control Execution General Workstation Programming 15950-41 DDC Software END of Section