terminal on the controller.

C.Expansion Modules: Delta DDC

1.The Controls contractor shall follow the specifications shown in the Delta Hardware Installation Guide unless stated otherwise herein.

2.The use of Delta DCC expansion Modules shall be pre-approved by the University HVAC Shop.

3.Expansion modules can be used only with authorizations from HVAC shop.

D.Infilinks Installation Need revision from Delta for this section

1.The Controls contractor shall follow the specifications shown in the Delta Hardware Installation Guide unless stated otherwise herein.

2.Use an Infilink I2200 to connect controllers in a building together.

3.Use an Infilink I2210 to connect controllers between buildings.

4.When Infilink I2210s are required, Controls Contractor shall supply two Infilinks.

5.To series Infilinks together communication wires shall be connected to Port 1.

6.Only 2 pair on port 1.

7.Only 1 pair on ports 2-5

3.05INSTALLATION AND SETUP REQUIREMENTS

A.Metal Oxide Varistors (MOV) on Outputs:

1.Install MOVs across all inductive loads being switched by an output from an Delta controller. This includes all relay coils, solenoid coils (E/Ps), etc. Install the MOV across the coil of the device. Use an MOV rated for the voltage of the coil.

B.Grounding the Shield on Communication Wiring:

1.The shield on communication wiring should be grounded in only one location per building. The connection point for the shield wire on LCX and SCX panels is not grounded. Connect the shield to this terminal on each panel just for consistency. The standard grounding location for each building shall be at the Infilink (see 3.03,C).

2.Tape any exposed shield wiring so that it cannot short-out on the Infilink housing or other source.

C.Splices in Communication Wiring:

JANUARY 2008

UCCS STANDARDS

15950-33

Image 33
Contents Uccs Temperature Control Specifiers Guide Section Controls Part 1 General Special Conditions Work Included Drawings and Specifications DefinitionsSubmittal Data and Shop Drawings 15950-6 15950-7 Project Record Documents Demonstration and Training Warranty Ownership of Proprietary Material Quality AssurancePart 2 Products Manufacturers 15950-13 15950-14 Duct-mounted Uccs to add preferred manufacturer here 15950-16 Control Valves AIR Tubing and Control Wiring15950-18 Local Control Panels Compressed AIR Supply Pneumatic Actuators and Positioners Pneumatic 15950-22 15950-23 15950-24 Transmitters Solid State SOLID-STATE Sensing Devices15950-26 Auxiliary Devices Electric Actuators Electric Part 3 Execution CONTROL-AIR Piping Safety ControlsControl Piping Liquids Control Wiring SCX 920 LCX 810, TCX 850, LCX 800I ALL Infinity Controllers NET ControllersInstallation and Setup Requirements 15950-34 Control Device Locations Identification Control PanelsCleanup TestingProtection 15950-38 Control Execution General Workstation Programming 15950-41 END of Section DDC Software