Mitsubishi Electronics R410A installation manual Installation location

Page 3

1. Safety precautions

1.3.Before electric work

Caution:

Be sure to install circuit breakers. If not installed, electric shock may result.

For the power lines, use standard cables of sufficient capacity. Otherwise, a short circuit, overheating, or fire may result.

When installing the power lines, do not apply tension to the cables. If the connections are loosened, the cables can snap or break and overheating or fire may result.

Be sure to ground the unit. Do not connect the ground wire to gas or water pipes, lighting rods, or telephone grounding lines. If the unit is not properly grounded, electric shock may result.

Use circuit breakers (ground fault interrupter, isolating switch (+B fuse), and molded case circuit breaker) with the specified capacity. If the circuit breaker capacity is larger than the specified capacity, breakdown or fire may result.

1.4.Before starting the test run

Caution:

Turn on the main power switch more than 12 hours before starting operation. Starting operation just after turning on the power switch can severely dam- age the internal parts. Keep the main power switch turned on during the op- eration season.

Before starting operation, check that all panels, guards and other protective parts are correctly installed. Rotating, hot, or high voltage parts can cause injuries.

Do not touch any switch with wet hands. Electric shock may result.

Do not touch the refrigerant pipes with bare hands during operation. The refrigerant pipes are hot or cold depending on the condition of the flowing refrigerant. If you touch the pipes, burns or frostbite may result.

After stopping operation, be sure to wait at least five minutes before turning off the main power switch. Otherwise, water leakage or breakdown may result.

1.5.Using R410A refrigerant air conditioners

Caution:

Use C1220 copper phosphorus, for copper and copper alloy seamless pipes, to connect the refrigerant pipes. Make sure the insides of the pipes are clean and do not contain any harmful contaminants such as sulfuric compounds, oxidants, debris, or dust. Use pipes with the specified thickness. (Refer to page

5) Note the following if reusing existing pipes that carried R22 refrigerant.

-Replace the existing flare nuts and flare the flared sections again.

-Do not use thin pipes. (Refer to page 5)

Store the pipes to be used during installation indoors and keep both ends of the pipes sealed until just before brazing. (Leave elbow joints, etc. in their packaging.) If dust, debris, or moisture enters the refrigerant lines, oil dete- rioration or compressor breakdown may result.

Use ester oil, ether oil, alkylbenzene oil (small amount) as the refrigeration oil applied to the flared sections. If mineral oil is mixed in the refrigeration oil, oil deterioration may result.

Do not use refrigerant other than R410A refrigerant. If another refrigerant is used, the chlorine will cause the oil to deteriorate.

Use the following tools specifically designed for use with R410A refrigerant. The following tools are necessary to use R410A refrigerant. Contact your nearest dealer for any questions.

 

Tools (for R410A)

Gauge manifold

 

Flare tool

Charge hose

 

Size adjustment gauge

Gas leak detector

 

Vacuum pump adapter

Torque wrench

 

Electronic refrigerant charging scale

Be sure to use the correct tools. If dust, debris, or moisture enters the refrig- erant lines, refrigeration oil deterioration may result.

Do not use a charging cylinder. If a charging cylinder is used, the composi- tion of the refrigerant will change and the efficiency will be lowered.

1.6. Precautions for salt damage–resistant model (“-BS” model)

Although this product (only “-BS” model) has been designed to be resistant to salt damage, observe the following precautions to maintain the performance of the unit. 1.Avoid installing the unit in a location where it will be exposed directly to seawater or

sea breeze.

2.If the cover panel may become covered with salt, be sure to install the unit in a location where the salt will be washed away by rainwater. (If a sunshade is in- stalled, it may be difficult for rainwater to clean the panel.)

3.To ensure that water does not collect in the base of the outdoor unit, make sure that the base is level, not at angle. Water collecting in the base of the outdoor unit could cause rust.

4.If the unit is installed in a coastal area, clean the unit with water regularly to remove any salt build-up.

5.If the unit is damaged during installation or maintenance, be sure to repair it. 6.Be sure to check the condition of the unit regularly.

7.Be sure to install the unit in a location with good drainage.

2. Installation location

2.1. Refrigerant pipe

Refer to Fig. 4-1.

2.2. Choosing the outdoor unit installation location

Avoid locations exposed to sources of heat.

Select a location from which noise emitted by the unit will not inconvenience neighbors.

Select a location permitting easy wiring and pipe access to the power source and indoor unit.

Avoid locations where combustible gases may leak, be produced, flow, or accumulate.

Note that water may drain from the unit during operation.

Select a level location that can bear the weight and vibration of the unit.

Avoid locations where the unit can be covered by snow. In areas where heavy snow fall is anticipated, special precautions such as raising the installation location or installing a hood on the air intake must be taken to prevent the snow from blocking the air intake or blowing directly against it. This can reduce the airflow and a malfunction may result.

Avoid locations exposed to oil, steam, or sulfuric gas.

Use the transportation handles of the outdoor unit to transport the unit. If the unit is carried from the bottom, hands or fingers may be pinched.

-3/16 13+1

53-5/32

(inch)

37- 13/32

2.3. Outline dimensions (Outdoor unit) (Fig. 2-1)

Constraints on indoor unit installation

You should note that indoor units that can be connected to this outdoor unit are the following models.

Indoor units with model numbers P06-P54 (PUMY-P36 : P06-P36) can be con-

nected. Refer to the table below for possible 1-8 (PUMY-P36 : 1-6) room, indoor unit combinations.

Verification

The rated capacity should be determined by observing the table below. The unit’s quantities are limited in 1 to 8 units. For the next step, make sure that the total rated capacity selected will stay in a range of 50% - 130% of the outdoor unit capacity.

PUMY-P36 18,000 - 46,800 Btu/h

PUMY-P48 24,000 - 62,400 Btu/h

6

 

 

-

 

 

7/8

23-

 

 

5/8

 

 

-9/16

 

 

14

Fig. 2-1

Indoor unit type

P06

P08

P12

P15

P18

P24

P30

P36

P48

P54

Rated capacity

6,000

8,000

12,000

15,000

18,000

24,000

30,000

36,000

48,000

54,000

(Cooling) (Btu/h)

Combinations in which the total capacity of indoor units exceeds the capacity of the outdoor unit will reduce the cooling capacity of each indoor unit below their rated cooling capacity. Thus, combine indoor units with an outdoor unit within the outdoor

unit’s capacity, if possible.

3

 

Image 3
Contents PUMY-P·NHMU -BS Contents Safety precautionsConfirmation of parts attached Installation location Ventilation and service space When installing a single outdoor unitWhen installing multiple outdoor units Windy location installation Installing the outdoor unitInstalling the refrigerant piping Precautions for devices that use R410A refrigerantConnecting pipes Fig Refrigerant pipe airtight testing method Refrigerant piping FigStop valve opening method Drainage piping work Electrical workAdditional refrigerant charge Wiring transmission cables Control box and connecting position of wiring FigWiring of main power supply and equipment capacity NET Remote Controller MA Remote ControllerSchematic Drawing of Wiring Example Fig Refrigerant collecting Pump down Test runBefore test run Test runCuestiones previas a la instalación ContenidoConfirmación de las piezas incluidas Medidas de SeguridadAntes de realizar las pruebas de funcionamiento Dimensiones exteriores Unidad exterior FigLugar de instalación Antes de la instalación eléctricaVentilación y espacio de servicio Cuando se instala una unidad exterior simpleCuando instale varias unidades exteriores Instalación de la unidad exterior Instalación de la unidad exteriorInstalación de los tubos del refrigerante Instalación en lugares expuestos al vientoTubos de conexión Fig Tubos de refrigerante Fig Prueba de fuga de gas del tubo de refrigeranteMétodo de abertura de la válvula de retención Cuidado Tubería de drenajeTrabajo eléctrico Carga adicional de refrigeranteTendido de cables de transmisión Caja de control y posición de conexión de los ca- bles FigDibujo esquemático del cableado ejemplo Fig Controlador remoto M-NET Controlador remoto MARecuperación de refrigerante vaciado Prueba de funcionamientoAntes de realizar las pruebas Prueba de funcionamientoVérification des pièces livrées Avant l’installationAvant l’installation déplacement IndexAvant la marche d’essai Emplacement d’installationAvant l’installation électrique Dimensions extérieures Appareil extérieur FigVentilation et espace de service Lors de l’installation d’un seul appareil extérieurLors de l’installation de plusieurs appareils extérieurs Installation de l’appareil extérieur Installation de l’appareil extérieurInstallation de la tuyauterie du réfrigérant Installation à un endroit exposé au vent100 120 Connexion des tuyaux FigØ9,52 3/8 Ø15,88 5/8 C, d, e, f Mm inch Numéro de modèle Couple de serrageMise en place des tuyaux de réfrigérant Fig Test d’étanchéité des tuyaux de réfrigérantComment ouvrir la vanne d’arrêt Précaution Installations électriquesMise en place du tuyau d’écoulement Charge supplémentaire de réfrigérantMise en place des câbles de transmission Schéma du câblage exemple Fig Commande à distance M-NET Commande à distance MARécupération du réfrigérant Aspiration Utilisation de la télécommandeMarche d’essai Marche d’essaiBG79U872H02

R410A specifications

Mitsubishi Electronics R410A is a highly regarded refrigerant widely used in modern HVAC systems, particularly air conditioning units. This hydrofluorocarbon (HFC) refrigerant has gained popularity due to its environmental benefits and performance characteristics that meet the demands of contemporary cooling solutions.

One of the main features of R410A is its high energy efficiency. The refrigerant operates at a higher pressure compared to its predecessor, R22, which allows for smaller, more compact systems. This higher efficiency translates to lower energy consumption during operation, making R410A an environmentally friendly option that contributes to reducing greenhouse gas emissions. The energy savings not only benefit the environment but also reduce operational costs for end-users.

R410A also boasts excellent cooling capacity. Its thermodynamic properties enable effective heat exchange, making it suitable for various applications ranging from residential air conditioners to commercial chillers. The ability to maintain effective cooling performance even at high outdoor temperatures is a crucial characteristic, especially in warmer climates where high reliability is essential.

In terms of safety, R410A is classified as non-flammable and has a low toxicity level, making it a safer choice for use in both residential and commercial installations. It carries an ozone depletion potential (ODP) of zero, aligning with global efforts to phase out substances that deplete the ozone layer. As such, it complies with various international environmental regulations, ensuring that users are contributing to a sustainable future.

Mitsubishi Electronics integrates advanced technologies in their heating and cooling systems that utilize R410A. Features such as variable speed compressors and advanced control systems optimize performance, enhancing both comfort and energy efficiency. Additionally, the systems are designed to offer quiet operation, catering to users who prioritize noise reduction in their living or working environments.

In conclusion, Mitsubishi Electronics R410A refrigerant presents a combination of high energy efficiency, excellent cooling capacity, and safety attributes, solidifying its role as a vital component in contemporary HVAC technology. By utilizing R410A, Mitsubishi Electronics demonstrates its commitment to sustainability and performance, offering solutions that cater to the diverse needs of consumers while minimizing environmental impact.