Mitsubishi Electronics R410A Refrigerant piping Fig, Refrigerant pipe airtight testing method

Page 7

4. Installing the refrigerant piping

D

AFront piping cover

C

B

4.3. Refrigerant piping (Fig. 4-4)

Remove the service panel D (three screws) and the front piping cover A (two screws) and rear piping cover B (two screws).

1Perform refrigerant piping connections for the indoor/outdoor unit when the out- door unit’s stop valve is completely closed.

2Vacuum-purge air from the indoor unit and the connection piping.

3After connecting the refrigerant pipes, check the connected pipes and the indoor

unit for gas leaks. (Refer to 4.4 Refrigerant pipe airtight testing method)

4 Vacuumize the refrigerant lines through the service port of the liquid and gas stop

valves. And then open the stop valves completely (for both the liquid and gas stop

valves). This will completely connect the refrigerant lines of the indoor and out-

door units.

• If the stop valves are left closed and the unit is operated, the compressor and

control valves will be damaged.

B Piping cover

 

 

C Stop valve

 

 

D Service panel

A

E

EBend radius : 100 mm - 150 mm

Fig. 4-4

 

 

 

B

 

 

 

 

A

 

 

C

 

H

 

 

 

 

 

 

D

 

 

 

 

E

 

 

 

 

F

 

I

 

 

 

 

 

 

 

 

C

 

 

G

 

 

 

A Stop valve <Liquid side>

 

F Sealed, same way for gas side

B Stop valve <Gas side>

 

G Pipe cover

 

C Service port

 

 

H Do not use a wrench here.

 

D Open/Close section

 

Refrigerant leakage may result.

E Local pipe

 

 

I Use two wrenches here.

 

 

 

 

Fig. 4-5

 

(1)

 

 

 

 

B

 

 

B

 

 

 

 

 

A

 

A

C

 

 

 

D

 

 

 

 

 

J

D

 

 

 

 

 

 

 

G

 

 

 

 

 

G

 

G

F

E

 

 

E

 

 

 

 

 

Type A

 

Type B

 

 

 

 

Fig. 4-6

 

(2) 1 B G

 

2

 

D

H

EI

Fig. 4-7

• Use a leak detector or soapy water to check for gas leaks at the pipe connec-

tion sections of the outdoor unit.

• Do not use the refrigerant from the unit to purge air from the refrigerant lines.

• After the valve work is completed, tighten the valve caps to the correct torque:

20 to 25 N·m [14 to 18 ft·lbs] (200 to 250 kgf·cm).

Failure to replace and tighten the caps may result in refrigerant leakage. In

addition, do not damage the insides of the valve caps as they act as a seal to

prevent refrigerant leakage.

5Use sealant to seal the ends of the thermal insulation around the pipe connection sections to prevent water from entering the thermal insulation.

4.4.Refrigerant pipe airtight testing method

(1)Connect the testing tools.

Make sure the stop valves A B are closed and do not open them.

Add pressure to the refrigerant lines through the service port C of the liquid stop valve A and the gas stop valve B.

(2)Do not add pressure to the specified pressure all at once; add pressure little by little. 1 Pressurize to 0.5 MPa [73 PSIG], wait five minutes, and make sure the

pressure does not decrease.

2 Pressurize to 1.5 MPa [218 PSIG], wait five minutes, and make sure the pres- sure does not decrease.

3 Pressurize to 3.8 MPa [550 PSIG] and measure the surrounding temperature and refrigerant pressure.

(3)If the specified pressure holds for about one day and does not decrease, the pipes have passed the test and there are no leaks.

If the surrounding temperature changes by 1°C [1.8°F], the pressure will change by about 0.01 MPa [1.5 PSIG]. Make the necessary corrections.

(4)If the pressure decreases in steps (2) or (3), there is a gas leak. Look for the source of the gas leak.

4.5. Stop valve opening method

(1)Gas side (Fig. 4-6) Type A

1 Remove the cap, then turn one-quarter rotation counter-clockwise with a flat-bladed screwdriver to complete open.

2 Check that the valves are fully open, then return the cap to its original state and tighten it down.

Type B

1 Remove the cap, pull the handle toward you and rotate 1/4 turn in a counterclock- wise direction to open.

2 Make sure that the stop valve is open completely, push in the handle and rotate the cap back to its original position.

(2)Liquid side (Fig. 4-7)

1Remove the cap and turn the valve rod counterclockwise as far as it will go with the use of a 4 mm [5/32 inch] hexagonal wrench. Stop turning when it hits the stopper.

(ø6.35 [1/4 inch]: Approximately 4.5 revolutions) (ø9.52 [3/8 inch]: Approximately 10 revolutions)

2Make sure that the stop valve is open completely, push in the handle and rotate the cap back to its original position.

A Valve

F Open position side

B Unit side

G Service port

C Handle

H Wrench hole

D Cap

I Refrigerant flow direction

E Local pipe side

J Operation section

Refrigerant pipes are protectively wrapped

The pipes can be protectively wrapped up to a diameter of ø90 mm [ø3-35/64 inch] before or after connecting the pipes. Cut out the knockout in the pipe cover follow-

ing the groove and wrap the pipes. Pipe inlet gap

Use putty or sealant to seal the pipe inlet around the pipes so that no gaps remain. (If the gaps are not closed, noise may be emitted or water and dust will enter the unit and breakdown may result.)

7

Image 7
Contents PUMY-P·NHMU -BS Safety precautions ContentsConfirmation of parts attached Installation location When installing a single outdoor unit Ventilation and service spaceWhen installing multiple outdoor units Windy location installation Installing the outdoor unitInstalling the refrigerant piping Precautions for devices that use R410A refrigerantConnecting pipes Fig Refrigerant piping Fig Refrigerant pipe airtight testing methodStop valve opening method Electrical work Drainage piping workAdditional refrigerant charge Wiring transmission cables Control box and connecting position of wiring FigNET Remote Controller MA Remote Controller Wiring of main power supply and equipment capacitySchematic Drawing of Wiring Example Fig Refrigerant collecting Pump down Test runBefore test run Test runCuestiones previas a la instalación ContenidoConfirmación de las piezas incluidas Medidas de SeguridadAntes de realizar las pruebas de funcionamiento Dimensiones exteriores Unidad exterior FigLugar de instalación Antes de la instalación eléctricaCuando se instala una unidad exterior simple Ventilación y espacio de servicioCuando instale varias unidades exteriores Instalación de la unidad exterior Instalación de la unidad exteriorInstalación de los tubos del refrigerante Instalación en lugares expuestos al vientoTubos de conexión Fig Prueba de fuga de gas del tubo de refrigerante Tubos de refrigerante FigMétodo de abertura de la válvula de retención Cuidado Tubería de drenajeTrabajo eléctrico Carga adicional de refrigeranteTendido de cables de transmisión Caja de control y posición de conexión de los ca- bles FigDibujo esquemático del cableado ejemplo Fig Controlador remoto M-NET Controlador remoto MARecuperación de refrigerante vaciado Prueba de funcionamientoAntes de realizar las pruebas Prueba de funcionamientoVérification des pièces livrées Avant l’installationAvant l’installation déplacement IndexAvant la marche d’essai Emplacement d’installationAvant l’installation électrique Dimensions extérieures Appareil extérieur FigLors de l’installation d’un seul appareil extérieur Ventilation et espace de serviceLors de l’installation de plusieurs appareils extérieurs Installation de l’appareil extérieur Installation de l’appareil extérieurInstallation de la tuyauterie du réfrigérant Installation à un endroit exposé au vent100 120 Connexion des tuyaux FigØ9,52 3/8 Ø15,88 5/8 C, d, e, f Mm inch Numéro de modèle Couple de serrageTest d’étanchéité des tuyaux de réfrigérant Mise en place des tuyaux de réfrigérant FigComment ouvrir la vanne d’arrêt Précaution Installations électriquesMise en place du tuyau d’écoulement Charge supplémentaire de réfrigérantMise en place des câbles de transmission Schéma du câblage exemple Fig Commande à distance M-NET Commande à distance MARécupération du réfrigérant Aspiration Utilisation de la télécommandeMarche d’essai Marche d’essaiBG79U872H02

R410A specifications

Mitsubishi Electronics R410A is a highly regarded refrigerant widely used in modern HVAC systems, particularly air conditioning units. This hydrofluorocarbon (HFC) refrigerant has gained popularity due to its environmental benefits and performance characteristics that meet the demands of contemporary cooling solutions.

One of the main features of R410A is its high energy efficiency. The refrigerant operates at a higher pressure compared to its predecessor, R22, which allows for smaller, more compact systems. This higher efficiency translates to lower energy consumption during operation, making R410A an environmentally friendly option that contributes to reducing greenhouse gas emissions. The energy savings not only benefit the environment but also reduce operational costs for end-users.

R410A also boasts excellent cooling capacity. Its thermodynamic properties enable effective heat exchange, making it suitable for various applications ranging from residential air conditioners to commercial chillers. The ability to maintain effective cooling performance even at high outdoor temperatures is a crucial characteristic, especially in warmer climates where high reliability is essential.

In terms of safety, R410A is classified as non-flammable and has a low toxicity level, making it a safer choice for use in both residential and commercial installations. It carries an ozone depletion potential (ODP) of zero, aligning with global efforts to phase out substances that deplete the ozone layer. As such, it complies with various international environmental regulations, ensuring that users are contributing to a sustainable future.

Mitsubishi Electronics integrates advanced technologies in their heating and cooling systems that utilize R410A. Features such as variable speed compressors and advanced control systems optimize performance, enhancing both comfort and energy efficiency. Additionally, the systems are designed to offer quiet operation, catering to users who prioritize noise reduction in their living or working environments.

In conclusion, Mitsubishi Electronics R410A refrigerant presents a combination of high energy efficiency, excellent cooling capacity, and safety attributes, solidifying its role as a vital component in contemporary HVAC technology. By utilizing R410A, Mitsubishi Electronics demonstrates its commitment to sustainability and performance, offering solutions that cater to the diverse needs of consumers while minimizing environmental impact.