Load limitations

Quick Installation Guide

March 2013

 

 

Step 3 continued...

Load limitations

The Field Communicator requires a minimum load resistance of 250 Ω within the loop to function properly. The maximum load resistance can be obtained from the following diagrams.

Non-Hazardous Installations,Explosion-proof/Flameproof (Ex d)
and Non-Sparking / EnergyInstallations
Limited Power Supply

 

Operating region
Operating
region
R(Ω): Maximum Load Resistance

R(Ω): Maximum Load Resistance

UE(V): External Power Supply VoltageU (V): External Power Supply Voltage

 

E

Intrinsically Safe Installations

R(Ω): Maximum Load Resistance

UE(V): External Power Supply Voltage

NOTE:

For Flameproof / Explosion-proof installations, the diagram is only valid if the HART load resistance is at the + side and if the - side is grounded. Otherwise, the load resistance value is limited to

435Ω.

NOTE:

Rosemount 5300 Series Transmitters with Flameproof/Explosion-proof output have a built-in barrier; no external barrier needed.

12

Image 12
Contents 00825-0100-4530,Rev EC March Quick Installation GuideSuperior Performance Guided Wave Radar Level and Interface TransmitterAbout this guide Quick Installation GuideProbes with non-conductingsurfaces Contents MarchSwitch HART revision mode Step 1: Confirm system readinessConfirm HART revision capability Confirm correct Device DriverStep 2 Mount the transmitter head/probe Tank connection with flangeThreaded tank connection Tri-Clamptank connectionStep 2 continued Bracket mounting, on wallBracket mounting, on pipe Remote housing Step 2 continuedStep 3 Connect the wiring GroundingTo connect the transmitter Terminal blockNon-intrinsicallysafe power supply Intrinsically safe power supplyHART communication Step 3 continuedTransient protection terminal block Quick Installation GuidePower PowerLoad limitations Quick Installation GuideNon-HazardousInstallations InstallationsStep 3 continued FOUNDATION fieldbus Non-intrinsicallysafe power supplyIntrinsically safe power supply RS-485with Modbus communication Power Consumption 0.5 W with HART address =Quick Installation Guide Step 3 continuedStep 4 Configure Installing the Rosemount Radar Master softwareRun Wizard 1Only for HART communicationFOUNDATION fieldbus parameters FOUNDATION fieldbus parameters FOUNDATION fieldbus parameters Setup - Modbus communication parameters 3.Click Modbus SetupSafety Instrumented Systems 4-20mA only InstallationConfiguration Alarm and saturation levels Table 3. Alarm levels and operation valuesDamping Write protectionOperation and maintenance Site acceptanceProof test Specifications InspectionReferences Visual inspectionSafety Instrumented Systems SIS Product certificationsEU conformity North-AmericancertificationsCanadian Standards Association CSA approvals Quick Installation GuideDual seal maintenance I5, IE1 Intrinsically safe and FISCO modelEuropean certifications ATEX approvalsMarch Special conditions for safe useBrazilian certifications INMETRO approvalsQuick Installation Guide Special conditions for safe useChinese certifications MarchI21 Intrinsically safe IB1 FISCO modelJapanese certifications Quick Installation GuideIC1 FOUNDATION fieldbus FISCO model N3 Type nIECEx certifications IECEx approvalsMarch Special conditions for safe useOther certifications Overfill protectionQuick Installation Guide Suitability for intended useEC Declaration of Conformity Figure 1. EC Declaration of Conformity - pageQuick Installation Guide MarchFigure 2. EC Declaration of Conformity - page Quick Installation GuideMarch Figure 3. EC Declaration of Conformity - page Quick Installation GuideMarch Quick Installation Guide 00825-0100-453000825-0100-4530,Rev EC March Emerson Process Management Rosemount Measurement