March 2013 | Quick Installation Guide |
the available
Handheld HART Communicator: Fast Key Sequence [2, 1, 5]
FOUNDATION fieldbus parameters:
TRANSDUCER_1300 > VOL_VOLUME_CALC_METHOD
TRANSDUCER_1300 > VOL_IDEAL_DIAMETER
TRANSDUCER_1300 > VOL_IDEAL_LENGTH
TRANSDUCER_1300 > VOL_VOLUME_OFFSET
Click Next and the following window appears (Analog Output).
NOTE:
The
10.This step is not applicable for FOUNDATION fieldbus, the parameters are entered in the
Handheld HART Communicator: Fast Key Sequence [2, 1, 6]
For HART communication, choose Primary Variable, PV.
Specify the analog output range by setting the Upper Range Value (20 mA) and the Lower Range Value (4 mA) to the desired corresponding level values. The Alarm Mode specifies the output state when a measurement error occurs. Choose between the following:
High: 21.75 mA (standard) or 22.5 mA (Namur)
Low: 3.75 mA (standard) or 3.6 mA (Namur)
Freeze: the output current is set to the last valid value at the time when the error occurs.
Click Next.
11.Continue with Steps 2 to 5 in the Guided Setup window:
Step 2: Device specific setup might advise you to make further configurations.
Handheld HART Communicator: Fast Key Sequence [2, 1, 7, 2].
Step 3: Restart the device to make sure all configuration changes are properly activated.
Step 4: View live values from the device to verify that the transmitter works correctly.
Step 5: Make a complete backup of the device.
19