Step 1: Confirm system readiness

Quick Installation Guide

March 2013

 

 

Step 1: Confirm system readiness

Confirm HART revision capability

If using HART-based control or asset management systems, confirm the HART capability of those systems prior to transmitter installation. Not all systems are capable of communicating with the HART Revision 7 protocol.

This transmitter can be configured for either HART Revision 5 or 7.

For instructions on how to change the HART revision of your transmitter, see “Switch HART revision mode” on page 4.

Confirm correct Device Driver

Verify that the latest Device Driver (DD/DTM) is loaded on your systems to ensure proper communication.

Download the latest Device Driver from www.rosemount.com/LevelSoftware.

Rosemount 5300 device revisions and drivers

Table 1 provides the information necessary to ensure that you have the correct Device Driver and documentation for your device.

Table 1. Rosemount 5300 device revisions and files

Firmware

Find Device Driver

Review Instructions

Review Functionality

1

HART

Device

 

 

3

Version

Universal

Manual Document Number

Changes to Software

 

Revision2

 

 

Revision

 

 

 

 

2F0 and later

7

4

00809-0100-4530

See footnote 3 for list of

 

 

5

3

Rev EA

changes.

 

 

 

 

 

 

 

 

 

 

 

 

 

2A2 - 2D2

5

3

00809-0100-4530

N/A

 

Rev DA

 

 

 

 

 

 

1.Firmware version is printed on the transmitter head label, e.g. SW 2E0.

2.Device revision is printed on the transmitter head label, e.g. HART Dev Rev 4.

3.HART Revision 5 and 7 are selectable.

Switch HART revision mode

If the HART configuration tool is not capable of communicating with HART Revision 7, the Rosemount 5300 Series will load a Generic Menu with limited capability. The following procedures will switch the HART revision mode from the Generic Menu:

1.Manual Setup > Device Information > Identification > Message

To change to HART Revision 5, Enter: “HART5” in the Message field

To change to HART Revision 7, Enter: “HART7” in the Message field

4

Image 4
Contents 00825-0100-4530,Rev EC March Quick Installation GuideSuperior Performance Guided Wave Radar Level and Interface TransmitterQuick Installation Guide About this guideProbes with non-conductingsurfaces Contents MarchSwitch HART revision mode Step 1: Confirm system readinessConfirm HART revision capability Confirm correct Device DriverStep 2 Mount the transmitter head/probe Tank connection with flangeThreaded tank connection Tri-Clamptank connectionBracket mounting, on wall Step 2 continuedBracket mounting, on pipe Remote housing Step 2 continuedStep 3 Connect the wiring GroundingTo connect the transmitter Terminal blockNon-intrinsicallysafe power supply Intrinsically safe power supplyHART communication Step 3 continuedTransient protection terminal block Quick Installation GuidePower PowerLoad limitations Quick Installation GuideNon-HazardousInstallations InstallationsNon-intrinsicallysafe power supply Step 3 continued FOUNDATION fieldbusIntrinsically safe power supply RS-485with Modbus communication Power Consumption 0.5 W with HART address =Quick Installation Guide Step 3 continuedStep 4 Configure Installing the Rosemount Radar Master softwareRun Wizard 1Only for HART communicationFOUNDATION fieldbus parameters FOUNDATION fieldbus parameters FOUNDATION fieldbus parameters Setup - Modbus communication parameters 3.Click Modbus SetupInstallation Safety Instrumented Systems 4-20mA onlyConfiguration Alarm and saturation levels Table 3. Alarm levels and operation valuesDamping Write protectionSite acceptance Operation and maintenanceProof test Specifications InspectionReferences Visual inspectionSafety Instrumented Systems SIS Product certificationsEU conformity North-AmericancertificationsCanadian Standards Association CSA approvals Quick Installation GuideDual seal maintenance I5, IE1 Intrinsically safe and FISCO modelEuropean certifications ATEX approvalsMarch Special conditions for safe useBrazilian certifications INMETRO approvalsQuick Installation Guide Special conditions for safe useChinese certifications MarchI21 Intrinsically safe IB1 FISCO modelJapanese certifications Quick Installation GuideIC1 FOUNDATION fieldbus FISCO model N3 Type nIECEx certifications IECEx approvalsMarch Special conditions for safe useOther certifications Overfill protectionQuick Installation Guide Suitability for intended useEC Declaration of Conformity Figure 1. EC Declaration of Conformity - pageQuick Installation Guide MarchQuick Installation Guide Figure 2. EC Declaration of Conformity - pageMarch Quick Installation Guide Figure 3. EC Declaration of Conformity - pageMarch Quick Installation Guide 00825-0100-453000825-0100-4530,Rev EC March Emerson Process Management Rosemount Measurement