Emerson 00825-0100-4530 Rev EC manual RS-485with Modbus communication, continued

Page 14
RS-485 with Modbus communication

Quick Installation Guide

March 2013

 

 

Step 3 continued...

Type n approvals : non-sparking / energy limited power supply

Rosemount 5300 Series

Transmitter

 

 

Power

 

 

Supply

 

Fieldbus

 

Field Communicator

Modem

PC

 

 

RS-485 with Modbus communication

The 5300 Series RS-485 with Modbus communication transmitter version operates using a power supply ranging from 8 - 30 Vdc (max. rating). See the Rosemount 5300/5400 Series with HART to Modbus Converter Manual supplement (Document No. 00809-0500-4530) for details.

Power Consumption:

<0.5 W (with HART address = 1)

<1.2 W (incl. four HART slaves)

HART - Power Consumption:<1.2 W (incl. four HART slaves)Manual backgroundManual background HART + Manual backgroundManual backgroundManual backgroundManual background

120 Ω

nverter

 

 

MB

 

HARTtoModbusConverter

 

MODBUS MA

-

 

 

(RS-485)

 

MB

 

 

MODBUS MA

-

 

(RS-485)

 

-

POWER

+

 

HART

Ambients>60ºC

 

Use wiring ated

 

+

formin90ºC

 

 

 

 

 

A

If it is the last transmitter on the bus, connect the 120Ω termination resistor.

Manual background Power

Supply

120Ω

RS-485 Bus

B

120Ω

NOTE:

Rosemount 5300 Series Transmitters with Flameproof/Explosion-proof output have a built-in barrier; no external barrier needed.

14

Image 14
Contents Superior Performance Guided Wave Radar 00825-0100-4530,Rev EC MarchQuick Installation Guide Level and Interface TransmitterProbes with non-conductingsurfaces About this guideQuick Installation Guide Contents MarchConfirm HART revision capability Switch HART revision modeStep 1: Confirm system readiness Confirm correct Device DriverThreaded tank connection Step 2 Mount the transmitter head/probeTank connection with flange Tri-Clamptank connectionBracket mounting, on pipe Step 2 continuedBracket mounting, on wall Remote housing Step 2 continuedStep 3 Connect the wiring GroundingTo connect the transmitter Terminal blockHART communication Non-intrinsicallysafe power supplyIntrinsically safe power supply Step 3 continuedPower Transient protection terminal blockQuick Installation Guide PowerNon-HazardousInstallations Load limitationsQuick Installation Guide InstallationsIntrinsically safe power supply Step 3 continued FOUNDATION fieldbusNon-intrinsicallysafe power supply Quick Installation Guide RS-485with Modbus communicationPower Consumption 0.5 W with HART address = Step 3 continuedStep 4 Configure Installing the Rosemount Radar Master softwareRun Wizard 1Only for HART communicationFOUNDATION fieldbus parameters FOUNDATION fieldbus parameters FOUNDATION fieldbus parameters Setup - Modbus communication parameters 3.Click Modbus SetupConfiguration Safety Instrumented Systems 4-20mA onlyInstallation Damping Alarm and saturation levelsTable 3. Alarm levels and operation values Write protectionProof test Operation and maintenanceSite acceptance References SpecificationsInspection Visual inspectionEU conformity Safety Instrumented Systems SISProduct certifications North-AmericancertificationsDual seal maintenance Canadian Standards Association CSA approvalsQuick Installation Guide I5, IE1 Intrinsically safe and FISCO modelMarch European certificationsATEX approvals Special conditions for safe useQuick Installation Guide Brazilian certificationsINMETRO approvals Special conditions for safe useI21 Intrinsically safe Chinese certificationsMarch IB1 FISCO modelIC1 FOUNDATION fieldbus FISCO model Japanese certificationsQuick Installation Guide N3 Type nMarch IECEx certificationsIECEx approvals Special conditions for safe useQuick Installation Guide Other certificationsOverfill protection Suitability for intended useQuick Installation Guide EC Declaration of ConformityFigure 1. EC Declaration of Conformity - page MarchMarch Figure 2. EC Declaration of Conformity - pageQuick Installation Guide March Figure 3. EC Declaration of Conformity - pageQuick Installation Guide 00825-0100-4530,Rev EC March Quick Installation Guide00825-0100-4530 Emerson Process Management Rosemount Measurement