March 2013 | Quick Installation Guide |
Safety Instrumented Systems (4-20 mA only)
The following section is applicable to the Rosemount 5300
To identify a 5300
Verify the QS option code in the model code, on the label affixed to the outside of the transmitter head or
Handheld HART Communicator: Fast Key Sequence [1, 7, 8]. Verify that the
Open Rosemount Radar Master, right click on the device, and select Properties. Verify that the Safety Device (QS Option) is present
Installation
The device should be installed and configured as a level sensing device per manufacturer’s instructions. The materials must be compatible with process conditions and process fluids. No special installation is required in addition to the standard installation practices outlined in this document.
Environmental limits are available in the Rosemount 5300 Series Reference Manual (Document No.
The loop must be designed so the terminal voltage does not drop below the minimum input voltage, see values in Table 2, when the transmitter output is 22.5 mA.
Table 2. Minimum input voltage (Ui) at different currents
|
|
| Current |
| |
Hazardous approval | 3.60 mA | 3.75 mA |
| 21.75 mA | 22.50 mA |
|
| Minimum input voltage (UI) |
| ||
16 Vdc | 16 Vdc |
| 11 Vdc | 11 Vdc | |
Intrinsically Safe Installations |
| ||||
|
|
|
|
| |
|
|
|
|
|
|
20 Vdc | 20 Vdc |
| 15.5 Vdc | 15.5 Vdc | |
Installations |
| ||||
|
|
|
|
| |
|
|
|
|
|
|
Configuration
Use a
NOTE:
The Rosemount 5300 Series transmitter is not
21