Emerson 00825-0100-4530 Rev EC manual Damping, Alarm and saturation levels, Write protection

Page 22
Damping

Quick Installation Guide

March 2013

 

 

Damping

User adjusted damping affects the transmitter’s ability to respond to process changes. Therefore, the damping values + response time should not exceed the Safety loop requirements.

Alarm and saturation levels

DCS or safety logic solver should be configured to handle both High alarm and Low alarm. Table 3 identifies the alarm levels available and their operation values.1

Table 3. Alarm levels and operation values

Rosemount Alarm Level

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Normal Operation

 

 

 

 

 

3.75

 

mA1

 

 

 

 

 

 

 

21.75

 

mA2

 

4 mA

20 mA

 

 

 

 

3.9 mA

 

 

 

 

 

20.8 mA

 

 

low saturation

 

 

 

 

 

high saturation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Namur Alarm Level

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Normal Operation

 

 

 

 

 

3.6

 

mA1

 

 

 

 

 

 

 

22.5

 

mA2

 

4 mA

20 mA

 

 

 

 

3.8 mA

 

 

 

 

 

20.5 mA

 

 

low saturation

 

 

 

 

 

high saturation

1.Transmitter Failure, hardware or software alarm in Low position.

2.Transmitter Failure, hardware or software alarm in High position.

It is assumed that the current output signal is fed to a Safety Integrity Level 2 (SIL2) -compliant analog input board of a safety logic solver. For instructions on alarm level settings, see the Rosemount 5300 Series Reference Manual (Document No. 00809-0100-4530), “Analog Output (HART)” section.

NOTE:

Only the High or Low Alarm Mode can be used for the Safety Function. Do not choose Freeze Current as an error will not be announced in the current loop.

Write protection

A Rosemount 5300 transmitter can be protected from unintentional configuration changes by a password protected function. It is recommended to use write protection described in the Rosemount 5300 Series Reference Manual (Document No. 00809-0100-4530), “Write Protecting a Transmitter” section.

1)In certain cases, the transmitter does not go into the user defined alarm state. For example, in case of a short circuit, the transmitter goes into High Alarm state even if Low Alarm has been configured.

22

Image 22
Contents Superior Performance Guided Wave Radar 00825-0100-4530,Rev EC MarchQuick Installation Guide Level and Interface TransmitterQuick Installation Guide About this guideProbes with non-conductingsurfaces Contents MarchConfirm HART revision capability Switch HART revision modeStep 1: Confirm system readiness Confirm correct Device DriverThreaded tank connection Step 2 Mount the transmitter head/probeTank connection with flange Tri-Clamptank connectionBracket mounting, on wall Step 2 continuedBracket mounting, on pipe Remote housing Step 2 continuedStep 3 Connect the wiring GroundingTo connect the transmitter Terminal blockHART communication Non-intrinsicallysafe power supplyIntrinsically safe power supply Step 3 continuedPower Transient protection terminal blockQuick Installation Guide PowerNon-HazardousInstallations Load limitationsQuick Installation Guide InstallationsNon-intrinsicallysafe power supply Step 3 continued FOUNDATION fieldbusIntrinsically safe power supply Quick Installation Guide RS-485with Modbus communicationPower Consumption 0.5 W with HART address = Step 3 continuedStep 4 Configure Installing the Rosemount Radar Master softwareRun Wizard 1Only for HART communicationFOUNDATION fieldbus parameters FOUNDATION fieldbus parameters FOUNDATION fieldbus parameters Setup - Modbus communication parameters 3.Click Modbus SetupInstallation Safety Instrumented Systems 4-20mA onlyConfiguration Damping Alarm and saturation levelsTable 3. Alarm levels and operation values Write protectionSite acceptance Operation and maintenanceProof test References SpecificationsInspection Visual inspectionEU conformity Safety Instrumented Systems SISProduct certifications North-AmericancertificationsDual seal maintenance Canadian Standards Association CSA approvalsQuick Installation Guide I5, IE1 Intrinsically safe and FISCO modelMarch European certificationsATEX approvals Special conditions for safe useQuick Installation Guide Brazilian certificationsINMETRO approvals Special conditions for safe useI21 Intrinsically safe Chinese certificationsMarch IB1 FISCO modelIC1 FOUNDATION fieldbus FISCO model Japanese certificationsQuick Installation Guide N3 Type nMarch IECEx certificationsIECEx approvals Special conditions for safe useQuick Installation Guide Other certificationsOverfill protection Suitability for intended useQuick Installation Guide EC Declaration of ConformityFigure 1. EC Declaration of Conformity - page MarchQuick Installation Guide Figure 2. EC Declaration of Conformity - pageMarch Quick Installation Guide Figure 3. EC Declaration of Conformity - pageMarch 00825-0100-4530,Rev EC March Quick Installation Guide00825-0100-4530 Emerson Process Management Rosemount Measurement