Emerson 00825-0100-4530 Rev EC manual Operation and maintenance, Site acceptance, Proof test

Page 23
Site acceptance

March 2013

Quick Installation Guide

Site acceptance

After the installation and configuration, proper operation of the transmitter should be verified. A site acceptance test is therefore recommended. The proof test outlined in this section can be used for this.

Operation and maintenance

The Rosemount 5300 Series Prior-Use option must be tested at regular intervals to confirm that the overfill and empty tank protection function result in the desired system response. The following proof test is recommended. If an error is found in the safety functionality, the measuring system must be switched out of service and the process held in a safe state by means of other measures.

Proof test results and corrective actions taken must be documented at www.emersonprocess.com/rosemount/safety.

The required proof test intervals depend on the transmitter configuration and process environment. Refer to the reference manual and the Failure Modes, Effects, and Diagnostic Analysis (FMEDA) report for further information.

Proof test

This test detects approximately 95% of the possible Dangerous Undetected (DU) failures of the transmitter including the sensor element, not detected by the transmitter’s automatic diagnostics. See the Rosemount 5300 Reference Manual (Document No. 00809-0100-4530) for additional details and instructions. Prior to this test, the echo curve should be inspected to ensure that no disturbing echoes affecting the measurement performance are present in the tank.

Required tools: Field Communicator and mA meter.

1.Bypass the logic solver or take other appropriate actions to avoid false trip.

2.Disable write protection if the function is enabled.

3.Using Loop Test, enter the mA value representing a high alarm current output. Verify that the analog current reaches that value using the reference meter.

This step tests for compliance voltage problems, such as a low loop power supply voltage or increased wiring resistance.

NOTE:

Use the Handheld HART Communicator: Fast Key Sequence [2, 4, 1, 4] to perform a Loop Test. See the Rosemount 5300 Series Reference Manual (Document No. 00809-0100-4530) for additional information.

4.Using Loop Test, enter the mA value representing a low alarm current output. Verify that the analog current reaches that value using the reference meter. This step tests for possible quiescent current related failures.

5.Perform a two-point calibration check of the transmitter by applying level to two points on the probe within the measuring range1. Verify that the current output corresponds to the level input values using a known reference measurement.

This step verifies that the analog output is correct in the operating range and that the Primary Variable is properly configured.

1)For best performance, use the 4 - 20 mA range points as calibration points.

23

Image 23
Contents Level and Interface Transmitter 00825-0100-4530,Rev EC MarchQuick Installation Guide Superior Performance Guided Wave RadarProbes with non-conductingsurfaces About this guideQuick Installation Guide March ContentsConfirm correct Device Driver Switch HART revision modeStep 1: Confirm system readiness Confirm HART revision capabilityTri-Clamptank connection Step 2 Mount the transmitter head/probeTank connection with flange Threaded tank connectionBracket mounting, on pipe Step 2 continuedBracket mounting, on wall Step 2 continued Remote housingGrounding Step 3 Connect the wiringTerminal block To connect the transmitterStep 3 continued Non-intrinsicallysafe power supplyIntrinsically safe power supply HART communicationPower Transient protection terminal blockQuick Installation Guide PowerInstallations Load limitationsQuick Installation Guide Non-HazardousInstallationsIntrinsically safe power supply Step 3 continued FOUNDATION fieldbusNon-intrinsicallysafe power supply Step 3 continued RS-485with Modbus communicationPower Consumption 0.5 W with HART address = Quick Installation GuideInstalling the Rosemount Radar Master software Step 4 Configure1Only for HART communication Run WizardFOUNDATION fieldbus parameters FOUNDATION fieldbus parameters FOUNDATION fieldbus parameters 3.Click Modbus Setup Setup - Modbus communication parametersConfiguration Safety Instrumented Systems 4-20mA onlyInstallation Write protection Alarm and saturation levelsTable 3. Alarm levels and operation values DampingProof test Operation and maintenanceSite acceptance Visual inspection SpecificationsInspection ReferencesNorth-Americancertifications Safety Instrumented Systems SISProduct certifications EU conformityI5, IE1 Intrinsically safe and FISCO model Canadian Standards Association CSA approvalsQuick Installation Guide Dual seal maintenanceSpecial conditions for safe use European certificationsATEX approvals MarchSpecial conditions for safe use Brazilian certificationsINMETRO approvals Quick Installation GuideIB1 FISCO model Chinese certificationsMarch I21 Intrinsically safeN3 Type n Japanese certificationsQuick Installation Guide IC1 FOUNDATION fieldbus FISCO modelSpecial conditions for safe use IECEx certificationsIECEx approvals MarchSuitability for intended use Other certificationsOverfill protection Quick Installation GuideMarch EC Declaration of ConformityFigure 1. EC Declaration of Conformity - page Quick Installation GuideMarch Figure 2. EC Declaration of Conformity - pageQuick Installation Guide March Figure 3. EC Declaration of Conformity - pageQuick Installation Guide Emerson Process Management Rosemount Measurement Quick Installation Guide00825-0100-4530 00825-0100-4530,Rev EC March