March 2013 | Quick Installation Guide |
Site acceptance
After the installation and configuration, proper operation of the transmitter should be verified. A site acceptance test is therefore recommended. The proof test outlined in this section can be used for this.
Operation and maintenance
The Rosemount 5300 Series
Proof test results and corrective actions taken must be documented at www.emersonprocess.com/rosemount/safety.
The required proof test intervals depend on the transmitter configuration and process environment. Refer to the reference manual and the Failure Modes, Effects, and Diagnostic Analysis (FMEDA) report for further information.
Proof test
This test detects approximately 95% of the possible Dangerous Undetected (DU) failures of the transmitter including the sensor element, not detected by the transmitter’s automatic diagnostics. See the Rosemount 5300 Reference Manual (Document No.
Required tools: Field Communicator and mA meter.
1.Bypass the logic solver or take other appropriate actions to avoid false trip.
2.Disable write protection if the function is enabled.
3.Using Loop Test, enter the mA value representing a high alarm current output. Verify that the analog current reaches that value using the reference meter.
This step tests for compliance voltage problems, such as a low loop power supply voltage or increased wiring resistance.
NOTE:
Use the Handheld HART Communicator: Fast Key Sequence [2, 4, 1, 4] to perform a Loop Test. See the Rosemount 5300 Series Reference Manual (Document No.
4.Using Loop Test, enter the mA value representing a low alarm current output. Verify that the analog current reaches that value using the reference meter. This step tests for possible quiescent current related failures.
5.Perform a
This step verifies that the analog output is correct in the operating range and that the Primary Variable is properly configured.
1)For best performance, use the 4 - 20 mA range points as calibration points.
23